Basler BE1-51B Manual - Specifications
BE1-50/51B Retrofit Kits
5
CURRENT SENSING INPUT:
5 Amp Unit
14.0 Amps
400 Amps
1 Amp Unit
2.8 Amps
80 Amps
Continuous
One Second
Current
Current
TIME PICKUP RANGE:
5 Amp Unit: 0.5 to 15.9 Amps in 0.1 Amp steps
1 Amp Unit: 0.1 to 3.18 Amps in 0.02 Amp steps
TIME DROPOUT:
Not less than 95% of pickup value.
TIME PICKUP ACCURACY:
± 2% of setting
TIME DIAL RANGE:
0.0 to 9.9 in 0.1 steps
TIME CHARACTERISTICS:
Nine inverse time and 1 fixed time function can be
selected by a front panel switch. Characteristic
curves are defined by the time characteristic
equation. The fixed time characteristic provides
delays of 0.0 to 9.9 seconds corresponding to the
dial setting.
INVERSE TIMING ACCURACY:
± 2%, ±1 cycle for multiples of pickup from 2 to 40.
Below multiples of 2, errors may increase directly
proportional to the value of ______.
(M
N
-1)
FIXED TIME ACCURACY:
±2% or 30 milliseconds, whichever is greater.
TIME RESET:
Instantaneous or decay, internally selectable.
INST PICKUP RANGE:
5 Amp Unit: 2.0 to 99 Amps in 1 Amp steps
1 Amp Unit: 0.2 to 19.8 Amps in 0.2 Amp steps
INST B PICKUP RANGE
BE1-50/51B-230, -235, -237, -239 (5 Amp Unit):
1.0 to 15.9 Amps in 0.1 Amp steps
BE1-50/51B-234, -236, -238 (1 Amp Unit):
1 Amp Unit: 0.2 to 3.18 Amps in 0.02 Amp steps
INST DROPOUT:
95% of pickup
INST PICKUP ACCURACY:
± 2% of setting
INST CHARACTERISTIC:
See Figure 2. Additional user selectable
(by DIP switches) definite delay of 0.1 seconds.
INST TRANSIENT RESPONSE:
Less than 10% overreach with system time constants
up to 40 milliseconds.
BURDEN: Burden is non-linear and resistive.
5 Amp Unit: 4.8 Ohms @ 0.5A & 0.2 Ohms @ 5A
1 Amp Unit: 120 Ohms @ 0.1A & 5 Ohms @ 1A
TARGETS:
Magnetically latched, manually reset for TIME and
INST output functions.
Operate Current: 0.2 Amp minimum
Coil Resistance:
0.1 Ohm
Operate Time:
TARGET OPERATE CURRENT:
Units with second instantaneous include jumper-select-
able target operate currents.
Units without jumpers:
80-200 mA
Units with Jumper 1-2:
0.9-2.25 A
Units with Jumper 2-3:
80-200 mA
OUTPUTS: (50/51)
Resistive:
120/240 Vac: Make and carry 30 Amp for 0.2 sec.,
carry 7 Amp for 2 min., 3 Amp continuously, and
break 5 Amp.
125/250 Vdc: Make and carry 30 Amp for 0.2 sec.,
carry 7 Amp for 2 min., 3 Amp continuously, and
break 0.3 Amp.
Inductive:
120/240Vac, 125/250Vdc: Make and carry 30 Amp
for 0.2 sec., carry 7 Amp for 2 min., 3 Amp
continuously, and break 0.3 Amp. (L/R=0.04).
ISOLATION:
2000 Vac at 50/60 Hz for one minute (1500 Vac for
one minute across open contacts) in accordance
with IEC 255-5 and IEEE C37.90.1
(Dielectric Test).
SURGE WITHSTAND CAPABILITY:
Qualified to IEEE C37.90.1
FAST TRANSIENT:
Qualified to IEEE C37.90.1
IMPULSE TEST:
Qualified to IEC 255-5
RADIO FREQUENCY INTERFERENCE (RFI):
Qualified to IEEE C37.90.2. Field
tested using five watt transceiver operating at
random frquencies centered around 144 MHZ
and 440 MHZ.
TEMPERATURE:
Operating Range -40° C (-40° F) to 70° C (158° F).
Recommended Storage Range -50° C (-58° F) to
70° C (158° F).
SHOCK:
15g in each of three mutually perpendicular planes.