Badger Meter 340BN Installation & Operation Manual

Other manuals for 340BN: Installation & Operation Manual
Manual is about: Hydronic Energy Transmitter with RS-485 BACnet & Modbus and Scaled Pulse Output

Summary of 340BN

  • Page 1

    Badgermeter, inc. ® installation & operation manual model 340bn bacnet ® energy transmitter pn# 941700-0012 3-07.

  • Page 2

    2 table of contents introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 programming the transmitter . . . . . . . . . . . . . . . . . . . . . . . . 6 diagnostic utility...

  • Page 3

    3 1.60” (40.6mm) 3.65” (92.7mm) 2.95” (74.9mm) .88” (22mm) .60” (15mm) model: 340bn s/n 340bn-xxxxxx comm led data industrial ms/tp sensor input shield signal signal + power out - ref + _ ® bacnet fa ct or y p or t nt pd pu d.I.C. Comm port + - po w er in ac c /dc ac l /dc 1 2 3 te m p 1 1 3 te m p ...

  • Page 4

    4 figure 4: side view - typical 300 series removable connector wiring 3/32” flathead screwdriver series 300 connector wire figure 5: sample power supply wiring diagram electrical installation all connections to the model 340bn are made to screw terminals on removable headers. Power supply wiring the...

  • Page 5

    5 figure 9: sample wiring diagram to bacnet network note 1: biasing, circuitry, and resistors for pu, pd, and nt terminals are integral part of 340bn transmitter. Note 2: for the final 340bn transmitter in a given bacnet network, nt, pu, and pd jumpers should be in “open” position. Otherwise, nt, pu...

  • Page 6

    6 programming the model 340bn transmitter prior to introducing the model 340 bn onto a bacnet ® network, it must be configured for the type of input signal, pipe size, desired units of measure, filter coefficient, and temperature sensor. The default network address should be assigned to an unused ad...

  • Page 7

    7 9. Program the model 340bn transmitter using the diagram below as a reference. Note #1: badger meter sensors are pulse type sensors. The k and offset information is printed in the owners manual shipped with the prod- uct. This information is also available on our website. Calibration constants for...

  • Page 8

    8 12. To set the ms/tp address for the 340bn transmitter, open the new address pull-down menu and select the correct poll- ing address which matches the polling address entered into the master controller for this node of the bacnet network. Press the assign new address button to transmit polling in-...

  • Page 9

    9 press the retrieve parameters button which should display 340bn transmitter object data as shown below. The led located next to the 340bn network port, labeled “comm led”, will flash once to visually confirm communication between the 340bn transmitter and bacnet ® master controller. Use the scroll...

  • Page 10

    10 products product model number protocol revision software version firmware version 340bn 8340bn 135-2001 rev. 1.00 vendor information badger meter inc. 6116 e 15 th st. Tulsa, ok 74112 www.Badgermeter.Com product description the series 340 btu transmitter is a low cost, flow and temperature sensor...

  • Page 11

    11 communication port rs-485 with termination, pull up and pull down jumpers operating temperature 0° c to +70° c 32° f to +158° f storage temperature -40° c to +85° c -40° f to +185° f weight 4.8 oz. With connector headers installed sensor calibration badger meter use k and offset provided in senso...

  • Page 12: Badgermeter, Inc.

    ® due to continuous research, product improvements and enhancements, badger meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. Badgermeter, inc. 6116 e. 15th street, tulsa, oklahoma 74112 (918) 836-84...