Ekip Dip protection release | 8 - Default parameters
51 | © 2014
ABB |
1SDH000999R0002 - L8569
8 - Default parameters
Ekip DIP default parameters
The Ekip Dip releases are supplied with the following default parameters, some adjustable with the front dip-
switch (protections, Frequency, Neutral), other via front bus.
Protection/Parameter
Value
L
1 In; 144 s
S
(1)
Off; 0.1 s
I
4 In
G
(1)
Off; 0.1 s
Frequency
50 Hz (IEC) / 60 Hz (UL)
Neutral
Off (for circuit breakers three-pole).
50 % (for four-pole circuit-breaker)
Hardware Trip
Disabled
Measurement interval
5 minutes
Local Bus
Disabled
Alive LED
Disabled (Power LED on fixed)
(1)
Protection S available with LSI and LSIG versions of the release. Protection G available with LSIG version.