ABB REF601 Product Manual

Manual is about: Feeder/Motor protection and control

Summary of REF601

  • Page 1

    Relion ® 605 series feeder protection and control / feeder protection ref601 / rej601 product guide.

  • Page 2

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 2 abb contents 1. Description ............................................................. 3 2. Relay functions....................................................... 3 3. Protection functions ......

  • Page 3

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 3 abb 1.Description ref601/rej601 is a dedicated feeder protection relay, intended for the protection of utility substations and industrial power systems, in primary ...

  • Page 4

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 4 abb table 3. Application configurations and supported functions, continued related products rej601 / ref601 functionality ansi iec e control breaker control functi...

  • Page 5

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 5 abb figure 1. Functionality overview for ref601 standard configuration e with current transformer inputs 4.Application the ref601/rej601 is a protection relay aimed...

  • Page 6

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 6 abb 6.Control the relay offers control of one circuit breaker with dedicated push-buttons and guidance on local hmi for opening and closing. It includes two dedica...

  • Page 7

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 7 abb for the operator, engineer and administrator level. There is availability of 2 different password protection, one which is a combination of different navigation...

  • Page 8

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 8 abb 17.Technical data table 5. Dimensions relay type description value width frame 130.0 mm case 121.5 mm height frame 160.0 mm case 151.5 mm depth 151.5 mm weight...

  • Page 9

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 9 abb table 8. Binary input description value rated voltage 24...240 v ac / dc operating range 85...110% of un for ac and 70...120% of un for dc current drain 2...20 ...

  • Page 10

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 10 abb table 11.Signal output and irf output (xk2 : bo3, bo4, bo5, bo6) description value rated voltage 240 v ac/dc continuous contact carry 6 a make and carry for 3...

  • Page 11

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 11 abb table 14.Environmental tests description type test value reference dry heat test (humidity  working  storing  96 h at +70°c  96 h at +85°c iec 60068-2-2 ie...

  • Page 12

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 12 abb table 16.Electromagnetic compatibility tests, continue description type test value reference power frequency magnetic field immunity test:  continuous short ...

  • Page 13

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 13 abb table 18.Mechanical tests description type test value reference vibration tests  response endurance / withstand 10...150 hz, 0.035 mm / 1.0g, 1 sweep / axis 1...

  • Page 14

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 14 abb 18.Protection functions table 23.Low-set phase overcurrent protection, stage 3i> / 51 parameter value (range) setting range of pick-up current ‘i >’ 0.5...2.5...

  • Page 15

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 15 abb table 26.Low-set earth-fault protection, stage io> / 51n parameter value (range) setting range of pick-up current ‘io>’ external earth measurement : 0.05...2.0...

  • Page 16

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 16 abb table 28.Transformer inrush detection, 3i2f> / 68 parameter value (range) inrush threshold value 0.5...25 x in, in steps of 0.01 ratio setting 30%...50%, in s...

  • Page 17

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 17 abb table 31.Negative sequence overcurrent protection, i2> / 46 parameter value (range) start value, ‘i2>” 0.1…1.5 x in, in steps of 0.01 operate delay time, ‘ti2>...

  • Page 18

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 18 abb table 34.Counter parameter value (range) initial value of the counter at the start of ied, ‘value’ 0…65535, in steps of 1 binary input configured at pulse_inp...

  • Page 19

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 19 abb 19.Dimensions and mounting the ref601/rej601 have been equipped with in-built press-fit mechanism. Without using any additional mounting accessories, the ref60...

  • Page 20

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 20 abb 20.Selection and ordering data the relay type and serial number label identifies the protection relay. An order number label is placed on the side of the rela...

  • Page 21

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 21 abb 22.Terminal diagram figure 4. Terminal diagram of ref601/rej601.

  • Page 22

    Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 22 abb 23.References the www.Abb.Com/substationautomation portal offers you information about the distribution automation product and service range. You will find th...

  • Page 24

    Contact us abb india ltd, distribution automation maneja works vadodara-390013, india phone: +91 265 6724402 fax: +91 265 6724407 abb oy, distribution automation p.O. Box 699 fi-65101 vaasa, finland phone: +358 10 22 11 fax: +358 10 22 41094 www.Abb.Com/mediumvoltage www.Abb.Com/substationautomation...