    English eaton 9130 ups 5000 - 6000 va user's guide copyright © 2010 eaton all rights reserved. Service and support: call your local service representative 9130 ups-en.

  • Page 2

    Page 2 9130 ups-en class a emc statements requesting a declaration of conformity units that are labeled with a ce mark comply with the following harmonized standards and eu directives: harmonized standards: iec 61000-3-12 l eu directives: 2006/95/ec, council directive on equipment designed for use w...

  • Page 3: Contents

    Page 3 9130 ups-en english 1. Introduction 2. Installation 2.1 inspecting the equipment ..............................................................................................5 2.2 unpacking the cabinet .............................................................................................

  • Page 4: 1. Introduction

    Page 4 9130 ups-en 1. Introduction the eaton® 9130 uninterruptible power system (ups) protects your sensitive electronic equipment from the most common power problems, including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switching tran...

  • Page 5: 2. Installation

    Page 5 9130 ups-en english 2. Installation this section explains: equipment inspection l unpacking the cabinet l checking the accessory kit l product installation l connecting the internal battery l connecting the ebm(s) l installation requirements l 2.1 inspecting the equipment if any equipment has...

  • Page 6: 2. Installation

    Page 6 9130 ups-en 2. Installation 2.3 checking the accessory kit verify that the following additional items are included with the ups: ups user’s guide l software suite cd l usb cable l rs232 cable l e n g l is h eaton 9130 ups 5000 - 6000 va user's guide copyright © 2009 eaton all rights reserved....

  • Page 7: 2. Installation

    Page 7 9130 ups-en english 2. Installation 2.5 connecting the internal battery do not make unauthorized changes to the ups; otherwise, damage may occur to your equipment and void your warranty. Do not connect the ups to utility until installation is completed. To install the ups: 1. Remove the ups f...

  • Page 8: 2. Installation

    Page 8 9130 ups-en 2. Installation 2.6 connecting the ebm(s) to install the optional ebm(s) for a ups: a small amount of arcing may occur when connecting an ebm to the ups. This is normal and will not harm personnel. Insert the ebm cable into the ups battery connector quickly and firmly. 1. Plug the...

  • Page 9: 2. Installation

    Page 9 9130 ups-en english 2. Installation 2. Required cable cross-sections table 2. Cable cross sections ups power rating 5000 va / 6000 va minimum of section required terminal-block capacity phase and neutral solid or stranded wire 6 mm² awg 10 10 mm² awg 8 earthing solid or stranded wire 6 mm² aw...

  • Page 10: 2. Installation

    Page 10 9130 ups-en 2. Installation ups with separate input and bypass inputs, supplied by separate sources (figure 13) change in sea between upstream and downstream or galvanic isolation required (figure 14) 8 10 11 frequency converter (without bypass input) (figure 15) configuration used when the ...

  • Page 11

    Page 11 9130 ups-en english 3. Power cables connection & startup this section explains: access to terminal block l common input sources connection l separate input sources connection l frequency converter connection l ups initial startup l 3.1 access to terminal block 1. Access to terminal block: re...

  • Page 12

    Page 12 9130 ups-en 3. Power cables connection & startup 3.3 separate input sources connection this type of connection must be carried out by qualified electrical personnel. Before carrying out any connection, check that the upstream protection device input source is open ("o") (off). Always connect...

  • Page 13

    Page 13 9130 ups-en english 3. Power cables connection & startup 3.5 ups initial startup to start up the ups: verify that the total equipment ratings do not exceed the ups capacity to prevent an overload alarm. 1. Verify that the internal batteries are connected. See "connecting the internal battery...

  • Page 14: 4. Operation

    Page 14 9130 ups-en 4. Operation this chapter contains information on how to use the eaton 9130, including front panel operation, operating modes, ups startup and shutdown, transferring the ups between modes, retrieving the event log, setting the power strategy, and configuring bypass settings, load...

  • Page 15: 4. Operation

    Page 15 9130 ups-en english 4. Operation the table 4 shows the basic menu structure. Table 4. Menu map for display functions main menu submenu display information or menu function ups status main status (mode and load) / notice or alarm status (if any) / battery status (state and charge level) event...

  • Page 16: 4. Operation

    Page 16 9130 ups-en 4. Operation power strategy [normal] [high efficiency] see "setting power strategy" on page 19. Normal automatic start delay [no delay] [disabled] [1,2,...,32767 s] to define if the load turns automatically on, with the delay set after the utility return, if it has been shutdown ...

  • Page 17: 4. Operation

    Page 17 9130 ups-en english 4. Operation 4.2 operating modes the eaton 9130 front panel indicates the ups status through the ups indicators (see figure 20 on page 14). Normal mode during normal mode, the indicator illuminates solid and the ups is powered from the utility. The ups monitors and charge...

  • Page 18: 4. Operation

    Page 18 9130 ups-en 4. Operation 4.3 ups startup and shutdown to start up or shut down the ups, see: "starting the ups" on page 18 l "starting the ups on battery" on page 18 l "ups shutdown" on page 18 l starting the ups "start on bypass" settings can be used to power on capacitive loads. To start t...

