ABB i-bus KNX Product Manual

Manual is about: Room temperature controller

Summary of i-bus KNX

  • Page 1

    2cka001473b9482 │ 24.01.2018 product manual abb-tacteo abb i-bus ® knx tbr/u4.X.X-xx control element 4gang with rtc incl. Bau tr/u.X.X-xx room temperature controller incl. Bau.

  • Page 2

    Table of contents product manual 2cka001473b9482 │2 tabl e of contents 1 notes on the instruction manual ................................................................................................................. 9 2 safety .........................................................................

  • Page 3

    Table of contents product manual 2cka001473b9482 │3 9.4.2 adjust temperature ............................................................................................................................ 36 9.4.3 adjusting the fan speed levels .............................................................

  • Page 4

    Table of contents product manual 2cka001473b9482 │4 11.5 application "function block rtc" .................................................................................................. 71 11.5.1 control settings - general .............................................................................

  • Page 5

    Table of contents product manual 2cka001473b9482 │5 11.5.43 cooling control — control value type ............................................................................................... 92 11.5.44 cooling control — cooling type ....................................................................

  • Page 6

    Table of contents product manual 2cka001473b9482 │6 11.5.94 setpoint adjustment ......................................................................................................................... 111 11.5.95 setpoint adjustment — maximum manual increase during heating mode (0 - 9°c) .............

  • Page 7

    Table of contents product manual 2cka001473b9482 │7 11.5.138.6 colour for zone 1 (corresponds to 0%) ......................................................... 130 11.5.138.7 colour for zone 2 (starting at 1%) ................................................................. 131 11.5.138.8 threshold ...

  • Page 8

    Table of contents product manual 2cka001473b9482 │8 11.6.6.4 retriggering ..................................................................................................... 161 11.6.6.5 switch-off pre-warning .................................................................................... 161...

  • Page 9

    Notes on the instruction manual product manual 2cka001473b9482 │9 1 notes on the instruction manual please read through this manual carefully and observe the information it contains. This will assist you in preventing injuries and damage to property, and ensure both reliable operation and a long ser...

  • Page 10

    Safety product manual 2cka001473b9482 │10 2 safety the device has been constructed according to the latest valid regulations governing technology and is operationally reliable. It has been tested and left the factory in a technically safe and reliable state. However, residual hazards remain. Read an...

  • Page 11

    Safety product manual 2cka001473b9482 │11 2.2 intended use this device is a room temperature controller for decentralized flush-mounted installation. The room temperature controller is suitable for the control of a ventilator convector with a fan- coil actuator or a conventional heating and cooling ...

  • Page 12

    Safety product manual 2cka001473b9482 │12 2.4 target group / qualifications of personnel installation, commissioning and maintenance of the device must only be carried out by trained and properly qualified electrical installers. The electrical installer must have read and understood the manual and f...

  • Page 13

    Safety product manual 2cka001473b9482 │13 2.5 safety instructions danger - electric voltage! Electric voltage! Risk of death and fire due to electric voltage of 100 … 240 v. Dangerous currents flow through the body when coming into direct or indirect contact with live components. This can result in ...

  • Page 14

    Information on protection of the environment product manual 2cka001473b9482 │14 3 information on protection of the environment 3.1 environment consider the protection of the environment! Used electric and electronic devices must not be disposed of with domestic waste. – the device contains valuable ...

  • Page 15

    Setup and function product manual 2cka001473b9482 │15 4 setup and function ■ the device is designed for decentralised flush-mounted installation. ■ the device can be linked with an available actuator via knx group addresses. ■ the device (with bus coupler) can be assigned to an available switch actu...

  • Page 16

    Setup and function product manual 2cka001473b9482 │16 4.2 device overview 4.2.1 overview 1 4 2 3 fig. 1: product overview [1] support ring [1] [2] flush-mounted insert with control element [2] (firmly installed unit) [3] clamps of removal protection [3] (optional) [4] removal tool [4] (optional) 4.2...

  • Page 17

    Setup and function product manual 2cka001473b9482 │17 4.2.3 support rings the support rings are partly diffenerent from country to country. The correct support ring is supplied according to country. Country-specific support rings are for example: 1 2 3 4 fig. 3: country-specific support rings [1] vd...

  • Page 18

    Setup and function product manual 2cka001473b9482 │18 4.4 scope of supply fig. 4: scope of delivery included in the scope of delivery are: ■ support ring [1] ■ flush-mounted insert with control element [2] (firmly installed unit) ■ clamps of removal protection [3] (optional) ■ removal tool [4] (opti...

  • Page 19

    Technical data product manual 2cka001473b9482 │19 5 technical data 5.1 technical data designation value power supply: 24 v dc (via bus line) knx connection ■ bus connecting terminal, screwless: ■ line type: ■ wire stripping: 0.6 - 0.8 mm j-y(st)y, 2 x 2 x 0.8 mm 5 - 6 mm bus subscribers: 1 (≤12 ma) ...

