Eaton Powerware 9390 Installation And Operation Manual - page 10
List of Figures
viii
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
Figure 9-24. Maximum Current Log Setup Screen 1
9-21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-25. Maximum Current Log Setup Screen 2
9-22
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-26. Time Interval Monitored Setup Screen
9-23
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-27. Time Interval Monitored Setup Save Screen
9-24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-28. Maximum % of Full Load Setup Screen
9-25
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-29. Maximum % of Full Load Setup Save Screen
9-26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-30. Calculation Method Setup Screen
9-27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-31. System Meters Screen
9-28
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-32. Total System Output Meter Screen
9-29
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-33. Output Unit X Meter Screen
9-30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-34. Input Unit X Meter Screen
9-31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-35. Bypass Unit X Meter Screen
9-31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-36. Battery Unit X Meter Screen
9-32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-37. Output Current (Load) Unit X Meter Screen
9-32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-38. System Setup Level 0 Screen
9-33
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-39. Contrast Adjust Screen
9-34
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-40. Versions Screen
9-35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-41. Unit Type Screen
9-35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-42. Enter Password Screen
9-36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-43. System Setup Level 1 Screen
9-37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-44. Change Password Screen
9-38
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-45. Change Password Save Screen
9-39
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-46. Time Format Screen
9-40
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-47. Set Date and Time MM/DD/YYYY Screen
9-41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-48. Set Date and Time DD/MM/YYYY Screen
9-42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-49. COM Port Setup Screen
9-43
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-50. COM Setup Screen
9-44
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-51. System Controls Screen 1
9-45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-52. System Controls Screen 2
9-46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 9-53. Load Off Screen
9-47
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 11-1. Remote Monitor Panel II
11-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 11-2. Relay Interface Module II
11-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 11-3. Supervisory Contact Module II
11-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 13-1. Optional X-Slot Cards
13-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 13-2. Sample Event History Log
13-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Summary of Powerware 9390
Page 1
Powerware 9390 ups 100–160 kva installation and operation manual ®.
Page 2
Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
Page 3
I eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table of contents 1 introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 basic system configurations 1-...
Page 4
Table of contents ii eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 4 batteries 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 important safety instructi...
Page 5
Table of contents iii eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 8 features, options, and accessories 8-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.1 ups standard features 8-1 . . . . . . . . . . . ...
Page 6
Table of contents iv eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.3 system controls screen 9-45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4 load off screen 9-47 . . . . . ....
Page 7
Table of contents v eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 13 communication 13-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.1 x-slot cards 13-1 . . . . . . . ...
Page 8
Table of contents vi eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 9
Vii eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com list of figures figure 1-1. Powerware 9390 ups (100–160 kva) cabinet 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2-1. Powerware 9390 ups (100–160 kva) c...
Page 10
List of figures viii eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com figure 9-24. Maximum current log setup screen 1 9-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 9-25. Maximum current log setup sc...
Page 11: Chapter 1
1-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 1 introduction the powerware ® 9390 uninterruptible power supply (ups) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system, provid...
Page 12
Introduction 1-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 1.1 basic system configurations the following basic ups system configurations are possible: 쑺 single module ups and one to four battery cabinets 쑺 single module ups with ups si...
Page 13
Introduction 1-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 1.2 using this manual this manual describes how to install and operate the powerware 9390 ups (100–160 kva) cabinet. Read and understand the procedures described in this manual...
Page 14
Introduction 1-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 쑺 chapter 14, “maintaining the ups system” – contains maintenance instructions for the ups system. 쑺 chapter 15, “product specifications” – provides detailed specifications for...
Page 15
Introduction 1-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 1.4 safety warnings important safety instructions save these instructions this manual contains important instructions that should be followed during installation and maintenanc...
Page 16
Introduction 1-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 1.5 for more information refer to the powerware 9390 integrated battery cabinet (models ibc-s and ibc-l) installation manual (164201536) for the following additional informatio...
Page 17: Section I
1-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com section i installation.
Page 18
1-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 19: Chapter 2
2-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 2 ups installation plan and unpacking use the following basic sequence of steps to install the ups: 1. Create an installation plan for the ups system (chapter 2). 2. Prepare your si...
Page 20
Ups installation plan and unpacking 2-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 2.2.1 environmental considerations the life of the ups system is adversely affected if the installation does not meet the following guidelines: 쑺 the sys...
