ABB REF601 Applications Manual

Manual is about: Feeder/Motor protection and control

Summary of REF601

  • Page 1

    605 series / relion® protection and control feeder protection and control feeder protection ref601 / rej601 application manual.

  • Page 2

    Document id: 1mdu07212-yn issued: 2014-06-23 revision: revision: c product version: 2.2fp1 © copyright 2014 abb. All rights reserved.

  • Page 3

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and ...

  • Page 4

    Disclaimer the data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intende...

  • Page 5

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents ref601 / rej601 1 application manual table of contents section 1 general ................................................................... 5 1.1 this manual ..................................................................................................... 5 1.2 intended audien...

  • Page 8

    Table of contents 2 ref601 / rej601 application manual 4.2 earth fault protection ................................................................................... 17 4.2.1 functionality ............................................................................................ 17 4.2.2 principle...

  • Page 9

    Table of contents ref601 / rej601 3 application manual 4.14 breaker control and trip command operation ............................................... 36 4.15 trip circuit supervision ................................................................................. 36 section 5 use of lhmi ............

  • Page 10

    Table of contents 4 ref601 / rej601 application manual 6.8 accessories and ordering data ..................................................................... 64 6.9 setting table ................................................................................................. 65 6.10 earthing of re...

  • Page 11

    1mdu07212-yn rev. C section 1 general ref601 / rej601 5 application manual section 1 general 1.1 this manual this manual contains application and functionality descriptions and connection diagrams, input and output signals, setting parameters and technical data. The manual can be used as a technical...

  • Page 12

    Section 1 general 6 1.4 section 1 general 1.4 section 1 general section 1 general section 1 document symbol and conventions this publication includes the following icons that point out safety conditions or other important information: safety indication symbols document symbol and conventions this pu...

  • Page 13

    1mdu07212-yn rev. C section 2 ref601/rej601 overview ref601 / rej601 7 application manual section 2 ref601/rej601 overview 2.1 overview ref601/rej601 is a dedicated feeder protection relay, intended for the protection of utility substations and industrial power systems, in primary and secondary dist...

  • Page 14

    Section 2 1mdu07212-yn rev. C ref601/rej601 overview 8 ref601 / rej601 application manual 2.2 product version history product version release date product history 1.0 20.03.2009 product released 1.0 sp1 21.08.2009 service pack released 2.0 04.04.2012 version 2.0 released 2.1 28.09.2012 version 2.1 r...

  • Page 15

    1mdu07212-yn rev. C section 2 ref601/rej601 overview ref601 / rej601 9 application manual table 1: relay functions, continue related products rej601 / ref601 rej601 / ref601 ref601 functionality ansi iec b c d protection phase discontinuity protection 46pd i2/i1> - ● ● negative-sequence overcurrent ...

  • Page 16

    Section 2 1mdu07212-yn rev. C ref601/rej601 overview 10 ref601 / rej601 application manual at normal condition (no internal fault), the green ready led glow and the self- supervision output contact is closed. When an internal fault is detected in the ied, the green led ceases to glow and the self-su...

  • Page 17

    1mdu07212 ref601 / rej601 application manual 2.4.2 2.4.3 1mdu07212 ref601 / rej601 application manual 2.4.2 2.4.3 1mdu07212 ref601 / rej601 application manual 2.4.2 2.4.3 1mdu07212-yn ref601 / rej601 application manual yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 application m...

  • Page 18

    Section 2 1mdu07212-yn rev. C ref601/rej601 overview 12 ref601 / rej601 application manual table 3: list of event types and related description sr. No. Event type description data considered 1 power supply presence unit ready contact activation will be stored as an event. This unit ready contact is ...

  • Page 19

    1mdu07212-yn rev. C section 2 ref601/rej601 overview ref601 / rej601 13 application manual sr. No. Event type description data considered 4 protection start on thermal alarm output signal for both rising & falling signal 3ith> alarm ↑ 3ith> alarm ↓ 5 protection trip in the event of tripping, which p...