  • Page 20

    Connection, installation / mounting product manual 2cka001473b9482 │20 6 connection, installation / mounting danger - electric voltage! Install the device only if you have the necessary electrical engineering knowledge and experience. ■ incorrect installation endangers your life and that of the user...

  • Page 21

    Connection, installation / mounting product manual 2cka001473b9482 │21 6.1 installation site for proper commissioning please observe the following points: ■ the device should be installed at a height of approximately 150 cm from the floor and 50 cm from a door frame. Fig. 6: installation site - dist...

  • Page 22

    Connection, installation / mounting product manual 2cka001473b9482 │22 ■ this also applies to installation on an exterior wall. – low outside temperatures have an effect on temperature regulation. Fig. 10: installation site - exterior wall ■ wetting the room temperature controller with fluids is to ...

  • Page 23

    Connection, installation / mounting product manual 2cka001473b9482 │23 6.2 mounting caution! The device can sustain damage when coming into contact with hard objects! The plastic parts of the device are sensitive. – pull the attachment off only with your hands. – do not lever parts off with screwdri...

  • Page 24

    Connection, installation / mounting product manual 2cka001473b9482 │24 1 3. Pull the bus line out of the flush- mounted box and connect the line to the bus connection terminal [1], see chapter 6.3 “electrical connection“ on page 26. – check that the polarity is correct! Fig. 15: connection of the bu...

  • Page 25

    Connection, installation / mounting product manual 2cka001473b9482 │25 4. To commission the device, see chapter 7 “commissioning“ on page 27. – programming is carried out via the programming button [1] on the rear of the device. – press the programming button [1]. – all leds [2] light up red. Fig. 1...

  • Page 26

    Connection, installation / mounting product manual 2cka001473b9482 │26 6.3 electrical connection bus 24 v dc 24 v dc carry out the electrical connection according to the circuit diagram. Fig. 18: connection of bus coupler and display.

  • Page 27

    Commissioning product manual 2cka001473b9482 │27 7 commissioning 7.1 software to start the device a physical address must be assigned first. The physical address is assigned and the parameters are set with the engineering tool software (ets). Note the devices are products of the knx system and meet ...

  • Page 28

    Commissioning product manual 2cka001473b9482 │28 7.1.3 assigning the group address(es) the group addresses are assigned in connection with the ets. 7.1.4 selecting the application program please contact our internet support unit (www.Busch-jaeger.Com). The application is loaded into the device via t...

  • Page 29

    Updating options product manual 2cka001473b9482 │29 8 updating options a firmware update is carried out via the knx bus by means of the ets app "knx bus update". Note the description of the update process can be downloaded via the electronic catalogue (www.Busch-jaeger-catalogue.Com). It is stored o...

  • Page 30

    Operation product manual 2cka001473b9482 │30 9 operation caution - glass breakage! The breakage of a glass plate could lead to the risk of injury. Thr glass plate consists of high-quality safety glass. Yet breakage cannot be excluded. – avoid force being applied to the glass plate. – never reach int...

  • Page 31

    Operation product manual 2cka001473b9482 │31 9.1 control elements blind relax reading 1 2 4 3 5 6 5 5 6 5 fig. 20: control elements [1] selection of one of the following functions in the sequence of the list. Prerequisite: the parameters for the functions have been set beforehand. ■ setpoint adjustm...

  • Page 32

    Operation product manual 2cka001473b9482 │32 9.2 colour concept fig. 21: models of control elements (examples) ■ the function icons [2] [4] have grey background. – the function icons describe the function. ■ the control icons [1] [3] (on the buttons) have a coloured background. – the control icons "...

  • Page 33

    Operation product manual 2cka001473b9482 │33 the device has the following operating modes: display operating mode comfort operation – application: you are in the room for a longer period of time; the comfort temperature is to be reached. – behaviour of the rtc: the display indicates the set-value te...

  • Page 34

    Operation product manual 2cka001473b9482 │34 9.4 displays / messages fig. 23: displays display function action of the device 21,0°c controller switched on / display of set-point temperature comfort mode – heating/cooling is at the normal level. – the display is only visible when the "superimposed op...

  • Page 35

    Operation product manual 2cka001473b9482 │35 9.4.1 switching on and off switch-on 1. Press the button [1]. – the functions which were active before deactivation are activated. – the set-point temperature is shown on the display. Switch-off 1. Press the button [1] continuously until the display flash...

  • Page 36

    Operation product manual 2cka001473b9482 │36 9.4.2 adjust temperature display of the set-point temperature the set-point temperature appears automatically on the display. The device must be switched on for this to happen. Setting of the set-point temperature 1 2 4 3 the desired temperature is set wi...

  • Page 37

    Operation product manual 2cka001473b9482 │37 9.4.3 adjusting the fan speed levels 1 2 4 3 1. Press the button [1] continuously until the display flashes 2. Press the "menu" button [1]. – keep pressing it until the fan speed level icon is shown on the display. 3. Press the plus/minus button [2]/[3] t...

  • Page 38

    Operation product manual 2cka001473b9482 │38 9.4.4 eco mode eco mode can be used to automatically reduce the room temperature and for reducing the fan speed level. E.G. During absence. 1 2 4 3 activating eco mode 1. Press the button [4]. – the device switches to eco mode. Deactivating eco mode 2. Pr...