Page 21
Ups installation plan and unpacking 2-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com figure 2-1. Powerware 9390 ups (100–160 kva) cabinet as shipped on pallet c a u t i o n the ups cabinet is heavy (see table a on page a-3). If unpacking ...
Page 22
Ups installation plan and unpacking 2-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for removing the cabinet from the pallet. Note the up...
Page 23: Chapter 3
3-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 3 installing the ups system 3.1 preliminary installation information w a r n i n g installation should be performed only by qualified personnel. Refer to the following while install...
Page 24
Installing the ups system 3-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 3.2.1 unloading the powerware 9390 ups cabinet from the pallet the ups cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet, perform ...
Page 25
Installing the ups system 3-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com shipping bracket bolts front view pallet vented front doors front shipping bracket shipping bracket bolts removable skid skid bolts figure 3-1. Removing front ship...
Page 26
Installing the ups system 3-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com rear shipping bracket pallet rear view shipping bracket bolts shipping bracket bolts figure 3-2. Removing rear shipping bracket on the powerware 9390 ups.
Page 27
Installing the ups system 3-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com note in the following step the pallet tilts and acts as a ramp once the cabinet is rolled beyond the the center of the pallet. Be sure to restrain the cabinet as i...
Page 28
Installing the ups system 3-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 3.2.3 integrated distribution cabinet installation to install and wire an idc, refer to the powerware 9390 integrated distribution cabinet (160 kva) installation a...
Page 29
Installing the ups system 3-7 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com c a u t i o n delta sources (tn-s) - the 9390 ups system can be operated only from a delta supply source that is fully floating and if the neutral-forming transfor...
Page 30
Installing the ups system 3-8 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com c a u t i o n in the following step, do not move the sensing and emi wires from the rectifier contactor k1 input terminals. These wires must remain connected to th...
Page 31
Installing the ups system 3-9 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 3.2.6.2 480v input external wiring installation to install wiring to connections: 1. Slide the air filters up and remove them from the cabinet. 2. Remove the screw...
Page 32
Installing the ups system 3-10 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 14. Route and connect the output cable between the ups cabinet and the idc or iac. Refer to the applicable idc or iac installation and operation manual, reference...
Page 33
Installing the ups system 3-11 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 4. If wiring interface connections, proceed to paragraph 3.2.7; otherwise, proceed to step 5. 5. When all wiring is complete, reinstall the safety shield panels r...
Page 34
Installing the ups system 3-12 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11. Route and connect the wiring. 12. If wiring tb1 battery cabinet interface connections, proceed to paragraph 3.2.7.2; if wiring the x-slot connections only, pr...
Page 35
Installing the ups system 3-13 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 12. Remove the screws securing the bottom and right side internal safety shield panels and remove the panels to gain access to the bottom conduit landing plate. N...
Page 36
Installing the ups system 3-14 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 6. When all wiring is complete, reinstall the safety shield panels removed in previous steps. Secure with the retained hardware. 7. Close the control panel door a...
Page 37
Installing the ups system 3-15 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com installation checklist - all packing materials and restraints have been removed from each cabinet. - each cabinet in the ups system is placed in its installed loc...
Page 38
Installing the ups system 3-16 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com parallel system installation checklist - each cabinet in the parallel system is placed in its installed location. - all conduits and cables are properly routed to...
Page 39
Installing the ups system 3-17 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com notes _________________________________________________________________________ _________________________________________________________________________ ________...
Page 40
Installing the ups system 3-18 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 41: Chapter 4
4-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 4 batteries 4.1 important safety instructions this chapter describes installing the ups batteries. C a u t i o n only qualified service personnel (such as a licensed electrician) sh...
Page 42
Batteries 4-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com a v e r t i s s e m e n t ! 쑺 les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des courts-circuits de haute intensité. Prendre les précautions né...
Page 43: Chapter 5
5-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 5 installing a remote emergency power-off switch a latching-type repo switch can be used in an emergency to shut down the ups and remove power to the critical load from a location a...
Page 44
Installing a remote emergency power-off switch 5-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 6. Remove the screws securing the internal panel covering the tb1 and tb2 terminal blocks at the top of the ups cabinet (see drawing 164201554...
Page 45
Installing a remote emergency power-off switch 5-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 13. If you are installing multiple repo stations, wire additional stations in parallel with the first repo. 14. If required, install wiring fr...
