Accessories
(*)
to be che-
cked
Procedure
Closing coil with Ekip Com
Actuator
1. Power the protection release with the Vaux auxiliary power supply.
2. Power the Ekip Com Actuator contacts.
3. Load the springs.
4. Select
“close CB”
from the Ekip Touch menu
Result: The circuit-breaker closes correctly; the signals are normal.
NOTE!
The test can be performed if the protection release and the
coils are energized.
Lock for circuit-breaker in
open position (key or padlock)
1. Open the circuit-breaker
2. Keep the opening push-button pressed
3. Turn the key and remove it
4. Attempt the circuit-breaker closing operation.
Result: Both manual and electrical closing are prevented.
Auxiliary contacts of the
circuit-breaker
1. Connect the auxiliary contacts to appropriate signalling circuits or to
the multimeter.
2. perform some closing and opening operations on the circuit-breaker.
Result: signalling occurs normally.
Circuit-breaker connected,
isolated for test, disconnected
auxiliary contacts
1. Connect the auxiliary contacts to appropriate signalling circuits.
2. next bring the circuit-breaker to the connected, isolated for test and
disconnected position.
Result: the signals due to the relative operations are normal.
Interlocking devices of the
circuit-breaker connected and
extracted
(**)
1. Perform operating tests.
Result: the locks function correctly.
Interlock devices between cir-
cuit breakers assembled side
by side and stacked
1. Perform operating tests.
Result: the locks function correctly.
Device insertion and extrac-
tion
(**)
1. Perform a few racking-in and racking-out operations.
Result: in the rack-in operation the circuit-breaker is connected correctly.
There is no particular resistance during the first turns of the handle.
Auxiliary accessories and
auxiliary voltage
Verify the installation The value of the power supply auxiliary voltage of the
auxiliary accessories must be between 85% and 110% of the rated volt-
age for the auxiliary accessories.
Modules
1. Power the protection release
Result: Verify that Power LED is lit up on each accessory present.
Make sure that the Local Bus communication line is activated on the
protection release.
External connections
1. In the case of Neutral external sensors, single-pole or differential, to set
the model and protection parameters appropriately.
Result: No alarm present on the protection release.
WARNING! During this phase the circuit-breaker must be
open and withdrawn (if withdrawable).
(*)
if present.
(**) only withdrawable versions.