ABB i-bus KNX Product Manual

Manual is about: Room temperature controller

Summary of i-bus KNX

  • Page 1

    Abb i-bus ® knx room thermostat fan coil with display 6138/11-xx-500 product manual intelligent installation systems.

  • Page 2

    Temabb i-bus £ knx contents and document history © 2009 busch-jaeger elektro gmbh – a company of the abb group 1 page 1 general.................................................................................................3 1.1 overview of product and functions........................................

  • Page 3

    Temabb i-bus £ knx contents and document history © 2009 busch-jaeger elektro gmbh – a company of the abb group 2 4.2 temperature measurement ................................................................85 4.2.1 internal temperature recording ..........................................................

  • Page 4

    Abb i-bus £ knx general © 2009 busch-jaeger elektro gmbh – a company of the abb group 3 1 general the fan coil ambient temperature controller with display is a continuous knx ambient temperature controller for fan convectors in 2 and 4-pipe systems. It measures the current ambient temperature (actua...

  • Page 5

    Abb i-bus £ knx general © 2009 busch-jaeger elektro gmbh – a company of the abb group 4 1.1 overview of product and functions the fan coil ambient temperature controller with display records the current room temperature and controls the heating and/or cooling. It also controls 2 and 4-pipe fan coil ...

  • Page 6

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 5 2 technology the fan coil ambient temperature controller with display records the current room temperature and controls the heating and/or cooling. It also controls 2 and 4-pipe fan coil units and conventional...

  • Page 7

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 6 - "fan stage adjustment" when the switch is pressed, the device runs through the sequence "1 2 3 auto 0 1 ...“ starting from the current fan stage. If the fan is set to automatic, this is deactivated when the ...

  • Page 8

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 7 2.2 connection diagram eib/knx bus + - connection diagram of fan coil ambient temperature controller with display 2.3 dimensional drawing 81 81 51 39 20 dimensional drawing of fan coil ambient temperature cont...

  • Page 9

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 8 2.4 assembly and installation the fan coil with display ambient temperature controller is a surface- mounted device (ap) with an integrated bus coupler. The device operates without additional supply voltage. I...

  • Page 10

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 9 - the ambient temperature controller must not be exposed to direct contact with liquids. - temperature regulation will also be affected by exposure to heat from electrical appliances and direct sunlight on the...

  • Page 11

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 10 maintenance the device is maintenance-free. It must not be repaired by third parties if it is damaged, such as in transport and/or storage. The guarantee is cancelled if the device is opened. The device must ...

  • Page 12

    Abb i-bus £ knx technology © 2009 busch-jaeger elektro gmbh – a company of the abb group 11 2.5 operation and display messages internal temp error ia – fault in internal temperature sensor external temp error ea – update of external temperature not received -> outdoor temp error oa – update of outsi...

  • Page 13

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 12 3 commissioning 3.1 application program for the ambient temperature controller the fan coil display operate control/1.2 application program for the fan coil ambient temperature controller with display cont...

  • Page 14

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 13 3.2 parameters 3.2.1 parameter window "general" send "in operation" object options: - no - send value “0” cyclic - send value “1” cyclic the "in operation" object reports to the bus that the device is oper...

  • Page 15

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 14 display during normal operation options: - no temperature display - absolute setpoint temperature - relative setpoint temperature (+/-k) - current setpoint use this parameter to specify what information is...

  • Page 16

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 15 if an on message is received by multiple objects, freezing/heat protection has a higher priority than comfort mode. Night reduction has a higher priority than comfort mode. When switching operating mode vi...

  • Page 17

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 16 operation mode after reset options: - comfort operation - standby - night mode - frost/heat protection this parameter specifies the mode activated after resetting the temperature sensor or after commission...

  • Page 18

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 17 3.2.2 "temperature measurement" parameter window offset for room temp. Meas. (measured value changed by (-128..127)x0.1 k) options: - -128 - … - 0 - … - 127 value range –128..127 corresponds to –12.8k..12....