Page 46
Installing a remote emergency power-off switch 5-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 47: Chapter 6
6-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 6 installing options and accessories 6.1 installing a powerware hot sync can bridge card as an option, a powerware hot sync computer area network bridge card shown in figure 6-1, ca...
Page 48
Installing options and accessories 6-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 4. Install wiring from the powerware hot sync can bridge card in accordance with the instructions listed below: 쑺 parallel system wiring (see paragraph 6....
Page 49
Installing options and accessories 6-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11. Install parallel system backup control (pull chain) wiring between upms. See drawing 164201554-8 starting on page a-33 for terminal locations and wiri...
Page 50
Installing options and accessories 6-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7. Install wiring between the ups and rmp ii. See drawing 164201554-8 starting on page a-33 for powerware hot sync can bridge card and rmp ii location, te...
Page 51
Installing options and accessories 6-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com note when installing signal wiring for can card j3 terminals, conduit must be installed between the device and the ups cabinet. Note remove the ups cabine...
Page 52
Installing options and accessories 6-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 6.5 installing a supervisory contact module ii to install scm ii wiring, perform the following procedure: 1. Verify the ups system is turned off and all p...
Page 53
Installing options and accessories 6-7 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9. Install wiring between the scm ii terminal block tb2 and the monitoring equipment. See figure 6-2 for terminal assignments and drawing 164201554-8 on p...
Page 54
Installing options and accessories 6-8 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 55: Section Ii
6-9 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com section ii operation.
Page 56
6-10 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 57: Chapter 7
7-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 7 understanding ups operation 7.1 looking inside the ups system the powerware 9390 ups is a continuous-duty, solid-state, transformerless (at 208 and 480 vac), three-phase, true onl...
Page 58
Understanding ups operation 7-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com if utility power is interrupted or falls outside the parameters specified in chapter 15, “product specifications,” the ups uses a backup battery supply to mainta...
Page 59
Understanding ups operation 7-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the ups continually monitors itself and the incoming utility power, and automatically switches between these modes as required, without operator intervention. Th...
Page 60
Understanding ups operation 7-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7.2.2 normal mode – rt figure 7-2 shows the path of electrical power through the ups system when the ups is operating in normal mode. Static switch k5 rectifier ...
Page 61
Understanding ups operation 7-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the neutral from the system input is connected to the neutral regulator in the dc capacitors. The output neutral of the system is connected with the required neu...
Page 62
Understanding ups operation 7-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7.2.3 bypass mode – rt the ups automatically switches to bypass mode if it detects an overload, load fault, or internal failure. The bypass source supplies the c...
Page 63
Understanding ups operation 7-7 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com during an outage, the ups prohibits transfers to bypass and provides upstream protection. The backfeed protection contactor is opened, preventing system output v...
Page 64
Understanding ups operation 7-8 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7.2.4 battery mode – rt the ups automatically transfers to battery mode if a utility power outage occurs, or if the utility power does not conform to specified p...
Page 65
Understanding ups operation 7-9 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com if the input power fails to return or is not within the acceptance windows required for normal operation, the battery continues discharging until a dc voltage le...
Page 66
Understanding ups operation 7-10 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com up to four units can be paralleled for redundancy or capacity without any additional cabinets. The system is paralleled for redundancy (1+1) in a system where t...
Page 67
Understanding ups operation 7-11 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7.3.2 normal mode – parallel in normal mode, utility ac power is supplied to the upms. Each upm then conditions the incoming ac power and provides clean, regula...
Page 68
Understanding ups operation 7-12 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7.3.3 bypass mode – parallel in bypass mode, the output of the system is provided with three-phase ac power directly from the bypass input. While in this mode, ...
Page 69
Understanding ups operation 7-13 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the parallel system can be transferred from normal mode to bypass mode manually. However, the parallel system automatically switches to bypass mode whenever the...
Page 70
Understanding ups operation 7-14 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7.3.4 battery mode – parallel the upms transfer to battery mode automatically if a utility power outage occurs, or if the utility power does not conform to spec...
Page 71
Understanding ups operation 7-15 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com if the input power fails to return or is not within the acceptance windows required for normal operation, the battery continues discharging until a dc voltage l...
Page 72
Understanding ups operation 7-16 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com an abm charging cycle starts with the charger driving the battery voltage, at maximum current limit, to a battery charge level of 2.34 volts/cell. The time it t...