  • Page 20

    Section 2 1mdu07212-yn rev. C ref601/rej601 overview 14 ref601 / rej601 application manual sr. No. Event type description data considered 17 power off when binary input is mapped to register power off situation & power supply to ied goes off. Power off 18 breaker failure stage 1, 2 output on breaker...

  • Page 21

    1mdu07212-yn rev. C section 2 ref601/rej601 overview ref601 / rej601 15 application manual sr. No. Event type description data considered 32 start an event for general start will be capture for both rising and falling which will be from any of start of i>,i>>, i>>> ,io> ,io>>, i2>, i2/i1> start ↑ st...

  • Page 22

    Section 3 1mdu07212-yn rev. C technical data 16 ref601 / rej601 application manual section 3 technical data for detailed technical data please refer the product guide. Section 4 protection and control function 4.1 three phase overcurrent protection 4.1.1 functionality the three-phase overcurrent pro...

  • Page 23

    1mdu07212-yn rev. C section 4 protection and control function ref601 / rej601 17 application manual table 5: setting ranges non-directional overcurrent protection, high stage 3i>>, 50-1 description value setting range of pick-up current i>> 0.2...25 x in in steps 0.001, infinite for ct variant 0.2…2...

  • Page 24

    Section 4 1mdu07212-yn rev. C protection and control function 18 ref601 / rej601 application manual 4.2.3 setting range of earth fault overcurrent protection table 7: setting ranges non-directional earth fault protection, low stage io>, 51n description value nominal value of earth current 1 a or 5a ...

  • Page 25

    1mdu07212-yn rev. C section 4 protection and control function ref601 / rej601 19 application manual 4.4 negative-sequence overcurrent protection 4.4.1 functionality the negative-sequence overcurrent protection is used for increasing sensitivity to detect unbalance load or unsymmetrical feeder voltag...

  • Page 26

    Section 4 1mdu07212-yn rev. C protection and control function 20 ref601 / rej601 application manual 4.5.2 principle of operation the unbalance of network is detected by monitoring the ratio of negative sequence current to positive sequence current i 2 /i 1 . The function operates when the ratio of u...

  • Page 27

    1mdu07212-yn rev. C section 4 protection and control function ref601 / rej601 21 application manual 4.6.2 principle of operation the operation of the breaker failure protection can be described using a module diagram. Figure 3: circuit breaker failure protection functional module diagram the measure...

  • Page 28

    Section 4 1mdu07212-yn rev. C protection and control function 22 ref601 / rej601 application manual backup trip function the timer 2 for backup trip function activates after timer 1 expires. Once activated, the timer runs until the set t backup value has elapsed. The time characteristic is according...

  • Page 29

    1mdu07212 ref601 application manual 4.8 4.8.1 4.8.2 1mdu07212 ref601 application manual 4.8 4.8.1 4.8.2 1mdu07212 ref601 / rej601 application manual 4.8.1 4.8.2 1mdu07212-yn / rej601 application manual yn rev. C / rej601 application manual rev. C / rej601 application manual rev. C auto functionality...

  • Page 30

    Section 4 protection and control function 24 section 4 protection and control function section 4 protection and control function section 4 protection and control function section 4 protection and control function protection and control function protection and control function protection and control ...

  • Page 31

    1mdu07212-yn rev. C section 4 protection and control function ref601 / rej601 25 application manual 4.8.2.1 setting range for auto-reclose function table 13 setting ranges for auto-reclose function i o, 79 parameter description range unit step default o→i start mode auto reclose initialization mode ...

  • Page 32

    Section 4 1mdu07212-yn rev. C protection and control function 26 ref601 / rej601 application manual 4.9 thermal overload protection 4.9.1 functionality the thermal overload protection protects the apparatus from overheating, which causes the premature insulation failures. The protection function has...

  • Page 33

    1mdu07212 ref601 / rej601 application manual 1mdu07212 ref601 / rej601 application manual 1mdu07212 ref601 / rej601 application manual 1mdu07212-yn ref601 / rej601 application manual yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 application manual rev. C thermal characteristic ...