  • Page 19

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 18 send setpoint cyclic (0 – inactive, min) options: - 0 .. 60 if the current value is to be sent cyclically independent of a change, the parameter "send setpoint cyclic" must be set to a time. This may be ne...

  • Page 20

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 19 control value at temp. Measuring error options: - final value - 0 % - 10 % - 20 % - 30 % - 40 % - 50 % - 60 % - 70 % - 80 % - 90 % - 100 % in case of error the device output uses the specified value to run...

  • Page 21

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 20 3.2.3 parameter window "controller general" operating mode of unit options: - normal operation with control function - ext. Input, only operating and display function the control function of the device is ...

  • Page 22

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 21 switchover between heating and cooling options: - automatic - automatic and send - exterior you can switch between heating and cooling automatically in the room thermostat. To do so, select the "automatic"...

  • Page 23

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 22 condensate alarm active options: - yes - no if the parameter "condensate alarm active" is activated, the room thermostat has a 1-bit communication object that can be used to send telegrams from a container...

  • Page 24

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 23 operation mode after reset options: - heating - cooling - dependent on object “switchover heat / cool” this parameter specifies the mode activated after resetting the temperature sensor or after commission...

  • Page 25

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 24 3.2.4 parameter window "heating control" status send heat requirement options: - yes - no if you set the "status send heat requirement" to "yes", the ambient temperature controller will send an on telegram...

  • Page 26

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 25 control mode options: - 2-step - pwm - continuous - fancoil this function allows you to specify the mode of control. You can select "2-step control", "pwm control", "continuous control" or "fancoil actuati...

  • Page 27

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 26 control value larger when sending change options: - 0% - 1 % - … - 5 % - … - 15 % the parameter "control value larger when sending change" can be used to influence the bus load. This setting is configured ...

  • Page 28

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 27 proportional range (xp) options: - 0.5 k - 1.0 k - 1.5 k - 2.0 k - 2.5 k - 3.0 k - 3.5 k - 4.0 k - 4.5 k - 5.0 k - 5.5 k … - 10.0 k the proportional range stands for the p amount of controller. It varies a...

  • Page 29

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 28 maximum control value options: - 70% - 75% - 80 % - 85 % - 90 % - 95 % - 100 % this parameter is required if the ambient temperature controller with constant control regulates a continuous actuator or a fa...

  • Page 30

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 29 3.2.5 parameter window "controller pwm heating" invert heating options: - yes - no "invert heating" is used to adjust the direction of control action of the control value to "de-energised open" or "de-ener...

  • Page 31

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 30 pwm cycle is 0% up to control value options: - 0% - 5 % - … - 10 % - … - 30 % if the control value is very small for pwm control, the switch-on period for the actuator might not be sufficient to put in mot...

  • Page 32

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 31 3.2.6 parameter window "cooling control" status send cooling requirement options: - yes - no if you set the "status send cooling requirement" to "yes", the room thermostat will send an on telegram via the ...

  • Page 33

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 32 control mode options: - 2-step - pwm - continuous - fancoil this function allows you to specify the type of control. You can choose from 2-step control, pwm control, continuous control or fancoil control. ...

  • Page 34

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 33 control value larger when sending change options: - 0% - 1 % - … - 5% - … - 15 % the parameter "control value larger when sending change" can be used to influence the bus load. This setting is configured i...

  • Page 35

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 34 proportional range (xp) options: - 0.5 k - 1.0 k - 1.5 k - 2.0 k - 2.5 k - 3.0 k - 3.5 k - 4.0 k - 4.5 k - 5.0 k - 5.5 k - 6.0 k - 6.5 k - 7.0 k - 8.0 k - 9.0 k - 10.0 k the proportional range stands for t...

  • Page 36

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 35 minimum control value options: - 0% - 5% - 10 % - 15 % - 20 % - 25 % - 30 % this parameter is required if the ambient temperature controller with constant control regulates a continuous actuator or a fan c...