Page 73: Chapter 8
8-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 8 features, options, and accessories 8.1 ups standard features the ups has many standard features that provide cost-effective and consistently reliable power protection. 8.1.1 contr...
Page 74
Features, options, and accessories 8-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 8.1.5 advanced battery management a three-stage charging system increases battery service life by optimizing recharge time, and protects batteries from da...
Page 75
Features, options, and accessories 8-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 8.2.3 integrated accessory cabinet (iac-b, iac-t, and iac-d) the following iacs are designed for use with the powerware 9390 three-phase uninterruptible p...
Page 76
Features, options, and accessories 8-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 8.2.8 remote monitor panel ii an optional rmp ii contains backlit status indicators and a local horn, allowing you to monitor the operational status and a...
Page 77: Chapter 9
9-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 9 using the control panel this chapter describes the ups control panel, including controls and indicators, and how to monitor ups operation. The control panel (see figure 9-1) is lo...
Page 78
Using the control panel 9-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.1 using the lcd and pushbuttons the lcd on the control panel provides an operator interface with the ups system. Figure 9-2 identifies the display areas discussed ...
Page 79
Using the control panel 9-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2 using the main menu the ups main menu bar allows you to display data in the information area to help you monitor and control ups operation. The following menus a...
Page 80
Using the control panel 9-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.2 event screens press the events pushbutton on the main menu bar or history menu bar to display a listing of all system events that are currently active. The mos...
Page 81
Using the control panel 9-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the history pushbutton on the active events menu bar to display the history log. The history log lists up to the 500 system events in chronological order, with...
Page 82
Using the control panel 9-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.3 unit meter screens the unit meter screens show the ups meter readings for the unit (or units, if a parallel system is installed). The default voltage displayed...
Page 83
Using the control panel 9-7 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the input screen shows input voltage (phase-to-neutral), input current (each phase), and frequency of the incoming utility source, as well as the kva, kw, and power ...
Page 84
Using the control panel 9-8 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the battery screen displays the battery voltage (vdc), the battery current (idc), the minutes of battery time remaining, and battery temperature. Battery temperature...
Page 85
Using the control panel 9-9 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.4 battery discharge log press the meters pushbutton on the main menu bar to display the unit meter screens. Scroll through the meter screens using the or pushbut...
Page 86
Using the control panel 9-10 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the log pushbutton on the battery discharge log summary menu bar to display the battery discharge log screen. The battery discharge log screen displays the in...
Page 87
Using the control panel 9-11 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.5 kw demand log press the meters pushbutton on the main menu bar to display the unit meter screens. Scroll through the meter screens using the or pushbuttons on...
Page 88
Using the control panel 9-12 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the log pushbutton on the kw demand log summary menu bar to display the kw demand log screen. The kw demand log screen displays the individual log entries, in...
Page 89
Using the control panel 9-13 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the setup pushbutton on the kw demand log summary menu bar to display the current kw demand log setup screen 1. The current kw demand log setup screen 1 displ...
Page 90
Using the control panel 9-14 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the change pushbutton on the current kw demand log setup menu bar to display the current kw demand log setup screen 2. The current kw demand log setup screen ...
Page 91
Using the control panel 9-15 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select time interval monitored from the current kw demand log setup screen 2 menu to display the time interval monitored setup screen. The time interval monitored s...
Page 92
Using the control panel 9-16 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the time interval monitored setup save screen lets you save the new time interval, retry another time interval, or abort the change. Figure 9-18 shows the time inte...
Page 93
Using the control panel 9-17 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select maximum level (kw) from the current kw demand log setup screen 2 menu to display the maximum level (kw) setup screen. The maximum level (kw) setup screen all...
Page 94
Using the control panel 9-18 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the maximum level (kw) setup save screen lets you save the new kw limit, retry another kw limit, or abort the change. Figure 9-20 shows the maximum level (kw) setup...
Page 95
Using the control panel 9-19 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.6 maximum current log press the meters pushbutton on the main menu bar to display the unit meter screens. Scroll through the meter screens using the or pushbutt...
Page 96
Using the control panel 9-20 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the log pushbutton on the maximum current log summary menu bar to display the maximum current log screen. The maximum current log screen displays the individu...
