ABB VersaRupter Installation, Operation And Maintanance Manual - page 39
Manual is about: MV Indoor Switch 4.76-38 kV, 200-1200 A, 40 & 61 kA
of
83
VersaRupter MV Indoor Switch | Installation and Operation Manual
39
Installing the Direct Drive Handle
Refer to the drawings “Direct Drive Handle Right Side/Left
Side” for details.
1. Ensure that the VersaRupter is closed and the handle
is in the closed position.
2. Mount the direct drive handle to the switchgear enclo-
sure using a 9/16” socket making sure the hub assem-
bly slides onto the operating shaft of the VersaRupter.
3. Check that the VersaRupter opens and closes when the
handle is operated.