ABB REF601 Product Manual

Manual is about: Feeder/Motor protection and control

Summary of REF601

  • Page 1

    Relion ® 605 series relion ® 605 series feeder protection and control ref601 product guide relion ® 605 series.

  • Page 2

    Abb 2 1mdb07207-yn feeder protection ref601 product version: 2.0 contents 1. Description ..... .................................................................3 2. Relay functions.............................................. .... ...... . .......3 3. Protection functions..............................

  • Page 3

    Abb 3 1mdb07207-yn feeder protection ref601 product version: 2.0 1. Description ref601 is a dedicated feeder protection relay, intended for the protection and control of utility substations and industrial power systems, in primary and secondary distribution networks. Ref601 is a member of abb’s reli...

  • Page 4

    Abb 4 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 3. Protection functions ref601 offers three-stage phase segregated overcurrent and two-stage earth-fault protection functions. The transformer inrush detector function is incorporated to ...

  • Page 5

    Abb 5 1mdb07207-yn feeder protection ref601 product version: 2.0 coil is not current, but a voltage. Due to absence of ferromagnetic core, the sensor is linear up to the highest currents. The wide measurement range of sensors with high accuracy eliminates the need for high variants of conventional i...

  • Page 6

    Abb 6 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 11. Trip-circuit supervision the trip-circuit supervision continuously monitors the availability and operability of the trip circuit. It provides open-circuit monitoring both when the cir...

  • Page 7

    Abb 7 1mdb07207-yn feeder protection ref601 product version: 2.0 16. Technical data table 2. Dimensions description value height frame 160.0 mm case 151.5 mm table 3. Power supply width frame 130.0 mm case 121.5 mm depth case 102.0 mm (92 + 10 mm) weight relay 1.2 kg table 4. Energizing inputs descr...

  • Page 8

    Abb 8 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 table 5. Binary input description value rated voltage 24...240 v ac / dc operating range 85...110% of u aux for ac and 70...120% of u aux for dc input sensing time 100 ms table 6. Double-...

  • Page 9

    Abb 9 1mdb07207-yn feeder protection ref601 product version: 2.0 table 9. Degree of protection of relay description value front side ip 43 side with terminal connector ip 20 table 10. Environmental conditions description value operating temperature range -25...+55 º c short-time service temperature ...

  • Page 10

    Abb 10 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 table 12. Electromagnetic compatibility tests description type test value reference 1 mhz burst disturbance test: iec 61000-4-12 iec 60255-22-1, class iii 2.5 kv, 1mhz, 400 pulses/sec 1....

  • Page 11

    Abb 11 1mdb07207-yn feeder protection ref601 product version: 2.0 description type test value reference emission tests: iec 60255-25 en 55011-cispr ii • conducted 150 khz-0.5 mhz table 13. Electromagnetic compatibility tests, continued • radiated table 14. Insulation tests description type test valu...

  • Page 12

    Abb 12 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 description type test value table 16. Product safety lv directive 2006/95/iec standard en 60255-27 (2005) en 60255-1 (2009) description type test value table 17. Emc compliance emc direc...

  • Page 13

    Abb 13 1mdb07207-yn feeder protection ref601 product version: 2.0 17. Protection functions table 20. Low-set phase overcurrent protection, stage i> / 51 parameter value (range) setting range of pick-up current ‘i >’ 0.2...1.0 x i n in steps 0.025, infinite operation accuracy ± 5.0% of set value oper...

  • Page 14

    Abb 14 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 table 23. Low-set earth-fault protection, stage i o > / 51n parameter value (range) internal earth measurement : 0.2...1.0 x i n in steps 0.05, infi nite operation accuracy external eart...

  • Page 15

    Abb 15 1mdb07207-yn feeder protection ref601 product version: 2.0 table 25. Transformer inrush detector parameter value (range) inrush threshold value 0.2...20 x i n ratio setting 30%...50%.

  • Page 16

    Abb 16 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 18. Dimensions and mounting the ref601 have been equipped with in-built press- fit mechanism. Without using an additional mounting accessories, the ref601 can be easily flush mount- ed o...

  • Page 17

    Abb 17 1mdb07207-yn feeder protection ref601 product version: 2.0 19. Selection and ordering data the relay type and serial number label identifies the protection relay. An order number label is placed on the side of the relay. The order number consists of a string of codes generated from the hardwa...

  • Page 18

    Abb 18 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 20. Accessories and ordering data table 26. Compatible sensors item order number kevcr for integrated circuit-breakers type vd4/hd4 kevcr24oc2r0101, 630a kevcr24ac2r0102, 1250a keca for ...

  • Page 19

    Abb 19 1mdb07207-yn feeder protection ref601 product version: 2.0 21. Terminal diagram figure 7. Terminal diagram of ref601 ref601 xk5 xk6 xk7 il1 diff il2 diff il3 diff xk8 1 2 io (1a) xk4 1 2 bi : remote trip 3 4 bi : remote reset uaux 1 2 xk9 3 4 xk10 1 2 trip1 * xk2 1 2 e/f trip 3 4 5 6 o/c trip...

  • Page 20

    Abb 20 guid-89a9f7df-fb82-4e8d-b449-7c0bb51c1dca v1 en 1mdb07207-yn feeder protection ref601 product version: 2.0 22. References the www.Abb.Com/substationautomation portal offers you information about the distribution automa- tion product and service range. You will find the latest relevant informa...

  • Page 22

    Contact us 1mdb07207-yn e © copyright 2012 abb. All rights r eserved. Abb ltd, distribution automation maneja works vadodara-390013, india phone: +91 265 2604386 fax: +91 265 2638922 www.Abb.Com/substationautomation.