  • Page 37

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 36 3.2.7 parameter window "control pwm cooling" invert cooling options: - yes - no "invert cooling" is used to adjust the direction of control action of the control value to "de-energised open" or "de-energis...

  • Page 38

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 37 pwm cycle is 0% up to control value options: - 0% - 5 % - … - 10 % - … - 30 % if the control value is very small for pwm control, the switch-on period for the actuator might not be sufficient to put in mot...

  • Page 39

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 38 3.2.8 parameter window "additional heating" type of control value options: - continuous (1 byte) - switching (1 bit) the additional stage for heating can transmit a 1-bit or 1-byte sized control value. If ...

  • Page 40

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 39 hysteresis (one-sided) options: - 0.0 k - 0.1 k - 0.2 k - 0.3 k … - 1.00 k … - 2.00 k the parameters "interval of additional level" and "hysteresis (one-sided)" enable you to specify when the additional st...

  • Page 41

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 40 3.2.9 parameter window "additional cooling stage" type of control value options: - continuous (1 byte) - switching (1 bit) the additional stage for cooling can transmit a 1-bit or 1-byte sized control valu...

  • Page 42

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 41 hysteresis (one-sided) options: - 0.0 k - 0.1 k - 0.2 k - 0.3 k … - 1.0 k … - 2.00 k the parameters "interval of additional level" and "hysteresis (one-sided)" enable you to specify when the additional sta...

  • Page 43

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 42 3.2.10 parameter window "setpoint general" setpoint larger when sending change options: - inactive - 0.1 k - 0.2 k - 0.3 k - 0.4 k - 0.5 k - 0.6 k - 0.7 k - 0.8 k - 0.9 k - 1.0 k if this parameter is set t...

  • Page 44

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 43 select base setpoint options: - dependent setpoints - single setpoints the "select base setpoint" option defines whether the room thermostat refers to "dependent setpoints" or to "single setpoints". Depend...

  • Page 45

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 44 manual setpoint adjustment at reset of change from night / to night options: - yes - no if this parameter is set to "yes", the setpoint offset is automatically reset when switching operating modes from nig...

  • Page 46

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 45 3.2.11 parameter window "manual setpoint" manual setpoint adjustment options: - disabled - actice this parameter allows end users to adjust the configured setpoint during commissioning. The settings "... M...

  • Page 47

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 46 maximum manual setpoint increase options: - 0 k - 1 k - 2 k - 3 k - 4 k - 5 k - 6 k - 7 k - 8 k - 9 k - 10 k if you wish to prevent an excessive temperature increase by the manual setpoint setting, the upp...

  • Page 48

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 47 object reset of manual setpoint adjustment active options: - yes - no this parameter releases a 1-bit communication object that upon receipt of an on telegram can be used manually reset the setpoint adjust...

  • Page 49

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 48 3.2.12 parameter window "setpoint heat/cool" heating setpoint comfort mode options: - 16.0 °c - 16.5 °c - … - 21.0 °c - … - 31.0 °c the "heating setpoint comfort mode" specifies the individual comfort temp...

  • Page 50

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 49 heating setpoint reduction night operation options: - 0.5 k - 1.0 k - … - 4 k - … - 8.0 k the setting "heating setpoint reduction night operation" allows you to specify the number of degrees kelvin that th...

  • Page 51

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 50 cooling setpoint comfort mode options: - 16.0 °c - 16.5 °c - … - 23.0 °c - … - 31.0 °c the "cooling setpoint comfort mode" specifies the individual comfort temperature for the cooling mode. This parameter ...

  • Page 52

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 51 cooling setpoint standby mode options: - 21.0 °c - 21.5 °c - … - 25.0 °c - … - 36.0 °c "cooling setpoint for standby mode" specifies the individual standby temperature for cooling mode. The temperature val...

