Eaton ® 93pm ups 60–100 kw (480v) installation and operation manual.
Eaton ® 93pm ups 60–100 kw (480v) installation and operation manual.
Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality i table of contents 1 introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Table of contents ii eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4.8 installing interface connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11 4.8.1 i...
Table of contents eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality iii 8 ups maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Table of contents iv eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality this page intentionally left blank..
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality v list of figures figure 1-1. Eaton 93pm ups (60–100 kw) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 figure 1-...
List of figures vi eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality this page intentionally left blank..
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality vii list of tables table 3-1. Ups cabinet weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 ta...
List of tables viii eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality this page intentionally left blank..
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 1-1 chapter 1 introduction the eaton ® 93pm 60–100 kw uninterruptible power supply (ups) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase sys...
Introduction 1-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 1-2. Eaton 93pm ups (60–100 kw) with left or right mounted sidecar 1.1 ups standard features the ups has many standard features that provide cost-effective and cons...
Introduction eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 1-3 1.1.3 customer interface l building alarm monitoring – up to five inputs in the ups are available to connect the facility's alarm system contacts. Some system configuratio...
Introduction 1-4 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 1.2.3 sidecar integrated accessory cabinet-bypass an sidecar integrated accessory cabinet-bypass (siac-b) provides maintenance bypass functions. The siac-b is available in...
Introduction eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 1-5 1.6 conventions used in this manual this manual uses these type conventions: l bold type highlights important concepts in discussions, key terms in procedures, and menu op...
Introduction 1-6 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 1.8 for more information refer to the eaton 93pm integrated battery cabinet installation manual for the following additional information: l installation instructions, incl...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 2-1 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that should be followed during installation and maintenance ...
Safety warnings 2-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality l determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contacting any part of a grounded battery can cause a risk of electric ...
Section 1 installation.
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-1 chapter 3 ups installation plan and unpacking use the following basic sequence of steps to install the ups: 1. Create an installation plan for the ups system (chapter 3). 2. Prepare yo...
Ups installation plan and unpacking 3-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality the ups cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front of the cabinet and outlets are on to...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-3 the ups ventilation requirements are shown in table 3-3. Figure 3-1. Ups cabinet dimensions (front and right side views) table 3-3. Air conditioning...
Ups installation plan and unpacking 3-4 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 3-2. Ups cabinet dimensions (top and bottom views) bottom dimensions are in millimeters [inches] front top front note top exhaust configurati...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-5 figure 3-3. Ups cabinet with left-mounted or right-mounted sidecar dimensions (front and right side views) dimensions are in millimeters [inches] fr...
Ups installation plan and unpacking 3-6 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 3-4. Ups cabinet with left-mounted or right-mounted sidecar dimensions (top and bottom views) dimensions are in millimeters [inches] front fr...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-7 figure 3-5. Ups cabinet center of gravity dimensions are in millimeters [inches] weight and center of gravity a b c weight kg (lb) eaton 93pm-100 up...
Ups installation plan and unpacking 3-8 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 3-6. Ups cabinet with left-mounted or right-mounted sidecar center of gravity dimensions are in millimeters [inches] weight and center of gra...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-9 figure 3-7. Remote epo switch dimensions 115.8 [4.56] 114.3 [4.50] 0.87 [0.22] 88.9 [3.50] 1.57 [0.40] 95.3 [3.57] front view 1/2" knockout pattern ...
Ups installation plan and unpacking 3-10 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3.2.2 ups system power wiring preparation read and understand the following notes while planning and performing the installation: warning as a resu...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-11 for external wiring requirements, including the minimum awg size of external wiring, see table 3-4. Wire sizes listed are for copper wiring only. T...
Ups installation plan and unpacking 3-12 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality the power wiring terminals are pressure terminations, ul and csa rated at 90°c. See table 3-5 for external power cable terminations. Figure 4-6 and...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-13 conduit sizes were chosen from nec table 4, electrical metallic tubing (emt). See table 3-6 for conduit requirements. Per nec article 300, 3(b)(1),...
Ups installation plan and unpacking 3-14 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality external overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to table 3-4 for wiring requireme...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-15 there is no manual dc disconnect device within the ups. Battery voltage is computed at 2 volts per cell as defined by article 480 of the nec. Rated...
Ups installation plan and unpacking 3-16 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality l a supplemental 48 vdc shunt trip signal for the battery disconnect device is provided, but is not required for normal operation. L battery detect...
Ups installation plan and unpacking eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 3-17 4. Remove the protective packaging material from the cabinet and recycle in a responsible manner. Retain any parts kits packaged with the cabinet. ...
