Badger Meter 340BN Installation & Operation Manual - page 9
9
Press the Retrieve Parameters button which should display
340BN transmitter object data as shown below.
The LED located next to the 340BN network port, labeled “Comm
LED”, will flash once to visually confirm communication between
the 340BN transmitter and BACnet
®
master controller.
Use the scroll bar to view all object data.
If the 340BN transmitter fails to communicate with the BACnet
master controller, check that the correct polling address was
entered in step 12 found on page 8, the integrity of the network
port connection and, if necessary, settings in the BACnet mas-
ter controller.
Press the Close button to return to the Main Screen.
NETWORK SET-UP
The following Property Map is provided to assist in the program-
ming of the BACnet network.
MODEL 340BN OBJECT MAP
Description
ID
Name
Out of Service
Units
Analog
Input
AN1
TempIn
FALSE
°C, °F
"
AN2
TempOut
FALSE
°C, °F
"
AN3
FreqIn
FALSE
Hz
"
AN4
VolFlow
FALSE
gpm, gph, lps, lpm, lph, ft
3
/s,
ft
3
/m, ft
3
/h, m
3
/s, m
3
/min, m
3
/h
"
AN5
EnrgyFlow
FALSE
kBTU/min, kBTU/h,
kW, MW, HP, Tons
Analog
Value
AV1
TotalVol
FALSE
gallons, liters,ft
3
, m
3
"
AV2
TotEnergy
FALSE
BTU, kBTU, MBTU,
kWh, MWh, kJ, MJ
"
AV3
Kfactor
FALSE
dimensionless
"
AV4
Offset
FALSE
dimensionless
"
AV5
TempMode
FALSE
dimensionless
"
AV6
FFilterCoef
FALSE
dimensionless
"
AV7
TFiltCoef
FALSE
dimensionless
"
AV8
SpHtCapac
FALSE
BTU/lb-F
"
AV9
Density
FALSE
lb/gallon
"
AV10
InTACoef
FALSE
dimensionless
"
AV11
InTBCoef
FALSE
dimensionless
"
AV12
InTCCoef
FALSE
dimensionless
"
AV13
InTOffset
FALSE
°C, °F
"
AV14
OutTACoef
FALSE
dimensionless
"
AV15
OutTBCoef
FALSE
dimensionless
"
AV16
OutTCCoef
FALSE
dimensionless
"
AV17
OutTOffset
FALSE
°C, °F
MODEL 340BN FACTORY DEFAULT SETTINGS
The table below is a list of factory default setting for all 340BN
variables. These settings can be changed by accessing the pa-
rameters sensor (page 7) or Configure MS/TP screen (page 8) to
best fit your application. As new valves are assigned, they can be
written in the blank provided next to each variable for future refer-
ence.
Description
Default Value
Customer Value
Flow Sensor Type
Pulse
"K" Value
1
"Offset" Value
0
Flow Rate
gpm
Flow Total
gallons
Temperature °F
Energy Calculation
absolute
Temperature Sensor Type
10 k
ȍ thermistor
Energy Rate
kBTU/hr
Energy Total
BTU
Flow Filter Coefficient
5
Energy Filter Coefficient
1
MS/TP Address
1
MS/TP Baud Rate
9600
Model 340BN Factory Default Settings