  • Page 34

    Section 4 protection and control function 28 section 4 protection and control function section 4 protection and control function section 4 protection and control function section 4 protection and control function protection and control function protection and control function protection and control ...

  • Page 35

    1mdu07212 ref601 / rej601 application manual 1mdu07212 ref601 / rej601 application manual 1mdu07212 ref601 / rej601 application manual 1mdu07212-yn ref601 / rej601 application manual yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 application manual rev. C interrupted) to calcula...

  • Page 36

    Section 4 1mdu07212-yn rev. C protection and control function 30 ref601 / rej601 application manual 4.9.2.1 setting range for thermal overload protection table 16 setting range for thermal overload protection 3ith, 49 parameter description range unit step default mode ϑ mode of thermal overload prot...

  • Page 37

    1mdu07212-yn rev. C section 4 protection and control function ref601 / rej601 31 application manual 4.10 protection characteristics 4.10.1 time / current characteristics relay offers three-stage overcurrent and two stage earth-fault protection functions. The low-set stage of overcurrent protection a...

  • Page 38

    Section 4 1mdu07212-yn rev. C protection and control function 32 ref601 / rej601 application manual 4.10.3 ansi c37.112 idmt characteristic the relationship between current and time for standard moderate inverse, normal inverse, very inverse, extremely inverse complies with the ansi c37.112 standard...

  • Page 39

    1mdu07212 ref601 / rej601 application manual 4.11 1mdu07212 ref601 / rej601 application manual 4.11 1mdu07212 ref601 / rej601 application manual 4.11 1mdu07212-yn ref601 / rej601 application manual yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 application manual rev. C configur...

  • Page 40

    Section 4 1mdu07212-yn rev. C protection and control function 34 ref601 / rej601 application manual · external close command available at binary input (configured for breaker command operation) as well command available from modbus / iec_103 or front hmi · external user defined signal 1 to signal 3 ...

  • Page 41

    1mdu07212 ref601 / rej601 application manual 4.13 mdu07212 ref601 / rej601 application manual 4.13 mdu07212 ref601 / rej601 application manual 4.13 mdu07212-yn ref601 / rej601 application manual yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 application manual rev. C table confi...

  • Page 42

    Section 4 1mdu07212-yn rev. C protection and control function 36 ref601 / rej601 application manual 4. Reset: binary input bi2 to bi4 can be configured for reset operation. When the rising edge is detected, the ied resets all the protection and control functions (all internal timers are reset). It a...

  • Page 43

    1mdu07212-yn rev. C section 4 protection and control function ref601 / rej601 37 application manual figure 8: application diagram of tcs function when the circuit breaker is open, tcs measure the voltage across the trip contact through rext (external shunt resistance shown in below figure) and trip ...

  • Page 44

    Section 5 1mdu07212-yn rev. C use of lhmi 38 ref601 / rej601 application manual section 5 use of lhmi 5.1 overview figure 10: local hmi of relay ref601/rej601 the local hmi of the relay contains following elements: · led indicators · lcd display · navigation buttons / keys the lhmi is used for setti...

  • Page 45

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 39 application manual back used for going to higher level of menu item from its lower level submenu. Next used for going to lower level submenu from higher level menu. Enter used for saving of edited parameter value. Escape/cancel a) used for...

  • Page 46

    Section 5 1mdu07212-yn rev. C use of lhmi 40 ref601 / rej601 application manual 5.1.4 authorization to protect the relay from unauthorized access and to maintain the integrity of information, the relay is armed with a three level, role based user authentication system with individual password for op...

  • Page 47

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 41 application manual in case of wrong password being entered by the user, automatically the operator user category is selected. The selected category will pop up for one second before the main menu is shown. Sequence looks as follow: figure ...

  • Page 48

    Section 5 1mdu07212-yn rev. C use of lhmi 42 ref601 / rej601 application manual 5.2 lhmi menu navigation 5.2.1 default screen the default view of the relay displays the largest phase current and earth current which is indicated in fig. 10. The relay returns to default screen after 5 minutes if no ke...