Ups installation plan and unpacking 3-18 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 3-9. Ups cabinet with left-mounted or right-mounted sidecar as shipped on pallet ups with left-mounted sidecar ups with right-mounted sideca...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-1 chapter 4 ups system installation 4.1 preliminary installation information warning installation should be performed only by qualified personnel. Refer to the following while installing...
Ups system installation 4-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-1. Removing the pallet skids and supports – eaton 93pm ups warning do not remove or loosen the cabinet mounting or cabinet support bolts until instruct...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-3 6. Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately 3 mm (1/8"). 7. Remove the hardware loosened in...
Ups system installation 4-4 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-2. Removing the sidecar pallet skids and supports – eaton 93pm ups 4.3 integrated battery cabinet installation if installing integrated battery cabinet...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-5 4.6 external ac power wiring installation to install wiring: 1. Open the front door by lifting the latch from the bottom and turning to the right (counterclockw...
Ups system installation 4-6 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality warning as a result of the connected loads high leakage current is possible. Connection to earth ground is required for safety and proper product operation. Do ...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-7 figure 4-4. Sidecar conduit and wire entry locations top entry conduit landing for ac input and output, and dc input (remove panel to drill or punch conduit hol...
Ups system installation 4-8 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-5. Ups inter-cabinet wiring access location inter-cabinet wiring access to route interface wiring between cabinets. Inter-cabinet wiring access knockou...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-9 figure 4-6. Power terminal locations dc input from battery (see figure 4-7 for detail) ac input to ups rectifier (a, b, c) (see figure 4-7 for detail) front ac ...
Ups system installation 4-10 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-7. Power terminal detail 4.7 battery power wiring caution when sizing the battery system, do not exceed the internal battery charger capabilities. See...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-11 4.8 installing interface connections use the procedures in the following paragraphs to connect the battery and customer interface connections. 4.8.1 installing...
Ups system installation 4-12 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 12. If wiring building alarm or alarm contact connections, proceed to paragraph 4.8.2; if wiring minislot connections, proceed to paragraph 4.8.3; if wiring re...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-13 figure 4-9. Battery shunt trip and battery detect terminal detail figure 4-10. Battery shunt trip and battery detect terminal assignments shunt trip and batter...
Ups system installation 4-14 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4.8.2 installing building alarm and relay contact connections to install wiring: 1. Verify the ups system is turned off and all power sources are removed. See ...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-15 figure 4-11. Interface terminal locations front interface terminals (see figure 4-12 for detail) minislot communication bays (see figure 4-12 for detail).
Ups system installation 4-16 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-12. Interface terminal detail figure 4-13. Bottom access interface wiring access pull chain terminals minislot communication bay 2 minislot communicat...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-17 figure 4-14. Wire tie anchors figure 4-15. Building alarm terminal block connector assignments wire tie anchors table 4-2. Building alarm connections and wire ...
Ups system installation 4-18 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-16. Relay contact terminal block connector assignments 4.8.3 installing minislot interface connections for installation and setup of a minislot card, ...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-19 13. Install the lan and other cables to the appropriate minislot cards. Refer to the manual supplied with the minislot card for terminal assignments. 14. Refer...
Ups system installation 4-20 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 4-17. Repo switch 11. Route the repo wiring through the bottom interface entry conduit landing plates to the bottom access interface wiring channel alon...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-21 figure 4-19. Normally-open repo switch wiring figure 4-20. Normally-closed repo switch wiring table 4-4. Normally-open repo connections and wire terminations f...
Ups system installation 4-22 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4.10 initial startup startup may be performed by the customer’s battery qualified electrical contractor for single (not parallel) ups installations without any...
Ups system installation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 4-23 installation checklist o all packing materials and restraints have been removed from each cabinet. O the ups cabinet is placed in its installed location o all ...
Ups system installation 4-24 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality notes ________________________________________________________________________ ________________________________________________________________________ _______...
Section 2 operation.
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 5-1 chapter 5 understanding ups operation 5.1 ups system overview the eaton 93pm ups is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides condi...
Understanding ups operation 5-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 5.2.1 modes the eaton 93pmups supports a critical load in four different modes of operation: l in energy saver system (ess) mode, commercial ac power is sup...
Understanding ups operation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 5-3 figure 5-2. Path of current through the ups in energy saver system mode 5.2.3 normal mode during normal mode, power for the system is derived from a utility...
Understanding ups operation 5-4 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 5-3. Path of current through the ups in normal mode 5.2.4 bypass mode caution the critical load is not protected from voltage or frequency fluctuatio...
Understanding ups operation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 5-5 figure 5-4. Path of current through the ups in bypass mode 5.2.5 battery mode the ups automatically transfers to battery mode if a utility power outage occu...
Understanding ups operation 5-6 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 5-5. Path of current through the ups in battery mode 5.3 single ups unit system oneline configurations the system oneline drawings in this section sh...