  • Page 19: 4. Operation

    Page 19 9130 ups-en english 4. Operation 4.5 retrieving the event log to retrieve the event log through the display: 1. Press any button to activate the menu options, then select event log. 2. Scroll through the listed events. To retrieve the event log through the serial port: 1. From the communicat...

  • Page 20: 4. Operation

    Page 20 9130 ups-en 4. Operation 4.8 configuring battery settings set the ups for the number of ebms installed whether to run automatic battery tests, and automatic restart configuration. Configuring the ups for ebms to ensure maximum battery runtime, configure the ups for the correct number of ebms...

  • Page 21: 5. Communication

    Page 21 9130 ups-en english 5. Communication this section describes the: communication ports (rs-232 and usb) l connectivity cards l remote power-off (rpo) l relay output contacts l programmable signal inputs l modem operation l eaton® power management software l figure 21. Communication options and...

  • Page 22: 5. Communication

    Page 22 9130 ups-en 5. Communication rs 232 and usb communication ports to establish communication between the ups and a computer, connect your computer to one of the ups communication ports using an appropriate communication cable. See figure 21 for the communication port locations. When the commun...

  • Page 23: 5. Communication

    Page 23 9130 ups-en english 5. Communication the rpo circuit is an iec 60950 safety extra low voltage (selv) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation. The rpo must not be connected to any utility connected circuits. Reinforced insulation to...

  • Page 24: 5. Communication

    Page 24 9130 ups-en 5. Communication the table 10 shows the options for the relay output contacts. Table 10. Relay output configuration options relay signal description ups ok activated when the ups is feeding the load on inverter or on bypass and no alarms are active on bypass activated when the up...

  • Page 25: 5. Communication

    Page 25 9130 ups-en english 5. Communication table 12. Polarity options input description high active state on high voltage (+udc) level low active state on low voltage (gnd or -udc) level 5.3 eaton power management software suite each eaton 9130 ups ships with eaton power management software suite....

  • Page 26: 6. Ups Maintenance

    Page 26 9130 ups-en 6. Ups maintenance this section explains how to: care for the ups and batteries l replace the ups internal batteries and extended battery modules (ebms) l test new batteries l recycle used batteries or ups l 6.1 ups and battery care for the best preventive maintenance, keep the a...

  • Page 27: 6. Ups Maintenance

    Page 27 9130 ups-en english 6. Ups maintenance servicing should be performed by qualified service personnel knowledgeable of batteries and l required precautions. Keep unauthorized personnel away from batteries. Batteries can present a risk of electrical shock or burn from high short circuit current...

  • Page 28: 6. Ups Maintenance

    Page 28 9130 ups-en 6. Ups maintenance figure 28. Disconnecting the ups internal batteries. 3. Disconnect one of the 4 battery trays. Remove the plastic protection above the connector and disconnect the battery tray (see figure 29). Figure 29. Disconnecting the internal battery tray. 4. Remove the m...

  • Page 29: 6. Ups Maintenance

    Page 29 9130 ups-en english 6. Ups maintenance 6. Slide the new battery package into the cabinet. Push the battery package in firmly. 7. Screw the metal part to fix the battery tray. Make sure main internal battery connector is disconnected. 8. Connect the battery tray and put back the plastic prote...

  • Page 30: 6. Ups Maintenance

    Page 30 9130 ups-en 6. Ups maintenance 6.6 recycling the used battery or ups contact your local recycling or hazardous waste center for information on proper disposal of the used battery or ups. Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of l batteri...

  • Page 31: 7. Specifications

    Page 31 9130 ups-en english 7. Specifications 7.1 model specifications this section provides the following specifications: communication options l model lists l weights and dimensions l electrical input and output l environmental and safety l battery l table 13. Communication options communication b...

  • Page 32: 7. Specifications

    Page 32 9130 ups-en 7. Specifications table 18. Electrical input model default input (voltage/current) selectable input voltage range voltages at 100 % load pw9130i5000t-xl 230 v / 21.7 a 200*, 208*, 220, 230, 240 180–276 vac pw9130i6000t-xl 230 v / 26.1 a 200*, 208*, 220, 230, 240 180–276 vac 208 v...

  • Page 33: 7. Specifications

    Page 33 9130 ups-en english 7. Specifications table 22. Environmental and safety surge suppression en 61000-2-2 en 61000-4-2, level 3 en 61000-4-3, level 3 en 61000-4-4, level 3 (also on signal ports) en 6100-4-5, level 3 criteria a (ieee c62.41 6 kv) en 61000-4-6, level 3 en 61000-4-8, level 4 en 6...

  • Page 34: 8. Troubleshooting

    Page 34 9130 ups-en 8. Troubleshooting the eaton 9130 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms int...

  • Page 35: 8. Troubleshooting

    Page 35 9130 ups-en english 8. Troubleshooting overload power requirements exceed the ups capacity (greater than 100 % of nominal; see page 31 for specific output overload ranges). Remove some of the equipment from the ups. The ups continues to operate, but may switch to bypass mode or shut down if ...

  • Page 36: 8. Troubleshooting

    Page 36 9130 ups-en 8.2 silencing the alarm press any button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. 8.3 service...