Page 97
Using the control panel 9-21 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com maximum current log summary interval : 07/30/2005 time over limit 15 : 26 : 10 – 15 : 30 : 10 *** . ** % 2 minutes 3 reset maximum current event num times over this...
Page 98
Using the control panel 9-22 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com press the change pushbutton on the maximum current log setup menu bar to display the maximum current log setup screen 2. The maximum current log setup screen can be...
Page 99
Using the control panel 9-23 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select time interval monitored from the maximum current log setup screen 2 menu to display the time interval monitored setup screen. The time interval monitored set...
Page 100
Using the control panel 9-24 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the time interval monitored setup save screen lets you save the new time interval, retry another time interval, or abort the change. Figure 9-18 shows the time inte...
Page 101
Using the control panel 9-25 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select maximum % of full load from the maximum current log setup screen (screen 2) menu to display the maximum % of full load setup screen. The maximum % of full lo...
Page 102
Using the control panel 9-26 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the maximum % of full load setup save screen lets you save the new load limit, retry another load limit, or abort the change. Figure 9-29 shows the maximum % of ful...
Page 103
Using the control panel 9-27 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select calculation method from the maximum current log setup screen 2 menu to display the calculation method setup screen. The calculation method setup screen allow...
Page 104
Using the control panel 9-28 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.7 system meters screens the system meters screens show the total system and individual ups unit meter readings from any unit, when a parallel system is installe...
Page 105
Using the control panel 9-29 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the output total system screen shows output voltage (phase-to-neutral), output current (each phase), and frequency being supplied by the ups, as well as the kva, kw...
Page 106
Using the control panel 9-30 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com figure 9-33 through figure 9-37 show the system meters screens. To scroll through the meter screens, press the or pushbuttons on the menu bar. The current ups readi...
Page 107
Using the control panel 9-31 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the input screen shows input voltage (phase-to-neutral), output current (each phase), and frequency of the incoming utility source, as well as the kva, kw, and powe...
Page 108
Using the control panel 9-32 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the battery screen displays the battery voltage (vdc), the battery current (idc), the minutes of battery time remaining, and battery temperature. Battery temperatur...
Page 109
Using the control panel 9-33 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.8 system setup level 0 screens press the setup pushbutton on the main menu bar to display the system setup level 0 screen. This screen can be used to: 쑺 enter a...
Page 110
Using the control panel 9-34 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select contrast from the system setup level 0 menu to display the contrast adjust screen. Figure 9-39 shows the contrast adjust screen. Use the or pushbuttons to ad...
Page 111
Using the control panel 9-35 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select versions from the system setup level 0 menu to display the versions screen. The versions screen provides the firmware version numbers installed on the ups. F...
Page 112
Using the control panel 9-36 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.2.9 system setup level 1 screens a password is required to access the level 1 functions. To enter the password, select enter password from the system setup level ...
Page 113
Using the control panel 9-37 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the system setup level 1 screen can be used to set the ups date and time, set the serial ports, change the level 1 password, and log out of level 1. In addition, th...
Page 114
Using the control panel 9-38 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select change password from the system setup level 1 menu to display the change password screen. The change password screen allows the system setup level 1 password...
Page 115
Using the control panel 9-39 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the change password save screen lets you save the new password, retry another password, or abort the password change. Figure 9-45 shows the change password save scr...
Page 116
Using the control panel 9-40 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select date and time from the system setup level 1 menu to display the time format setup screen. The time format setup screen allows the selection of either month/d...
Page 117
Using the control panel 9-41 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the set date and time mm/dd/yyyy screen allows the internal date and time of the ups to be set in the month/day/year format. The date and time information is used f...
Page 118
Using the control panel 9-42 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the set date and time dd/mm/yyyy screen allows the internal date and time of the ups to be set in the day/month/year format. The date and time information is used f...
Page 119
Using the control panel 9-43 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com select com port setup from the system setup level 1 menu to display the com port setup screen. This screen allows selection of the serial com port to set up. Figure...
Page 120
Using the control panel 9-44 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the com setup screen is used to change and save the settings for the serial communication ports. The com port number selected from the com port setup screen display...
Page 121
Using the control panel 9-45 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.3 system controls screen press the controls pushbutton on the main menu bar to display the system controls screen. Load off, normal operation, transfer to bypass,...
Page 122
Using the control panel 9-46 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com system controls load off pm off chgr on maintenance bypass bypass power module (pm) off : off : online : charger off : figure 9-52. System controls screen 2 the chg...