  • Page 39

    Operation product manual 2cka001473b9482 │39 9.4.5 changing the operating status (heating/cooling) 1 2 4 3 1. Press the button [1] continuously until the display flashes 2. Press the "menu" button [1]. – keep pressing it until the function "operating mode" is shown on the display. 3. Select the desi...

  • Page 40

    Maintenance product manual 2cka001473b9482 │40 10 maintenance 10.1 maintenance-free device the device is maintenance-free. In case of damage, e.G. During transport or storage), do not perform repairs. Once the device is opened, the warranty is void. Access to the device must be guaranteed for operat...

  • Page 41

    Description of application and parameters application program product manual 2cka001473b9482 │41 11 description of application and parameters 11.1 application program available devices (control elements): ■ tbr/u4.X.X-xx control element 4gang with rtc incl. Bau ■ tr/u.X.X-xx room temperature control...

  • Page 42

    Description of application and parameters overview of functions product manual 2cka001473b9482 │42 11.2 overview of functions application parameters options device settings — acoustic feedback signal — buzzer application selected feedback signal noise is on clicking / beeping acoustic feedback signa...

  • Page 43

    Description of application and parameters overview of functions product manual 2cka001473b9482 │43 value 1 setting dependent on object type value 2 setting dependent on object type function block rtc — control settings — general jump-back time to the primary function 5 s / 10 s / 20 s / 30 s / 1 min...

  • Page 44

    Description of application and parameters overview of functions product manual 2cka001473b9482 │44 cyclic sending of the control value (min) 1 - 60 pwm cycle heating (min) 1 - 60 max. Control value (0 to 255) 0 - 255 min. Control value for basic load (0 to 255) 0 - 255 function block rtc — rtc — con...

  • Page 45

    Description of application and parameters overview of functions product manual 2cka001473b9482 │45 min. Control value for basic load (0 to 255) 0 - 255 function block rtc — rtc — control of additional cooling stage control value type 2-point 1 bit, on/off / 2-point 1 byte, 0/100% / pi continuous, 0-...

  • Page 46

    Description of application and parameters overview of functions product manual 2cka001473b9482 │46 setpoint temperature heat protection (°c) 27 - 45 display indicates current setpoint / relative setpoint send current setpoint cyclic and at change / only at change cyclic sending of the current setpoi...

  • Page 47

    Description of application and parameters overview of functions product manual 2cka001473b9482 │47 (°c) function block rtc — rtc — fan coil settings - fan speed levels number of fan speed levels 3 levels / 5 levels format of the level output 0-5 / 0-255 / 1 bit m off n / 1 bit 1 off n level output a...

  • Page 48

    Description of application and parameters overview of functions product manual 2cka001473b9482 │48 channel x — cyclic telegram object type 1 bit switching / 1 bit alarm / 1 byte 0-100% / 1 byte 0-255 / 2 byte float / 2 byte signed / 2 byte unsigned / 4 byte float / 4 byte signed / 4 byte unsigned cy...

  • Page 49

    Description of application and parameters overview of functions product manual 2cka001473b9482 │49 filter function deactivated / on filter out / off filter out data flow direction input in direction of output / output in direction of input / in both directions enable object deactivated / activated o...

  • Page 50

    Description of application and parameters overview of functions product manual 2cka001473b9482 │50 unsigned number of input objects 1 - 8 output sends at each input assignment / when the output object is changed output object assumes the largest input value / assumes the smallest input value / assum...

  • Page 51

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │51 11.3 application "device settings" 11.3.1 acoustic feedback signal - application options: inactive buzzer application ■ inactive: – the application is not active. ■ buzzer application: – the ap...

  • Page 52

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │52 11.3.1.2 acoustic feedback signal via object options: deactivated activated ■ deactivated: – the communication object is not enabled. ■ activated: – the communication object is enabled. A 1-bit...

  • Page 53

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │53 11.3.1.4 feedback signal after bus voltage recovery options: deactivated activated ■ deactivated: – automatic deactivation after bus voltage recovery. ■ activated: – automatic activation after ...

  • Page 54

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │54 11.3.1.6 activation of the acoustic feedback signal with options: on telegram off telegram ■ on telegram: – activation via on telegram. ■ off telegram: – activation via off telegram. The parame...

  • Page 55

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │55 11.3.1.8 ending the alarm automatically options: deactivated activated ■ deactivated: – the alarm is not switched off automatically. ■ activated: – the alarm is switched off automatically at an...

  • Page 56

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │56 11.3.1.10 time for automatic ending via object options: deactivated activated ■ deactivated: – the communication object is not enabled. ■ activated: – the communication object is enabled. A 2-b...

  • Page 57

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │57 11.3.2 proximity - application options: inactive proximity application ■ inactive: – application is not active. ■ proximity application: – application is active. The application is used to spec...

  • Page 58

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │58 11.3.2.2 automatic switchover time options: setting option from 00:00:10 to 18:00:00 (hh:mm:ss) the switching on or switchover always occurs immediately the user has approached the device. The ...

