Relion ® 605 series feeder protection and control / feeder protection ref601 / rej601 product guide.
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 2 abb contents 1. Description ............................................................. 3 2. Relay functions....................................................... 3 3. Protection functions ......
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 3 abb 1.Description ref601/rej601 is a dedicated feeder protection relay, intended for the protection of utility substations and industrial power systems, in primary ...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 4 abb table 3. Application configurations and supported functions, continued related products rej601 / ref601 functionality ansi iec e control breaker control functi...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 5 abb figure 1. Functionality overview for ref601 standard configuration e with current transformer inputs 4.Application the ref601/rej601 is a protection relay aimed...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 6 abb 6.Control the relay offers control of one circuit breaker with dedicated push-buttons and guidance on local hmi for opening and closing. It includes two dedica...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 7 abb for the operator, engineer and administrator level. There is availability of 2 different password protection, one which is a combination of different navigation...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 8 abb 17.Technical data table 5. Dimensions relay type description value width frame 130.0 mm case 121.5 mm height frame 160.0 mm case 151.5 mm depth 151.5 mm weight...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 9 abb table 8. Binary input description value rated voltage 24...240 v ac / dc operating range 85...110% of un for ac and 70...120% of un for dc current drain 2...20 ...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 10 abb table 11.Signal output and irf output (xk2 : bo3, bo4, bo5, bo6) description value rated voltage 240 v ac/dc continuous contact carry 6 a make and carry for 3...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 11 abb table 14.Environmental tests description type test value reference dry heat test (humidity working storing 96 h at +70°c 96 h at +85°c iec 60068-2-2 ie...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 12 abb table 16.Electromagnetic compatibility tests, continue description type test value reference power frequency magnetic field immunity test: continuous short ...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 13 abb table 18.Mechanical tests description type test value reference vibration tests response endurance / withstand 10...150 hz, 0.035 mm / 1.0g, 1 sweep / axis 1...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 14 abb 18.Protection functions table 23.Low-set phase overcurrent protection, stage 3i> / 51 parameter value (range) setting range of pick-up current ‘i >’ 0.5...2.5...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 15 abb table 26.Low-set earth-fault protection, stage io> / 51n parameter value (range) setting range of pick-up current ‘io>’ external earth measurement : 0.05...2.0...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 16 abb table 28.Transformer inrush detection, 3i2f> / 68 parameter value (range) inrush threshold value 0.5...25 x in, in steps of 0.01 ratio setting 30%...50%, in s...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 17 abb table 31.Negative sequence overcurrent protection, i2> / 46 parameter value (range) start value, ‘i2>” 0.1…1.5 x in, in steps of 0.01 operate delay time, ‘ti2>...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 18 abb table 34.Counter parameter value (range) initial value of the counter at the start of ied, ‘value’ 0…65535, in steps of 1 binary input configured at pulse_inp...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 19 abb 19.Dimensions and mounting the ref601/rej601 have been equipped with in-built press-fit mechanism. Without using any additional mounting accessories, the ref60...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 20 abb 20.Selection and ordering data the relay type and serial number label identifies the protection relay. An order number label is placed on the side of the rela...
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2fp2 issued: 2017-05-09 revision: a 21 abb 22.Terminal diagram figure 4. Terminal diagram of ref601/rej601.
Feeder protection and control / feeder protection 1mdb07221-yn ref601 / rej601 product version: 2.2 fp2 issued: 2017-05-09 revision: a 22 abb 23.References the www.Abb.Com/substationautomation portal offers you information about the distribution automation product and service range. You will find th...
Contact us abb india ltd, distribution automation maneja works vadodara-390013, india phone: +91 265 6724402 fax: +91 265 6724407 abb oy, distribution automation p.O. Box 699 fi-65101 vaasa, finland phone: +358 10 22 11 fax: +358 10 22 41094 www.Abb.Com/mediumvoltage www.Abb.Com/substationautomation...