Programming
Totalizer Pulse Output
The pulse output parameter can be enabled or disabled When enabled this output
generates 20 mS duration pulse for every time the least significant digit of the totalizer
increments The amplitude of the pulse is dependent on the voltage level of the supply
connected to the pulse output and is limited to a maximum 30V DC Press UP or OIGHT to
scroll to ON or OFF Press ENTEO to save and advance to the PASSWORD parameter
Password
The PASSWORD setting restricts access to PROGRAM mode Initially, the password is set to
all zeros and any user can modify the parameter settings in PROGRAM mode To change the
password, enter any four digit code Press UP to increment the digit, and OIGHT to advance
to the next digit Press ENTEO to store the password and advance to RST PSWD The new
password is now required to enter PROGRAM mode With this password set, any user is able
to reset the stored totals on the monitor
Oeset Password
The RST PSWD restricts resetting the totals on the monitor The PASSWORD must also be set
to restrict the total reset Initially, the password is set to all zeros and any user can reset the
stored totals on the monitor To change the password, enter any four digit code Press UP to
increment the digit, and OIGHT to advance to the next digit After entering all digits, press
ENTEO to store the password and return to RUN mode The reset password is now required
to reset the totals on the monitor
Oun Mode
Oeset Total
To reset the monitor total display, in RUN mode press MENU and ENTEO simultaneously If
the RST PSWD has been set to something other than the default, you must enter the new
password before the monitor will reset The monitor flashes
TOTAL RST and returns to RUN mode at the conclusion of the reset procedure
Store Total
The current total can be manually stored in the monitor’s flash memory Use this feature
prior to replacing the battery Press and hold ENTEO for 2 seconds The display responds
with a flashing TOTALSVD and then returns to RUN mode
Automatic Store Total
The monitor is equipped with a store total feature that works automatically, saving the
current total to flash memory The frequency of saves depends on the power supply option
chosen
Battery Powered: Once per hour and just before a low battery condition turns the unit off
Loop Powered:
Once every ten minutes