  • Page 59

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │59 11.3.2.4 led colour in a blocked state options: yellow orange red violet blue green white ■ yellow - white: – the led lights up in the specified colour during blockage. The parameter is used to...

  • Page 60

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │60 11.3.3 device enable - application options: inactive enable application ■ inactive: – application is not active. ■ enable application: – application is active. If the application is activated t...

  • Page 61

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │61 11.3.3.2 after bus voltage recovery the device is options: blocked enabled ■ blocked: – the enable object has value"1" after bus voltage recovery. ■ enabled: – the enable object has value "0" a...

  • Page 62

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │62 11.3.3.5 switchover time via object options: deactivated activated ■ deactivated: – the communication object is not enabled. ■ activated: – the communication object is enabled. A 2-byte communi...

  • Page 63

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │63 11.3.3.7 brightness of the led during blockage options: off dark bright ■ off: – the led does not light up at blockage. ■ dark: – the led lights up dark at blockage. ■ bright: – the led lights ...

  • Page 64

    Description of application and parameters application "device settings" product manual 2cka001473b9482 │64 11.3.4 during operation function - application options: inactive object during operation ■ inactive: – application is not active. ■ object during operation: – application is active. The applica...

  • Page 65

    Description of application and parameters application "primary function" product manual 2cka001473b9482 │65 11.4 application "primary function" 11.4.1 primary function - application options: inactive 1-button switching ■ inactive: – application is not active. ■ 1-button switching: – application is a...

  • Page 66

    Description of application and parameters application "primary function" product manual 2cka001473b9482 │66 11.4.1.1 object type options: 1 bit 1 byte 0 - 100% 1 byte 0 - 255 light scene number 1-64 rtc operating mode switchover (1 byte) ■ 1 bit: – the value is sent as 1-bit switching commands (0 or...

  • Page 67

    Description of application and parameters application "primary function" product manual 2cka001473b9482 │67 11.4.1.2 reaction on rising edge options: value 1 value 2 alternating value1/value2 deactivated ■ value 1: – value 1 is sent at the press of the button (at rising edge). ■ value 2: – value 2 i...

  • Page 68

    Description of application and parameters application "primary function" product manual 2cka001473b9482 │68 11.4.1.3 reaction on falling edge options: value 1 value 2 alternating value1/value2 deactivated ■ value 1: – value 1 is sent when the button is released (at falling edge). ■ value 2: – value ...

  • Page 69

    Description of application and parameters application "primary function" product manual 2cka001473b9482 │69 11.4.1.5 value 1/value 2 the possible options depend on parameter "object type". Options for selection "1 bit": options: off one options for selection "1 byte 0-100%": options: setting option ...

  • Page 70

    Description of application and parameters application "primary function" product manual 2cka001473b9482 │70 11.4.1.6 value 2 the possible options depend on parameter "object type". Options for selection "1 bit": options: off one options for selection "1 byte 0-100%": options: setting option from 0 t...

  • Page 71

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │71 11.5 application "function block rtc" 11.5.1 control settings - general 11.5.1.1 jump-back time to the primary function options: 5 s 10 s 20 s 30 s 1 min. 2 min. 4 min. The parameter is used...

  • Page 72

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │72 11.5.2.2 setting the temperature unit via object options: no yes ■ no: – communication object "hmi: units switchover" is not enabled. ■ yes: – communication object "hmi: units switchover" is...

  • Page 73

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │73 11.5.2.4 waiting period for display of actual temperature options: 5 s 10 s 20 s 30 s 1 min. 2 min. 4 min. The parameter is used to specify after which rest period the actual temperature is ...

  • Page 74

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │74 11.5.3 control settings — brightness setting 11.5.3.1 day/night mode options: no yes ■ no: – communication object "hmi: day/night mode" is not enabled. ■ yes: – communication object "hmi: da...

  • Page 75

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │75 11.5.4 control settings — button configuration 11.5.4.1 button top left options: eco on/off menu fan ■ eco: – if selected, the eco mode can be activated or deactivated with a press of the bu...

  • Page 76

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │76 11.5.4.2 button top right options: eco on/off menu fan ■ eco: – if selected, the eco mode can be activated or deactivated with a press of the button. ■ on/off: – if selected, the temperature...

  • Page 77

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │77 11.5.5 rtc - general 11.5.6 general — device function options: single device master device slave device ■ single device – the device is used individually in a room for temperature control wi...

  • Page 78

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │78 11.5.8 general — control function options: heating heating with additional stage cooling cooling with additional stage heating and cooling heating and cooling with additional stage – heating...

  • Page 79

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │79 11.5.9 general - operating mode after reset options: comfort standby eco mode frost/heat protection after a reset the device will run in the operating mode after a restart until a new operat...

  • Page 80

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │80 11.5.11 general - additional functions/objects options: no yes – this parameter enables additional functions and communication objects. 11.5.12 general — delay time for read telegrams after ...