Page 123
Using the control panel 9-47 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.4 load off screen the load off screen appears when the load off pushbutton is selected from the main menu bar or system controls menu bar. This screen allows the ...
Page 124
Using the control panel 9-48 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9.5 reading the status indicators the four symbols on the right side of the control panel are status indicators. They are colored light emitting diode (led) lamps, ...
Page 125: Chapter 10
10-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 10 ups operating instructions the following procedures provide instructions for operating the ups or parallel system. For a description of the ups control panel functions, see chap...
Page 126
Ups operating instructions 10-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7. Observe the following messages appear sequentially on the power module (pm) status line: dc starting inverter starting inverter syncing ready online the recti...
Page 127
Ups operating instructions 10-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.1.3 starting the power module to start the power module without transferring the critical load to normal, perform the following procedure: 1. Close the ups in...
Page 128
Ups operating instructions 10-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 3. The ups is now operating in bypass mode and the bypass status indicator is illuminated. The power module (pm) status indicates ready. The system is now on byp...
Page 129
Ups operating instructions 10-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.1.7 ups and critical load shutdown to perform maintenance or service on the critical load, shut down power to the load by performing the following procedure: ...
Page 130
Ups operating instructions 10-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.1.9 using the ups load off pushbutton a ups load off is initiated by the load off pushbutton from the main menu bar or the system controls menu bar. This push...
Page 131
Ups operating instructions 10-7 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.1.10 using the remote emergency power-off switch a ups emergency power-off is initiated by the repo pushbutton switch. In an emergency, you can use this switc...
Page 132
Ups operating instructions 10-8 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.2 multiple module parallel operation 10.2.1 starting the parallel system in normal mode to start the parallel system, perform the following procedure: 1. Clos...
Page 133
Ups operating instructions 10-9 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.2.2 starting the parallel system in bypass mode if the inverter output of the upms is not available and the critical load needs to be energized, perform the f...
Page 134
Ups operating instructions 10-10 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.2.3 transfer parallel system from normal to bypass mode to transfer the critical load to bypass mode, perform the following procedure: c a u t i o n in bypas...
Page 135
Ups operating instructions 10-11 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 10.2.5 single upm shutdown to shut down a single upm, perform the following procedure: note the upm can be shut down only if remaining upms can support the crit...
Page 136
Ups operating instructions 10-12 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7. Press the normal pushbutton on the system controls menu bar of the upm. 8. Observe the following messages appear sequentially on the power module (pm) status...
Page 137
Ups operating instructions 10-13 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7. To shut down the last upm, press the repo pushbutton switch. See “using the parallel system remote emergency power-off switch” in paragraph 10.2.9. The input...
Page 138
Ups operating instructions 10-14 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com c a u t i o n do not attempt to restart the system after load off until the cause of the shutdown has been identified and cleared. 3. To restart the ups after p...
Page 139: Chapter 11
11-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 11 using features and options the many standard features of your ups system provide consistent, economical, and dependable power protection. In addition, you can add available opti...
Page 140
Using features and options 11-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11.3 optional remote monitor panel ii as an option, a remote monitor panel ii (rmp ii) can be installed to monitor the operation of the ups system from virtually...
Page 141
Using features and options 11-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com the rmp ii contains a local horn and the backlit status indicators listed in table 11-1. Table 11-1. Rmp ii status indicators system normal the ups is energized ...
Page 142
Using features and options 11-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11.4 relay interface module ii an optional rim ii uses relay contact closures to indicate the operating status and alarm condition of the ups system. The rim ii ...
Page 143
Using features and options 11-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11.5 supervisory contact module ii an optional scm ii establishes an interface between the ups system and the customer’s monitor. This interface allows the custo...
Page 144
Using features and options 11-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 145: Chapter 12
12-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 12 responding to system events 12.1 general when the ups system is running in normal mode, it continually monitors itself and the incoming utility power. In battery or bypass modes...
Page 146
Responding to system events 12-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com alarms message horn phone relay log* indication battery totally discharged 1 no 1 ha shutdown imminent battery totally discharged ok off no 1 ha condition clear...
Page 147
Responding to system events 12-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com alarms indication log* relay phone horn message configuration error 1 no 1 ha service required configuration error ok off no 1 ha condition cleared external com...
