Badger Meter Blancett B2800 Standard User Manual

Other manuals for Blancett B2800 Standard: User Manual
Manual is about: Flow Monitor

Summary of Blancett B2800 Standard

  • Page 1

    Flow monitor b2800 standard dsy-pm-00276-en-04 (march 2017) user manual.

  • Page 2: Contents

    Contents scope of this manual 3 unpacking and inspection 3 safety ...

  • Page 3: Scope Of This Manual

    Scope of this manual scope of this manual this manual is intended to help you get the b2800 flow monitor up and running quickly mpootant i read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference. Unpacking and inspection upon openi...

  • Page 4: Intooduction

    Introduction intooduction the b2800 flow monitor is a state-of-the-art digital signal processing flow monitor, designed to provide exceptional flexibility at a very affordable price though designed for use with blancett flow meters, this display can be used with almost any flow meter producing a lo...

  • Page 5: Opeoating The Monitoo

    Operating the monitor opeoating the monitoo programming keys mode indicator units display and programming choices rate / total display and programming choices run program relay1 relay2 figure 1: b2800 flow monitor buttons menu switches to program mode up scrolls forward through the parameter options...

  • Page 6: Poogoamming

    Programming poogoamming each turbine flow meter is shipped with either a k-factor value or frequency data if frequency data is provided, the data must be converted to a k-factor before programming the monitor k-factor information, when supplied, can usually be found on the neck of the flow meter o...

  • Page 7

    Programming example if the meter was calibrated in us gallons, use pul/gal press enteo to save the k-factor unit and advance to the k factor parameter otee: n unless otherwise specified, blancett turbine flow meters are supplied with k-factors measured in pulses per gallon (pul/gal) which will aut...

  • Page 8

    Programming totalizer pulse output the pulse output parameter can be enabled or disabled when enabled this output generates 20 ms duration pulse for every time the least significant digit of the totalizer increments the amplitude of the pulse is dependent on the voltage level of the supply connect...

  • Page 9

    Additional scaling parameters additional scaling paoameteos otee: n the programming instructions below are only available for loop powered units battery powered units do not include these programming parameters flow 4 ma setting zero is the default flow rate at the 4 ma setting if the current sel...

  • Page 10

    Additional scaling parameters 4…20 ma test the monitor contains a diagnostic routine that allows the simulation of ma values between 4…20 to check output tracking at the 4-20test prompt press up to increment the simulated ma output or oight to decrement the value in increments of 1 ma the ammeter ...

  • Page 11: Additional Input Options

    Additional input options additional input options the b2800 flow monitor is capable of receiving magnetic pickup input (small signal sine wave) or a contact closure input (pulse) since most blancett turbine flow meters use a magnetic pickup, the b2800 flow monitor is shipped configured for magnetic...

  • Page 12: Default K-Factoo Values

    Default k-factor values default k-factoo values meter size default k-factor lower limit upper limit 3⁄8 in (9 53 mm) 20,000 16,000 24,000 1/2 in (12 7 mm) 13,000 10,400 15,600 3/4 in (19 05 mm) 2750 2200 3300 7/8 in (22 23 mm) 2686 2148 3223 1 in (25 4 mm) 870 0 696 0 1044 1-1/2 in (38 1 mm) 3...

  • Page 13: Installation Doawing

    Installation drawing installation doawing battery powered page 13 march 2017 dsy-pm-00276-en-04.

  • Page 14

    Installation drawing loop powered page 14 march 2017 dsy-pm-00276-en-04.

  • Page 15: Tooubleshooting Guide

    Troubleshooting guide tooubleshooting guide issue oemedy no lcd display • check battery voltage should be 1 5v dc replace if low or bad no rate or total displayed • check connection from meter pickup to display input terminals • check turbine meter rotor for debris rotor should spin freely • c...

  • Page 16: Specifications

    Specifications specifications power supply options battery powered one d size, 1 5v alkaline battery loop powered optional 4…20 ma loop power alphanumeric oate and total display eight digit, 0 75 inch high numeric display eight character, 0 38 inch high alphanumeric display fixed or toggle modes of ...

  • Page 17: Oeplacement Paots

    Replacement parts oeplacement paots component part number keypad b260713 battery b280601 battery tie wrap b228036 pickup cable b222-121 desiccant bag b260630 pvc union b220016 pvc reducer bushing b220056 rubber washer b228207 steel lock washer b220018 pcb shield (battery units) b280603 desiccant shi...

  • Page 18

    Mounting options and dimensions mounting options and dimensions meter mount c b a d e f g dia a b c d e f g dia 9 25 in (235 0 mm) 7 00 in (177 8 mm) 5 75 in (146 0 mm) 4 00 in (101 6 mm) 3 45 in (87 6 mm) 1 50 in (38 1 mm) 0 875 in (22 2 mm) oemote mount e d a b c .25 in. Dia (6.4 mm) (4 hol...

  • Page 19

    Mounting options and dimensions swivel mount d c b a e f g dia a b c d e f g dia 12 25 in (311 2 mm) 7 00 in (177 8 mm) 5 75 in (146 0 mm) 4 00 in (101 6 mm) 3 45 in (87 6 mm) 1 50 in (38 1 mm) 0 875 in (22 2 mm) page 19 march 2017 dsy-pm-00276-en-04.

  • Page 20

    Flow monitor, b2800 standard www.Badgermeter.Com blancett is a registered trademark of badger meter all other trademarks appearing in this document are the property of their respective entities due to continuous research, product improvements and enhancements, badger meter reserves the right to ch...