  • Page 49

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 43 application manual 5.2.3 menu – measurement submenu measurement shows analogue input values as primary or as secondary values according to primary and secondary current of current transformer selected in the submenu configuration – setting...

  • Page 50

    Section 5 1mdu07212-yn rev. C use of lhmi 44 ref601 / rej601 application manual 5.2.4 menu – fault record submenu fault record shows under recorded current the fault records for the last five protection trips and the values for trip counters segregated in phase fault trips and earth fault trips. For...

  • Page 51

    1mdu07212 ref601 / rej601 application manual 5.2.6 1mdu07212 ref601 / rej601 application manual 5.2.6 1mdu07212 ref601 / rej601 application manual 5.2.6 1mdu07212-yn ref601 / rej601 application manual yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 application manual rev. C menu ...

  • Page 52

    Section 5 1mdu07212-yn rev. C use of lhmi 46 ref601 / rej601 application manual figure 19: setting menu of relay ref601/rej601 with its submenu.

  • Page 53

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 47 application manual 5.2.7 menu – configuration · submenu configuration and respective submenus shows and allows depending on the user right to change · blocking of particular protection stage or remote trip activation · relay configuration ...

  • Page 54

    Section 5 1mdu07212-yn rev. C use of lhmi 48 ref601 / rej601 application manual.

  • Page 55

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 49 application manual.

  • Page 56

    Section 5 1mdu07212-yn rev. C use of lhmi 50 ref601 / rej601 application manual inrush inrush ratio :xxxx % inrush i inr :xx.Xx in factory settings load :yyy protection reset yyy 30; 50 for sensor - 00.20; 20.00 for ct - 00.20; 25.00 no; yes no; yes clock settings date settings dd/mm/yyyy time setti...

  • Page 57

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 51 application manual 5.2.8 menu – test submenu test and respective submenus shows and allows depending on the user right to perform several kind of tests to verify the ied functionality: test -> hardware: enables internal hardware tests, whi...

  • Page 58

    Section 5 1mdu07212-yn rev. C use of lhmi 52 ref601 / rej601 application manual 5.2.8.1 menu – hardware following functionalities can be tested through this menu. · lcd test · keyboard test · led test during each test wherever confirmation from user is asked to continue test sequence, if no selectio...

  • Page 59

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 53 application manual figure 23: hardware test menu of relay ref601/rej601 with its submenu (continue).

  • Page 60

    Section 5 1mdu07212-yn rev. C use of lhmi 54 ref601 / rej601 application manual figure 23: hardware test menu of relay ref601/rej601 with its submenu (continue) 5.2.8.2 submenu – binary output test submenu binary output test allows to force a binary output. The forced output operates for a pulse dur...

  • Page 61

    1mdu07212-yn rev. C section 5 use of lhmi ref601 / rej601 55 application manual 5.2.8.3 submenu – functional test submenu functional test allows performing simulation of each protection function by giving a test current to the selected protection function. Figure 25: functional test menu of relay re...

  • Page 62

    Section 5 1mdu07212-yn rev. C use of lhmi 56 ref601 / rej601 application manual 5.2.10 version information this menu provides information regarding the product type selected, software version being presently loaded into the product, model name, nominal current value selected, and the type of trip ci...

  • Page 63

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 57 application manual section 6 installation 6.1 unpacking and inspecting the device ref601/rej601 products, although of robust construction, require careful handling prior to installation on site. The delivered products should always be exa...

  • Page 64

    Section 6 1mdu07212-yn rev. C installation 58 ref601 / rej601 application manual 6.4 relay wiring the connection wiring to the relay should be made by using single strand wire or stranded wire with the use of insulated crimp terminal to maintain the insulation requirements. The wire with below indic...

  • Page 65

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 59 application manual figure 28: overall mounting dimension of ref601/rej601 with ct variant figure 29: overall mounting dimension of ref601/rej601 with sensor variant.

  • Page 66

    Section 6 installation 60 section 6 installation section 6 installation section 6 installation section 6 installation installation figure 151.5 figure 1.5 ± 0.5 figure 30 ± 0.5 30: ± 0.5 panel mounting details of panel mounting details of panel mounting details of panel mounting details of panel mou...