  • Page 81

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │81 11.5.13 heating control note only available when the "device function" parameter is set on either "single device" or "master device" and the control function parameter is set on either "heat...

  • Page 82

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │82 11.5.15 heating control — heating type options: pi continuous, 0 – 100% and pi pwm, on/off: ■ area (e.G. Floor heating) 4°c 200 min ■ convector (e.G. Heater) 1.5°c 100 min ■ free configurati...

  • Page 83

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │83 11.5.17 heating control — i-component (min.) options: setting option between 0 - 255 the i-component refers to the reset time of a control. The integral component has the effect of moving th...

  • Page 84

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │84 11.5.19 basic stage heating note only available when the "extended settings" parameter under "heating control" is set on "yes". 11.5.20 basic stage heating — status object heating options: n...

  • Page 85

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │85 11.5.23 basic stage heating — control value difference for sending of heating control value options: 2 % 5 % 10 % send cyclic only the control values of the 0 - 100% pi continuous controller...

  • Page 86

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │86 11.5.26 basic stage heating — maximum control value (0 - 255) options: setting option between 0 - 255 the maximum control value of the pi controller defines the maximum value outputted by th...

  • Page 87

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │87 11.5.28 control of additional heating stage note only available when the "device function" parameter is set on either "single device" or "master device" and the control function parameter is...

  • Page 88

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │88 11.5.30 control of additional heating stage — additional heating type options: pi continuous, 0 – 100% and pi pwm, on/off: ■ area (e.G. Floor heating) 4°c 200 min ■ convector (e.G. Heater) 1...

  • Page 89

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │89 11.5.32 control of additional heating stage — i-component (min) options: setting option between 0 - 255 the i-component refers to the reset time of a control. The integral component has the ...

  • Page 90

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │90 11.5.35 additional heating stage note only available when the "extended settings" parameter under "control of additional heating stage" is set on "yes". 11.5.36 additional heating stage — mo...

  • Page 91

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │91 11.5.39 additional heating stage — cyclic sending of the control value (min) options: setting option between 1 - 60 minutes the current control value used by the device can be cyclically tra...

  • Page 92

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │92 11.5.42 cooling control note only available when the "device function" parameter is set on either "single device" or "master device" and the control function parameter is set on either "cool...

  • Page 93

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │93 11.5.44 cooling control — cooling type options: pi continuous, 0 – 100% and pi pwm, on/off: ■ area (e.G. Cooling ceiling) 5°c 240 min ■ free configuration fan coil: ■ fan coil 4°c 90 min ■ f...

  • Page 94

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │94 11.5.46 cooling control — i-component (min.) options: setting option between 0 - 255 the i-component refers to the reset time of a control. The integral component has the effect of moving th...

  • Page 95

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │95 11.5.48 basic stage cooling note only available when the "extended settings" parameter under "cooling control" is set on "yes". 11.5.49 basic stage cooling — status object cooling options: n...

  • Page 96

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │96 11.5.52 basic stage cooling — hysteresis (x 0.1°c) options: setting option between 3 - 255 the hysteresis of the two-point controller specifies the fluctuation range of the controller around...

  • Page 97

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │97 11.5.54 basic stage cooling - pwm cycle cooling (min) options: setting option between 1 - 60 minutes in pi pwm, on/off the control value percentage values are converted into a pulse-interval...

  • Page 98

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │98 11.5.57 control of additional cooling stage note only available when the "device function" parameter is set on either "single device" or "master device" and the control function parameter is...

  • Page 99

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │99 11.5.58 control of additional cooling stage — cooling type options: pi continuous, 0 – 100% and pi pwm, on/off: ■ area (e.G. Cooling ceiling) 5°c 240 min ■ free configuration fan coil: ■ fan...

  • Page 100

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │100 11.5.60 control of additional cooling stage — p-component (min) options: setting option between 0 - 255 the i-component refers to the reset time of a control. The integral component has the...

  • Page 101

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │101 11.5.63 additional cooling stage note only available when the "extended settings" parameter under "control of additional cooling stage" is set on "yes". 11.5.64 additional cooling stage — m...

  • Page 102

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │102 11.5.67 additional cooling stage — cyclic sending of the control value (min) options: setting option between 1 - 60 minutes the current control value used by the device can be cyclically tr...

  • Page 103

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │103 11.5.70 settings of basic load note only available when the "device function" parameter is set on either "single device" or "master device" and the control function parameter is set on eith...

  • Page 104

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │104 11.5.73 combined heating and cooling modes note only available when the "device function" parameter is set on either "single device" or "master device" and the control function parameter is...

  • Page 105

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │105 11.5.76 combined heating and cooling modes — heating/cooling control value output options: via 1 object via 2 objects this parameter is used to define whether the control value is transmitt...

  • Page 106

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │106 11.5.78 setpoint settings note this parameter is only available if the "device function" parameter is set on either "single device" or "master device". 11.5.79 setpoint settings — setpoint ...

  • Page 107

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │107 11.5.81 setpoint settings — setpoint temperature for heating and cooling comfort (°c) options: setting option between 10 - 40 specifies the comfort temperature for heating and cooling when ...

