Basler BE1-51B Manual - Specifications, Continued
BE1-50/51B Retrofit Kits
6
SPECIFICATIONS, continued
RETROFIT FEATURES
The BE1-50/51B-214, -215, -225, -230, -231, -234, -237,
and -238 retrofit kits consist of a cradle, an adapter
plate, and a cover and provides for installing a Basler
BE1-50/51B single-phase time overcurrent relay in an
existing IAC case without making any wiring changes.
The BE1-50/51B-229 retrofit kit (not shown) provides
for installation of a Basler BE1-50/51B single-phase
time overcurrent relay in an existing SFC case without
wiring changes. The BE1-50/51B-229 offers the same
functionality, outputs, and curves as the 50/51B-214
but is designed to be an exact replacement for the
SFC.
The BE1-50/51B-218 and -228 (not shown) are com-
plete IAC replacement relays, including case.
The BE1-50/51B-219, -226, -235, and -236 retrofit kits
consist of a cradle and a cover and provides for install-
ing a Basler BE1-50/51B single-phase time overcurrent
relay in an existing CO case without making any wiring
changes. The BE1-50/51B-244 (not shown) is a com-
plete CO replacement relay and includes a case.
BE1-50/51B CO Retrofit Cradle and cover
BE1-50/51B IAC Retrofit
Cradle, adapter plate and cover
VIBRATION:
2g in each of three mutually perpendicular planes
swept over the range of 10 to 500 Hz for a total of
6 sweeps, 15 minutes per sweep.
AGENCY:
cURus recognition per UL Standard 508, File E97035
and CSA Standard C22.2 No. 14
CASE SIZE: S1 (-218 and -228 only)
NET WEIGHT:
6.1 pounds
8.6 pounds (-218 and -228 only)
4.3 pounds (-240 and -241 only)
BE1-50/51B CO FT-21 Retrofit Cradle
and replacement glass
The BE1-50/51B-240 and -241 retrofit kits consist of a
cradle and a piece of replacement Plexiglass and
provides for installing a Basler BE1-50/51B-240 or -241
relay in an existing CO FT-21 case.