Page 148
Responding to system events 12-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com alarms indication log* relay phone horn message l3 overload (high level) 1 no 1 ha user action required l3 overload (high level) ok off no 1 ha condition cleare...
Page 149
Responding to system events 12-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com notices message horn phone relay log* indication automatic shutdown pending 1 no no a information only automatic shutdown pending ok off no no a condition clear...
Page 150
Responding to system events 12-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com notices indication log* relay phone horn message input ac over voltage 1 no no ha information only input ac over voltage ok off no no ha condition cleared input...
Page 151
Responding to system events 12-7 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com notices indication log* relay phone horn message output ac under voltage 1 no no ha information only output ac under voltage ok off no no ha condition cleared o...
Page 152
Responding to system events 12-8 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com status message horn phone relay log* indication battery switchgear closed no no no h user status battery switchgear open no no no h user status bypass switchgea...
Page 153
Responding to system events 12-9 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com command message horn phone relay log* indication load off command received yes no no h information only to normal mode command no no no h information only to by...
Page 154
Responding to system events 12-10 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 155: Chapter 13
13-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 13 communication this chapter describes the communication features of the powerware 9390 100–160 kva ups and provides information about connecting hardware and using terminal mode....
Page 156
Communication 13-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com lan and telephone drops for use with x-slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an x-slot card, please con...
Page 157
Communication 13-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com remote notification is an extension of the terminal mode with the additional support algorithms necessary to control an external modem. Connection to the ups is made when a u...
Page 158
Communication 13-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 13.4.2 event history log this key sequence prints the entire event history log of the ups at the time the data is requested. The printout begins with the oldest alarm entry i...
Page 159
Communication 13-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 03/11/2004 14:13:03.000 status: csb power supply on 03/11/2004 14:13:03.043 notice: inverter initializing 03/11/2004 14:13:05.721 status: ups power supply ok 03/11/2004 14:13...
Page 160
Communication 13-6 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 161: Chapter 14
14-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 14 maintaining the ups system the components inside the ups cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very...
Page 162
Maintaining the ups system 14-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 쑺 determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded battery can result in electr...
Page 163
Maintaining the ups system 14-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 3. Ensure the operating environment is within the parameters specified in chapter 15, “product specifications,” and drawing 164201554-2 on page a-3. 4. Ensure th...
Page 164
Maintaining the ups system 14-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 165: Chapter 15
15-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com chapter 15 product specifications 15.1 model numbers the ups systems are housed in free-standing cabinets with safety shields behind the doors. The ups systems are available in 50/60 hz wi...
Page 166
Product specifications 15-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 15.2.2 ups system output ups output capacity 100% rated current output voltage regulation ¦ 1% (10% to 100% load) output voltage adjustment (nominal +/–3%) 208 vac n...
Page 167
Product specifications 15-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 15.3 multiple module parallel specifications 15.3.1 upm input same as single module. 15.3.2 upm output same as single module. 15.3.3 environmental same as single mod...
Page 168
Product specifications 15-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 169: Appendix A
A-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com appendix a 16- installation information the information in this appendix is helpful during the planning and installation of the ups system. This appendix contains the following drawings: 쑺 ...
Page 170
Battery cabinet ups cabinet 164201554---1 1 of 1 typical powerware 9390 ups system 111504 b description: date: drawing no: sheet: revision: installation information a-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com.
Page 171
164201554---2 1 of 2 physical features and requirements 081505 c description: date: drawing no: sheet: revision: installation information a-3 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 1. The ups equipment operating environment must mee...
Page 172
2 of 2 physical features and requirements 081505 c 164201554---2 description: date: drawing no: sheet: revision: installation information a-4 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 7. The basic environmental requirements for operati...
Page 173
1 of 1 ups system oneline configurations 081505 d 164201554---3 description: date: drawing no: sheet: revision: installation information a-5 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table d. Ups system oneline configurations oneline d...
Page 174
Battery breaker ups system oneline drawing 032406 d 164201554---4 description: date: drawing no: sheet: revision: ups cabinet inverter rectifier static switch remote epo building alarms ac output to critical load ac input to ups rectifier 3 wire a---b---c ac input to bypass 3 or 4 wire a---b---c rot...
