Cadel aquos 24 h2O Installation, Use And Maintenance Manual - page 40
40
AQUOS 24 H
2
O
EN
The control panel gives information on the reason of the alarm in progress. A sound signal is not envisioned for
alarms A01-A02 only so to PANEL ALERTnot disturb the user in the event of pellets running out in the hopper during
the night.
PANEL ALERT
TYPE OF PROBLEM
SOLUTION
A01
The fire does not ignite.
Check whether the brazier is clean / level of pellets
in the hopper.
A02
The fire goes off abnormally.
Check the level of pellets in the hopper.
A03 Thermostat
alarms
The temperature of the pellets hopper or the
water temperature exceed the envisioned
safety threshold.
Wait for the cooling stage to end, cancel the alarm
and restart the boiler setting the fuel loading at
minimum (SETTINGS menu - Pellets recipe). If the
alarm persists, contact the service centre. Check if
the room fan works properly (if present).
A04
Smoke overheating.
The set smoke threshold has been exceeded. Reduce
pellets loading (SETTINGS menu - Pellets recipe).
A05 Pressure
switches alarm
Smoke pressure switch intervention or water
pressure insufficient.
Verify chimney obstruction / door opening or
hydraulic system pressure.
A08
Abnormal smoke fan operation.
If the alarm persists, contact the service centre.
A09
Smoke probe faulty.
If the alarm persists, contact the service centre.
A19
Water probe faulty.
Water probe disconnected / interrupted / defective
/ not recognised.
A20
Puffer probe alarm.
Puffer probe disconnected / interrupted / defective
/ not recognised.
SERVICE
Routine maintenance alert (it does not block
the system).
When this flashing message appears upon start-up, it
means that the preset operating hours have elapsed
before maintenance. Contact the service centre.
12.15
ALARM RESET
To reset the alarm one must press and hold key 1 (ESC) for a few seconds. The boiler performs a check to
determine if the cause of the alarm persists or not.
In the first case the alarm will still be displayed, in the second case it will go onto OFF.
If the alarm persists, contact the service centre.
12.16
NORMAL SHUTDOWN (ON THE PANEL: OFF WITH FLASHING FLAME)
If the shutdown key is pressed or if there is an alarm signal, the boiler goes into the thermal shutdown phase which
entails the automatic execution of the following stages:
• It stops pellets loading
• The room fan (if provided) maintains the set speed until the smoke T reaches 100°C, then it automatically sets
itself at the minimum speed until it reaches the shutdown temperature
• The smoke fan sets itself at maximum speed and maintains it for a fixed time of 10 minutes, at the end of which
if the smoke T has fallen below the shutdown threshold it switches off permanently, otherwise it sets itself at the
minimum speed until it reaches such threshold before switching off.
• If the boiler was shutdown regularly but, due to thermal inertia the smoke temperature exceeds the threshold
again, the shutdown stage restarts at the minimum speed until the temperature goes down.
12.17
BLACKOUT WITH THE BOILER ON
In the event of a power cut (BLACKOUT) the boiler behaves as follows:
• Blackout below 10”: it returns to its operation in progress;
• In the event of a power cut that lasts over 10” with the boiler on or in the start-up stage, when the boiler is
powered again it goes back to the previous operating condition with the following procedure:
1)
It cools down activating the smoke extractor at minimum power for 10’ and goes onto the next point;
1)
It takes the boiler back to the operating condition before the blackout.
During stage 1 the panel displays ON BLACK OUT.
During stage 2 the panel displays Start-up.
If during stage 1 the boiler receives commands from the panel and thus carried out manually by the user, then
the boiler stops executing the blackout recovery status and proceeds to restart or shutdown as requested by
the command.
12.18
BLACKOUT ABOVE 10” WITH BOILER IN SHUTDOWN STAGE
In the event there is a power cut that lasts MORE THAN 10” with the boiler in the shutdown stage, when the
boiler is powered again it restarts in shutdown mode even if the smoke temperature has fallen under 45°C in the