  • Page 53

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 52 setpoint frost protection options: - 0 °c - 1 °c - … - 7 °c - … - 15 °c the setpoint for frost protection is the temperature that may not be undershot during the frost protection mode. If the current tempe...

  • Page 54

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 53 3.2.13 parameter window "fancoil general" number of fan levels options: - 1 level - 2 levels - 3 levels the parameter "number of fan levels" allows you to specify the number of fan stages that should be co...

  • Page 55

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 54 object manual fan stage send has the following code options: - 1-byte object as constant value 0-100% - 1-byte object as counting value 0-3 - 1-bit values if the user has made a manual fan stage switch, it...

  • Page 56

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 55 send cycle time of actuator in s (1 ..65,535) options: 1 / 2 / … / 120 / … / 65.535 if the "status byte operation" object is enabled and connected to the corresponding communication object of the fan coil ...

  • Page 57

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 56 3.2.14 parameter window "fancoil heating" stage limit in night mode options: - no limit - fan off - stage 1 - stage 2 if the device is used in an environment such as a hotel room, it may be desirable to li...

  • Page 58

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 57 return inactive a fan stage of and automatic return not 0 options: - yes - no if the user has manually changed the stage to "switch off", the ambient temperature controller can also be set so that it does ...

  • Page 59

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 58 threshold value stage 3 options: - 0% - 10 % - … - 70 % - … - 100 % threshold value stage 3 specifies the magnitude of the control value required to switch the ambient temperature controller from fan stage...

  • Page 60

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 59 3.2.15 parameter window "fancoil cooling" step limit in night mode options: - no limit - fan off - stage 1 - stage 2 if the device is used in an environment such as a hotel room, it may be desirable to lim...

  • Page 61

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 60 return inactive a fan stage off and automatic return not 0 options: - yes - no if the user has manually changed the stage to "switch off", the ambient temperature controller can also be set so that it does...

  • Page 62

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 61 threshold value stage 3 options: - 0% - 10 % - … - 70 % - … - 100 % threshold value stage 3 specifies the magnitude of the control value required to switch the ambient temperature controller from fan stage...

  • Page 63

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 62 3.2.16 parameter window "compensation" summer compensation active options: - yes - no to save energy and to maintain a reasonable temperature differential when entering an air-conditioned building, you sho...

  • Page 64

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 63 summer compensation upper exterior temp. Value options: - 9 °c - 10 °c - … - 32°c - … - 31: 40°c this specifies the upper outside temperature from which compensation should be enabled because of a high out...

  • Page 65

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 64 winter compensation active options: - yes - no to improve comfort and to maintain a reasonable temperature differential when entering a room with a large window area, you should increase the room temperatu...

  • Page 66

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 65 winter compensation lower setpoint offset options: - 0 k - 1 k - 2 k - … - 4 k - … - 10 k the "lower setpoint offset" specifies how many k the setpoint should be increased during winter compensation if the...

  • Page 67

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 66 3.3 communication objects 3.3.1 general no. Function object name data type flags 0 in operation general 1 bit eis1 dpt 1.001 k, Ü sends the object value "0" or "1" to the bus cyclically. Object value and c...

  • Page 68

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 67 3.3.2 control system no. Function object name data type flags 4 frost/heat protection control 1 bit eis1 dpt 1.001 k, s, l this data item forms the 1-bit object of knx for switching operating modes (frost ...

  • Page 69

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 68 no. Function object name data type flags 7 operating mode switchover control 1 byte dpt_hvac mode k, Ü, s, l this data item forms the 1-bit object of knx (dpt_hvac_mode) for switching operating modes. All ...

  • Page 70

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 69 no. Function object name data type flags 9 send setpoint temperature sensor 2 byte k, Ü, l this data item forms the 2-byte object of knx for the current temperature. The temperature is measured in the "tem...

  • Page 71

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 70 3.3.3 setpoints (dependent setpoints) (individual setpoints) no. Function object name data type flags 12 current setpoint cooling control 2 byte k, Ü, s, l this data item forms the 2-byte knx object and ca...