Understanding ups operation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 5-7 figure 5-6. Ups system oneline ac input to bypass 3 wire a-b-c rotation ac input to ups rectifier 3 wire a-b-c rotation a b parallel can mini-slot interface...
Understanding ups operation 5-8 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 5-7. Ups system oneline with two-breaker bypass note callout letters a, b, c, and d map to table 3-4. Parallel can mini-slot interface interface boar...
Understanding ups operation eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 5-9 figure 5-8. Ups system oneline with three-breaker bypass parallel can mini-slot interface interface board pull chain remote epo c e4, e5 battery breaker ext...
Understanding ups operation 5-10 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality figure 5-9. Ups system oneline with four-breaker bypass parallel can mini-slot interface interface board pull chain remote epo c e4, e5 battery breaker ext...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-1 chapter 6 ups operating instructions this section describes how to operate the ups. 6.1 ups controls and indicators the controls and indicators identified and described in this section...
Ups operating instructions 6-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.2 using the control panel the following paragraphs describe the ups control panel, including controls and indicators, and how to monitor ups operation. The...
Ups operating instructions eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-3 6.2.1 status indicators the four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (led) lamps work with t...
Ups operating instructions 6-4 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.2.3 using the lcd touch screen the lcd touch screen on the control panel provides an operator interface with the ups system. Figure 6-3 identifies the disp...
Ups operating instructions eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-5 6.2.4 using the menu the ups navigation tab menu bar allows you to display data in the information area to help you monitor and control ups operation. Table ...
Ups operating instructions 6-6 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.2.6 display menu operation table 6-3 describes the menu functions and how to use them. Table 6-3. Display menu operation function subfunction operation hom...
Ups operating instructions eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-7 figure 6-5. Typical settings user screen figure 6-6. Typical settings configuration screen.
Ups operating instructions 6-8 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.2.7 sign in the controls and setting screens are restricted. The user must sign in using a password to gain access. To sign in: 1. Tap the lock button in t...
Ups operating instructions eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-9 6.2.8 system controls tap the controls tab on the main menu navigation bar to display the controls screen. Double conversion operation, transfer to bypass, s...
Ups operating instructions 6-10 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.3 single ups operation 6.3.1 starting the ups in double conversion mode to start the ups system: 1. Close the ups input feeder circuit breaker. 2. If dual...
Ups operating instructions eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-11 7. Tap the controls tab on the main menu navigation bar. The system control screen is displayed. 8. Tap the go to bypass button. The critical load is immedi...
Ups operating instructions 6-12 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.3.6 transfer from double conversion mode to ess mode to transfer the load to he normal mode: 1. Tap the controls tab on the main menu navigation bar. The ...
Ups operating instructions eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6-13 6.3.9 battery test to start the battery test: 1. Tap the controls tab on the main menu navigation bar. The system control screen is displayed. 2. Tap the ru...
Ups operating instructions 6-14 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 6.3.11 using the remote emergency power-off switch a ups emergency power-off is initiated by the repo pushbutton switch. In an emergency, you can use this s...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 7-1 chapter 7 communication this chapter describes the communication features of the eaton 93pm ups. For terminal wiring information, see paragraph 3.2.3 and paragraph 4.8. For location of...
Communication 7-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 7.3 general purpose relay contact one general purpose relay contact is provided as a standard feature on the ups. The relay contact customer interface terminals are locat...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 8-1 chapter 8 ups maintenance the components inside the ups cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little ...
Ups maintenance 8-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 8.2 performing preventive maintenance the ups system requires very little preventive maintenance. However, the system should be inspected periodically to verify that th...
Ups maintenance eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 8-3 figure 8-1. Air filter location periodic maintenance periodic inspections of the ups should be made to determine if components, wiring, and connections exhibit evidence...
Ups maintenance 8-4 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 8.3 installing batteries install batteries in accordance with the battery and battery system manufacturer's instructions. 8.4 recycling the used battery or ups contact ...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 9-1 chapter 9 product specifications 9.1 model numbers the ups is housed in a free-standing cabinet with safety shields behind the door. The ups is available in 50 or 60 hz with various ou...
Product specifications 9-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality 9.2.2 ups output 9.2.3 ups environmental ups output capacity 100% rated current output voltage regulation ± 1% (10% to 100% load) output voltage 480 vac wye, 3w ...
Eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality w-1 warranty limited factory warranty for three-phase eaton ® 93pm ups and 93pm ups accessory products warrantor: the warrantor for the limited warranties set forth herein is eaton corpora...
Warranty w-2 eaton 93pm ups (60–100 kw, 480v) installation and operation manual p-164000227—rev 2 www.Eaton.Com/powerquality this warranty is the enduser's sole remedy and is expressly in lieu of, and there are no other, expressed or implied guarantees or warranties (including any implied warranty ...
*p-164000227 2* p-164000227 2.