  • Page 108

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │108 11.5.85 setpoint settings — set-point temperature for frost protection (°c) options: setting option between 5 - 15 function for protecting the building against the cold. On devices with a d...

  • Page 109

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │109 11.5.89 setpoint settings — set-point temperature for heat protection (°c) options: setting option between 27 - 45 function for protecting the building against heat. On devices with a displ...

  • Page 110

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │110 11.5.93 setpoint settings - basic set value is options: set-point for cooling comfort set-point for heating comfort mean value between heating comfort and cooling comfort ■ setpoint for coo...

  • Page 111

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │111 11.5.94 setpoint adjustment note this parameter is only available if the "device function" parameter is set on either "single device" or "master device". 11.5.95 setpoint adjustment — maxim...

  • Page 112

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │112 11.5.98 setpoint adjustment — maximum manual reduction during cooling mode (0 - 9°c) options: setting option between 0 - 9 this preset can be used to limit the manual decrease during coolin...

  • Page 113

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │113 11.5.101 setpoint adjustment — resetting the manual adjustment via object options: no yes if this parameter is activated, a separate object can be used to delete the manual adjustment at an...

  • Page 114

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │114 11.5.104 temperature reading — inputs of weighted temperature reading options: internal and external measurement 2 x external measurement internal and 2x external measurement specifies the ...

  • Page 115

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │115 11.5.107 temperature reading — weighting of external measurement 2 (0 to 100%) options: setting option between 0 - 100 specifying the weighting of the external measurement 2 from 0 to 100%....

  • Page 116

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │116 11.5.110 temperature reading — adjustment value for internal temperature measurement (x 0.1°c) options: setting option between 1 - 100 every installation location has different physical con...

  • Page 117

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │117 11.5.113 alarm functions note this parameter is only available if the "device function" parameter is set on either "single device" or "master device". 11.5.114 alarm functions — condensate ...

  • Page 118

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │118 11.5.116 alarm functions — frost alarm temperature for hvac and rhcc status (°c) options: setting option between 0 - 15 the rhcc status and hvac objects have a frost alarm bit. It the input...

  • Page 119

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │119 11.5.118 fan coil settings - fan speed levels note this parameter is only available if the "device function" parameter is set on either "single device" or "master device" and the "control v...

  • Page 120

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │120 11.5.121 fan coil settings - fan speed levels — level output options: for manual operation and automatic only for manual operation this parameter is used to specify when the output of the f...

  • Page 121

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │121 11.5.124 fan coil settings heating note this parameter is only available if the "device function" parameter is set on either "single device" or "master device" and the "control value type" ...

  • Page 122

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │122 11.5.128 fan coil settings for cooling note this parameter is only available if the "device function" parameter is set on either "single device" or "master device" and the "control value ty...

  • Page 123

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │123 11.5.132 summer compensation note this parameter is only available if the "device function" parameter is set on either "single device" or "master device". 11.5.133 summer compensation — sum...

  • Page 124

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │124 for example: for an increasing outside temperature, the minimum setpoint value for cooling will be increased starting at an outside temperature of 21°c. The minimum setpoint temperature for...

  • Page 125

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │125 11.5.136 summer compensation — (upper) exit temperature for summer compensation (°c) options: setting option between -127 - 127 the parameter defines the upper outside temperature value up ...

  • Page 126

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │126 11.5.138 application - led function the application can be used to configure the button leds for the status or function display. The following communication objects are available: ■ "status...

  • Page 127

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │127 11.5.138.2 object type for status object options: 1 bit 1 byte 0 - 100% ■ 1 bit: – the value is sent as 1-bit switching commands (on/off) and the button leds light up in the colour for on o...

  • Page 128

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │128 11.5.138.3 brightness of the colours options: dark bright ■ dark: – the button leds light up with minimal brightness. ■ bright: – the button leds light up with high brightness. The paramete...

  • Page 129

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │129 11.5.138.5 colour for on options: off yellow red-orange red violet blue green white ■ off: – the button leds are switched off. ■ yellow - white: – the button leds light up in the fixed colo...

  • Page 130

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │130 11.5.138.6 colour for zone 1 (corresponds to 0%) options: off yellow red-orange red violet blue green white ■ off: – the button leds are switched off. ■ yellow - white: – the button leds li...

  • Page 131

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │131 11.5.138.7 colour for zone 2 (starting at 1%) options: off yellow red-orange red violet blue green white ■ off: – the button leds are switched off. ■ yellow - white: – the button leds light...

  • Page 132

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │132 11.5.138.9 colour for zone 3 options: off yellow red-orange red violet blue green white ■ off: – the button leds are switched off. ■ yellow - white: – the button leds light up in the fixed ...

  • Page 133

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │133 11.5.138.11 colour for zone 4 (up to 99%) options: off yellow red-orange red violet blue green white ■ off: – the button leds are switched off. ■ yellow - white: – the button leds light up ...

  • Page 134

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │134 11.5.138.12 colour for zone 5 (corresponds to 100%) options: off yellow red-orange red violet blue green white ■ off: – the button leds are switched off. ■ yellow - white: – the button leds...