  • Page 72

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 71 17 heating setpoint night mode control 2 byte k, s, Ü, l object is visible if the individual setpoint preset has been set in the parameters. This data item forms the 2-byte knx object and can be received. ...

  • Page 73

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 72 3.3.4 control value no. Function object name data type flags 24 control value heating control value 1 byte / 1 bit k, Ü, l 2 channel (4-pipe system) this data item forms the 1-byte or 1-bit knx object and ...

  • Page 74

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 73 3.3.5 heating / cooling no. Function object name data type flags 24 control value heating control value 1 byte / 1 bit k, Ü, l 1 channel (2-pipe system) this data item forms the 1-byte or 1-bit knx object ...

  • Page 75

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 74 3.3.6 fan automatic / manual no. Function object name data type flags 31 automatic on/off fan automatic / manual 1 bit eis1 dpt 1.001 k, s, Ü, l if a fan coil actuator is tripped by the ambient temperature...

  • Page 76

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 75 no. Function object name data type flags 34 switch fan coil stage 1 fan manual 1 bit eis1 dpt 1.001 k, s, Ü, l this 1-bit communication object can be used to send an on telegram, if the first fan stage is ...

  • Page 77

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 76 3.3.7 monitoring no. Function object name data type flags 37 receive in operation actuator monitoring 1 bit k, s the object is visible if the corresponding parameter is set to "yes". This object monitors t...

  • Page 78

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 77 3.3.8 alarm temperature no. Function object name data type flags 41 report failure of current temp alarm temperature 1 bit eis1 dpt 1.001 k, Ü, l this data item forms the 1-bit knx object and can be sent o...

  • Page 79

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 78 3.3.9 status byte no. Function object name data type flags 43 status byte rhcc status status byte 2 byte dpt 22.101 k, Ü, l knx status byte dpt 22.101 bit 0 failure message of current temperature recording...

  • Page 80

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 79 3.3.10 compensation no. Function object name data type flags 45 summer compensation active control 1 bit k, s, Ü, l summer compensation enabled is reported via this 1-bit communication object. This is alwa...

  • Page 81

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 80 3.3.11 fan stage - state no. Function object name data type flags 47 state stage 1 fan coil operation state 1 bit eis1 dpt 1.001 k, s this 1-bit communication object can be used by the ambient temperature ...

  • Page 82

    Abb i-bus £ knx commissioning © 2009 busch-jaeger elektro gmbh – a company of the abb group 81 3.4 special operating states behaviour after reset the behaviour after reset can be set for the operating mode, the operating type and the fan stage. Heating, cooling and the state of the object "switching...

  • Page 83

    4 planning and use this section contains tips and application examples for practical application of the device. 4.1 operating modes the ambient temperature controller has he following four operating modes: – frost protection mode (with heating): ambient temperature control is disabled; heating is on...

  • Page 84

    4.1.1 operating mode switching 1 bit the frost/heat protection has the top priority, i.E. In this case switching to a different operating mode is disabled. Frost/heat protection must be disabled first, e.G. By closing an open window. Night mode has the next higher priority, followed by comfort mode....

  • Page 85

    The second object )"operating mode switching omo") may "overwrite" the first temporarily. This means, for example, if a frost/heat protection telegram is received, the ambient temperature controller switches to frost or heat protection mode. If the frost or heat protection is reset by the receipt of...

  • Page 86

    4.2 temperature measurement the ambient temperature controller with display can record the temperature with an internal sensor. Values can also be received from an external sensor or an outside temperature sensor via communication objects. Receipt of the values can be monitored and possibly calibrat...

  • Page 87

    The room temperature controller will stop controlling and will send a predefined control value ("control value for temperature measurement error") to prevent the room from overcooling or overheating. The control value is transmitted until the ambient temperature controller receives a temperature tel...

