THE AIRIUS SYSTEM HANGING/MOUNTING GUIDELINES
6. PLACEMENT OF THE AIRIUS SYSTEM
The AIRIUS SYSTEM performs best when installed such that the air stream/exhaust
from the nozzle is unimpeded to the floor. This will insure maximum circulation and
Thermal Equalization. Each System is designed to cover approximately 1200 Sq Feet
(100 Sq M) from its designed ceiling height, which is about a 40-Foot (12 M) diameter
circle. The density of the placement is a direct relationship to effectiveness,
performance and savings.
Floors plans, mezzanines, office location, machinery, people placement, plumbing,
lighting systems, duct work, electrical systems, natural light/air systems, indoor cranes,
doors, windows, ventilation and fire suppression systems are all factors in properly
locating the AIRIUS SYSTEM in the ceiling.
Floor Plans
- Sketch out the floor plan of the facility, divide it graphically into 1200 sq
ft (100 Sq M) squares and as closely as possible place an AIRIUS SYSTEM in the center
of each square of the grid. Adjust placement to accommodate.
Mezzanines
- The AIRIUS SYSTEM can be hung at an angle to throw accumulated heat
out to a larger space, or hang the AIRIUS SYSTEM near the mezzanine out in the larger
space to remove heat and balance room temperature.
Office
- Use smaller models to control individual office spaces, or larger units to
control common areas, eliminate hot and cold spots, create circulation, eliminate
electrical space heaters and reduce employee temperature related issues.
Cord Secured
RSJ or Ceiling Beam
Intake
Exhaust
Swivel
Receptical Rated
120 or 230 VAC
(277 VAC)
Twist Lock Plug
300 VAC Cord
Furnished
AIRIUS SYSTEM
W/Eyebolt
CAUTION:
Unprotected
moving blades
60lb (27 k)
Minimum rated
steel hook W/Latch
bridal ring or chain
Locking nuts, washers or beam clamp
FOR BEST EFFICIENCY
The AIRIUS SYSTEM should be securely installed as
close as possible to the ceiling. The AIRIUS
SYSTEM air column should have an unobstructed
passage to the floor.
The AIRIUS SYSTEM should not be mounted
directly in front of heat ducts, vents or near any
high heat source.
MAXIMUM SPACING 1 UNIT PER 1000 sq ft
(100 sq m) 40 ft diameter circle (12 m)
The AIRIUS SYSTEM
weighs 12 lb (5.5 k)
Height 22” (56 cm)
Diameter 12” (31 cm)