  • Page 135

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │135 11.5.138.13 colour of function illumination options: off yellow (light) red/orange (heating) red violet (scene) blue (blind) green white (neutral) ■ off: – the button leds are switched off....

  • Page 136

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │136 11.5.138.14 day/night mode options: deactivated activated ■ deactivated: – communication object "day/night mode" is not enabled. ■ activated: – communication object "day/night mode" is enab...

  • Page 137

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │137 11.5.138.15 light scene memory function options: deactivated activated ■ deactivated: – communication object "scene storage" is not enabled. ■ activated: – communication object "scene stora...

  • Page 138

    Description of application and parameters application "function block rtc" product manual 2cka001473b9482 │138 11.5.138.16 alarm function options: deactivated activated ■ deactivated: – communication object "alarm" is not enabled. ■ activated: – communication object "alarm" is enabled. The 1-byte co...

  • Page 139

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │139 11.6 application "general functions" up to five channels can be activated for the use of the applications described in this section. 11.6.1 channel x - application options: inactive cyclic t...

  • Page 140

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │140 ■ light scene actuator: – with the application it is possible to call up scenes that are stored in the device via the receipt of a scene number on the 1-byte communication object "gfx: scene...

  • Page 141

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │141 11.6.2 application - cyclic telegrams the application can be used to send telegrams cyclic on the bus under fixed conditions. The following communication objects are available: ■ "gfx: input...

  • Page 142

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │142 11.6.2.2 object type options: 1-bit switching 1-bit alarm 1 byte 0 - 100% 1 byte 0 - 255 2-byte float 2-byte signed 2-byte unsigned 4-byte float 4-byte signed 4-byte unsigned ■ 1-bit switchi...

  • Page 143

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │143 11.6.2.3 cycle time options: setting option from 00:00:55 to 01:30:00 (hh:mm:ss) the telegrams of the object during operation are sent cyclic on the bus. The parameter specifies the time int...

  • Page 144

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │144 11.6.2.6 enable object after return of voltage options: blocked enabled ■ blocked: – object "gfx: enable" is not activated at bus voltage recovery. The blocking function is deactivated. ■ en...

  • Page 145

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │145 11.6.2.8 value for cyclic sending the possible options and setting limits depend on parameter "object type". Options for selection "1 bit switching" and "1-bit alarm": options: off one optio...

  • Page 146

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │146 note the parameter can only be set if the "cyclic sending" parameter is set on "activated at a specified value" or on "activated except at a specified value. 11.6.3 application - priority th...

  • Page 147

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │147 11.6.4 application - logic gate up to ten input values can be linked with each other via the application. The following communication objects are available: ■ "gfx: output" ■ "gfx: input x“ ...

  • Page 148

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │148 11.6.4.2 logical function options: and or xor xnor nand nor ■ and - nor: – logic gates, with which communication objects can be linked. The parameter is used to specify the logic gate the co...

  • Page 149

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │149 11.6.4.5 initial value input x options: initialised with 0 initialised with 1 ■ initialised with 0: – after initial commissioning and after the return of voltage the input has the logical va...

  • Page 150

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │150 11.6.4.7 object type output options: 1 bit 1 byte ■ 1 bit: – object "gfx: output“ consists of a 1-bit value (0/1). ■ 1 byte: – object "gfx: output“ consists of a 1-byte value (0 - 255). Each...

  • Page 151

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │151 11.6.4.9 value of the output object for logic true options: output is set to 1 defined via output default value true ■ output is set on 1: – as soon as the logic function is fulfilled, a log...

  • Page 152

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │152 11.6.4.12 value of the output object for logic untrue options: output is set to 0 defined via output default value untrue ■ output is set on 0: – as soon as the logic function is fulfilled, ...

  • Page 153

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │153 11.6.5 application - gate the application allows specific signals to be filtered and the signal flow to be temporarily blocked. The following communication objects are available: ■ "gfx: inp...

  • Page 154

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │154 11.6.5.2 object type options: 1-bit switching 1-bit travel 1-bit stop/adjust 2-bit priority 4-bit relative dimming 1 byte 0 - 100% 1 byte 0 - 255 2-byte float 2-byte signed 2-byte unsigned 3...

  • Page 155

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │155 ■ 3-byte time of day: – the value is sent as 3-byte daytime value. ■ 3-byte date: – the value is sent as 3-byte date value. ■ 4-byte float: – the value is sent as 4-byte floating point value...

  • Page 156

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │156 11.6.5.4 data flow direction options: input towards the output output towards the input in both directions ■ input towards the output: – telegrams are transferred from object "gfx: input" to...

  • Page 157

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │157 11.6.5.6 object value enable object options: normal inverse ■ normal: – if an off telegram is received via the object "gfx: control input", the function "gate" is blocked. An on telegram dea...

  • Page 158

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │158 11.6.5.8 save input signal options: deactivated activated ■ deactivated: – input telegrams are not saved during the blocking phase. ■ activated: – input telegrams are saved during the blocki...