  • Page 88

    4.3 controller the ambient temperature controller can be used for heating only, cooling only or for heating and cooling. If the ambient temperature controller is to be used for heating and cooling, it can switch automatically from heating to cooling and cooling to heating. The controller automatical...

  • Page 89

    4.3.1 2-point controller 21 °c 22 °c 20 °c istwert sollwert t t t 1 0 stellgröße hysterese note: after switching the control value on or off the room continues to heat or cool because the heating elements are still hot or cool. A 2-point controller has two output states, which switch depending on th...

  • Page 90

    4.3.2 continuous controller 21 °c istwert sollwert t t t 100% 0% stellgröße a continuous controller has a continuously changing control value, which can take values between 0 and 100%. With the knx the control value signal is converted to a 1-byte value, i.E. The control value of 0% corresponds to t...

  • Page 91

    4.3.3 pwm controller 21 °c istwert sollwert t t t 1 0 stellgröße 10 min =70%^ =50%^ =40%^ =30%^ =30%^ note: after switching the control value on or off the room continues to heat or cool because the heating elements are still hot or cool. The pwm controller has the same continuous control as a conti...

  • Page 92

    4.3.4 fan coil if fan coil is selected under "control types", the control values are output in the same way as described at continuous controllers. A fan coil also has the option of controlling fan stages using a 1-byte or three 1-bit communication objects with a fan coil actuator. Switching fan sta...

  • Page 93

    21 °c istwert sollwert t t wendepunkt tu tu = verzugszeit tn = nachstellzeit tn = 3 * tu 4.3.6 two-stage heating and cooling in specific instances such as when using underfloor heating, it may be necessary to install a quick additional stage for the heat control in order to warm up the room rapidly....

  • Page 94

    4.4 setpoints the ambient temperature controller can be operated with dependent or individual setpoints. The two options are explained in more detail below. 4.4.1 dependent setpoints sollwerte heizen sollwerte kühlen frost/hitzschutz- betrieb regler fordert keine leistung (stellgröße = 0) komfort- b...

  • Page 95

    "setpoint heating" is the default setting. In regions where the cooling function is more important, it is recommended that you change this parameter to "setpoint cooling". This makes it easier to set the ambient temperature controller and raise the cooling setpoints (standby temperature cooling and ...

  • Page 96

    4.4.3 minimum distance the adjustable parameter "minimum distance between heating and cooling" is enabled with both dependent and individual setpoints. The minimum distance is always between "heating setpoint comfort mode" and "cooling setpoint comfort mode". It acts as a buffer zone to prevent the ...

  • Page 97

    4.5 fan coil general ventilator convectors, also referred to as blower convectors or fan coil units, are used for decentralised heating and cooling. They are mounted in the room and supplied by a central heating and cooling system. A distinction is made between 2-pipe and 4-pipe systems (see also pa...

  • Page 98

    For example, to prevent excessive noise during the night in hotel rooms, a "stage limitation in night mode" can be set. This means that only the specified fan stage or lower will be used in night mode. When switching to another operating mode all fan stages can still be used. A limitation can be set...

  • Page 99

    4.6 compensation the fan coil ambient temperature controller with display has summer compensation and winter compensation modes. Both are explained in detail below. 4.6.1 summer compensation to save energy and to maintain the temperature differential when entering an air-conditioned building, you sh...

  • Page 100

    30 20 10 10 20 30 40 25 außentemperatur/°c sollwert/°c note: co is shown in the display of the ambient temperature controller with active compensation. 4.6.2 winter compensation to improve comfort and to maintain a reasonable temperature differential when entering a room with a large window area, yo...

  • Page 101

    © 2009 busch-jaeger elektro gmbh – a company of the abb group 100 example: parameters for "heating setpoint comfort" 21 °c are defined in the bottom graph. With falling outside temperature the parameterised setpoint is adjusted from an outside temperature of 10 °c from 21 °c to 25 °c. The 25 °c is r...

  • Page 102