  • Page 67

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 61 application manual 6.6 terminal diagram relay terminal / connection diagram for both conventional ct as well sensor variant shall be as the relay. Figure 31: connection diagram of relay ref601 /rej601 with ct variant.

  • Page 68

    Section 6 1mdu07212-yn rev. C installation 62 ref601 / rej601 application manual figure 32: connection diagram of relay ref601 /rej601 with sensor variant.

  • Page 69

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 63 application manual 6.7 relay ordering information the relay type and serial number label identifies the protection relay. An order number label is placed on the side of the relay. The order number consists of a string of codes generated f...

  • Page 70

    Section 6 1mdu07212-yn rev. C installation 64 ref601 / rej601 application manual 6.8 accessories and ordering data table 28: ref601/rej601 accessories and ordering data item order number re_601 communication card cim601bnnnnbanxh.

  • Page 71

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 65 application manual 6.9 setting table table 29: settings parameter actual value default value unit range resolution 3i> / 51 i> 01.50 in 0.1...2.5; infinite 0.001 t> 01.00 s 0.04…64 0.010 i> curve dt - dt, iec ni, iec vi, iec li, iec ei, r...

  • Page 72

    Section 6 1mdu07212-yn rev. C installation 66 ref601 / rej601 application manual table 29: settings, continue parameter actual value default value unit range resolution 3ith> / 49 ϑ0 080 % 0.0…100% 1% ϑpoweroff 4 - 1…4 1 ib 1.0 in 0.1 … 1.5 0.100 τ ↑ 045 min 1.0…300 1.000 τ ↓s 045 min 1.0…300 1.000 ...

  • Page 73

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 67 application manual table 30: configuration configuration parameter actual value default value unit range resolution blocking: i> / 51 no - no; yes - blocking: i>> / 50-1 no - no; yes - blocking: i>>> / 50-2 no - no; yes - blocking: io> / ...

  • Page 74

    Section 6 1mdu07212-yn rev. C installation 68 ref601 / rej601 application manual table 31: binary input configuration binary input connected to signal bi1 bi2 bi3 bi4 input behavior: inversion (-) (-) (-) (-) block : i> / 51 block : i>> / 50-1 block : i>>> / 50-2 block : io> / 51n block : io>> / 50n...

  • Page 75

    1mdu07212-yn rev. C section 6 installation ref601 / rej601 69 application manual table 32: binary output configuration, continue binary output signal to activate output bo1 bo2 bo3 bo4 bo5 bo6 3ith > alm 3ith> blkcl i2/i1> str i2> start trip : i> / 51 (x) (x) (x) trip : i>> / 50-1 (x) (x) (x) trip :...

  • Page 76

    Section 6 1mdu07212-yn rev. C installation 70 ref601 / rej601 application manual table 33: binary output configuration, continue configurable led signal to activate output led1 led2 led3 led4 led5 led behavior: s=self reset h=hold (h) (h) (s) (h) (h) start : i> / 51 trip : i> / 51 (x) start : i>> / ...

  • Page 77

    1mdu07212 ref601 / rej601 application manual 6.10 6.10.1 1mdu07212 ref601 / rej601 application manual 6.10 6.10.1 1mdu07212 ref601 / rej601 application manual 6.10 6.10.1 1mdu07212-yn ref601 / rej601 application manual 6.10.1 yn rev. C ref601 / rej601 application manual rev. C ref601 / rej601 applic...

  • Page 78

    Section 6 1mdu07212-yn rev. C installation 72 ref601 / rej601 application manual 3. Tighten the protective earth screw. 4. Support the earth lead so that it cannot break or weaken. Be aware of the mechanical, chemical and electrochemical environment. 6.10.2 shield connection at relay side (sensor va...

  • Page 79

    Abb limited distribution automation maneja vadodara 390013, india phone +91 265 2604032 fax +91 265 2638922 abb oy distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/substationautomation d oc id © c op yri gh t2 01 4 a b b .A ll rig ht s...