  • Page 159

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │159 11.6.6 application - staircase lighting with the application, switching telegrams and value telegrams can be provided with a switch-off delay. The application has the following communication...

  • Page 160

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │160 11.6.6.2 object type/number options: a 1-bit object for input and output two 1-bit objects for input and output two 1-byte objects for input and output ■ a 1-bit object for input and output:...

  • Page 161

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │161 11.6.6.4 retriggering options: deactivated activated ■ deactivated: – the set switch-off delay always runs to its end, so that a telegram is always sent via object "gfx: output" after the de...

  • Page 162

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │162 11.6.6.6 time for switch-off pre-warning (s) options: setting option from 1 to 5400 the parameter is used to specify when the staircase lighting by means of flickering or dimming darker is t...

  • Page 163

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │163 11.6.7 application - delay the application can be used to receive telegrams via the "input" object. The telegrams received are sent out via the "output" object with a set delay time. The app...

  • Page 164

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │164 11.6.7.2 object type options: 1-bit switching 1-bit travel 1-bit stop/adjust 1 byte 0 - 100% 1 byte 0 - 255 2-byte float 2-byte signed 2-byte unsigned 4-byte float 4-byte signed 4-byte unsig...

  • Page 165

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │165 11.6.7.3 delay time options: setting option from 00:00:01.000 to 01:00:00:000 (hh:mm:ss) the parameter is used to set the delay with which the telegrams received via object "gfx: input" are ...

  • Page 166

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │166 11.6.7.6 filter function options: filter value is delayed, other values are sent directly filter value is delayed, other values are suppressed filter value is sent directly, other values are...

  • Page 167

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │167 options for selection "2-byte float": options: setting option from -671088.64 to 670760.96 options for selection "2-byte signed": options: setting option from -32768 to +32767 options for se...

  • Page 168

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │168 11.6.7.8 overwrite delay time during download options: deactivated activated ■ deactivated: – the delay time will not be overwritten when the device is reprogrammed. ■ activated: – the delay...

  • Page 169

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │169 11.6.8 application - min/max value transducer up to eight input values can be compared with each other via the application. The following communication objects are available: ■ "gfx: output"...

  • Page 170

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │170 11.6.8.2 object type options: 1 byte 0 - 100% 1 byte 0 - 255 2-byte float 2-byte signed 2-byte unsigned 4-byte float 4-byte signed 4-byte unsigned ■ 1 byte 0 - 100%: – the value is sent as 1...

  • Page 171

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │171 11.6.8.4 output sends options: for every assignment of the inputs with a change of the output object ■ for every assignment of the inputs: – when a telegram is received on one of the input o...

  • Page 172

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │172 11.6.9 application - light scene actuator the application is used to create up to eight scenes and eight actuator groups. The following communication objects are available: ■ "gfx: scene cal...

  • Page 173

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │173 11.6.9.3 number of actuator groups options: setting option from 1 to 8 the parameter is used to configure up to eight actuator groups for the light scene actuator. At a call up of a scene, t...

  • Page 174

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │174 11.6.9.6 object type actuator group x options: number of light scene 1-bit switching 1-bit blind 1 byte 0 - 100% temperature ■ 1-bit switching: – the value is sent as 1-bit switching command...

  • Page 175

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │175 11.6.9.8 scene can be saved options: deactivated activated ■ deactivated: – stored scene values that are sent at a scene call-up via different actuator objects, can not be changed and overwr...

  • Page 176

    Description of application and parameters application "general functions" product manual 2cka001473b9482 │176 11.6.9.11 value options: off one adjustable options, when parameter "object type actuator group x" is set on "1-bit switching". 11.6.9.12 value options: up down adjustable options, when para...

  • Page 177

    Notes product manual 2cka001473b9482 │177 12 notes.

  • Page 178

    Index product manual 2cka001473b9482 │178 13 index a acoustic alarm via object ................................ 53 acoustic feedback signal application ...................................................................... 51 acoustic feedback signal via object .................... 52 activation of ...

  • Page 179

    Index product manual 2cka001473b9482 │179 colour for zone 5 (corresponds to 100%) ............. 134 colour of function illumination ........................ 135 combined heating and cooling modes ................ 104 combined heating and cooling modes — heating/cooling control value output ............

  • Page 180

    Index product manual 2cka001473b9482 │180 i improper use ............................................... 11 information and symbols used ........................... 10 information on protection of the environment ........ 14 initial value input x ..................................... 149 installatio...

  • Page 181

    Index product manual 2cka001473b9482 │181 setpoint settings — setpoint temperature for cooling comfort (°c) .......................................... 108 setpoint settings — set-point temperature for frost protection (°c) ....................................... 108 setpoint settings — set-point tem...

  • Page 182

    A member of the abb group busch-jaeger elektro gmbh po box 58505 lüdenscheid freisenbergstraße 2 58513 lüdenscheid www.Busch-jaeger.Com info.Bje@de.Abb.Com central sales service: tel.: +49 2351 956-1600 fax: +49 2351 956-1700 notice we reserve the right to make technical changes at all times as well...