Page 175
Battery breaker ups system oneline drawing 032406 d 164201554---4 description: date: drawing no: sheet: revision: ups cabinet inverter rectifier static switch remote epo building alarms ac output to critical load ac input to ups rectifier 3 wire a---b---c ac input to bypass 3 or 4 wire a---b---c rot...
Page 176
Ups system oneline drawing 081505 c 164201554---4 description: date: drawing no: sheet: revision: maintenance bypass panel (provided by others) output from ups mib to ups input mib: maintenance isolation breaker mbp: maintenance bypass breaker mbp backfeed k5 k3 static switch ac input battery breake...
Page 177
Ups system oneline drawing 081505 d description: date: drawing no: sheet: revision: output to critical load battery cabinet battery breaker e4. E5 e9 e10 e11 e12 fuse k5 static switch fuse k3 fuse battery converter rectifier inverter k1 upm 1 e1 e2 e3 e6e 7e8 e12 a b see note 2 module tie cabinet (o...
Page 178
Ups system oneline drawing 081505 d typical parallel system (2+1 and 3+0 configurations) 164201554---4 note: 1. Upm and system bypass input feeds must come from the same source. 2. Remove jumper for dual-feed. 3. See note 27 on page a---21 for neutral bonding instructions. Description: date: drawing...
Page 179
Ups system oneline drawing 081505 d typical parallel system (3+1 and 4+0 configurations) 164201554---4 note: 1. Upm and system bypass input feeds must come from the same source. 2. Remove jumper for dual-feed. 3. See note 27 on page a---21 for neutral bonding instructions. Description: date: drawing...
Page 180
1 of 15 power wiring installation notes 032406 e 164201554---5 description: date: drawing no: sheet: revision: installation information a-12 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table e. Input/output ratings & external wiring requ...
Page 181
Power wiring installation notes 032406 e 164201554---5 2 of 15 description: date: drawing no: sheet: revision: installation information a-13 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table f. Input/output ratings & external wiring requ...
Page 182
Power wiring installation notes 032406 d 164201554---5 3 of 15 description: date: drawing no: sheet: revision: installation information a-14 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table g. Input/output ratings & external wiring requ...
Page 183
Power wiring installation notes 081505 c 164201554---5 note: customer ground can be run in any conduit listed in table j. 4 of 15 description: date: drawing no: sheet: revision: installation information a-15 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e...
Page 184
Power wiring installation notes 081505 c 164201554---5 note: customer ground can be run in any conduit listed in table j. 5 of 15 description: date: drawing no: sheet: revision: installation information a-16 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e...
Page 185
Power wiring installation notes 081505 c 164201554---5 6 of 15 description: date: drawing no: sheet: revision: installation information a-17 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11. Per nec article 300-20(a), all three-phase condu...
Page 186
Power wiring installation notes c 164201554---5 081505 7 of 15 description: date: drawing no: sheet: revision: installation information a-18 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table j. Power cable conduit requirements (cont’d) u...
Page 187
Power wiring installation notes 081505 d 164201554---5 8 of 15 description: date: drawing no: sheet: revision: installation information a-19 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 14. External overcurrent protection is not provided ...
Page 188
Power wiring installation notes 081505 c 164201554---5 9 of 15 description: date: drawing no: sheet: revision: installation information a-20 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 19. There is no dc disconnect device within the ups....
Page 189
Power wiring installation notes 032406 e 164201554---5 10 of 15 description: date: drawing no: sheet: revision: installation information a-21 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 25. Parallel system upm and system bypass input fee...
Page 190
Power wiring installation notes 081505 d 164201554---5 11 of 15 description: date: drawing no: sheet: revision: installation information a-22 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 28. See drawing 164201554---7 for upm terminal loca...
Page 191
Power wiring installation notes 032406 e 164201554---5 12 of 15 description: date: drawing no: sheet: revision: installation information a-23 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table o. Input/output ratings for powerware 9390---...
Page 192
Power wiring installation notes 032406 e 164201554---5 13 of 15 description: date: drawing no: sheet: revision: installation information a-24 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table p. Input/output ratings for powerware 9390---...
Page 193
Power wiring installation notes 032406 e 164201554---5 14 of 15 description: date: drawing no: sheet: revision: installation information a-25 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com table q. Input/output ratings for powerware 9390---...
Page 194
Power wiring installation notes 121504 c 164201554---5 description: date: drawing no: sheet: revision: upm 2 battery bypass inputs to upms upm 1 battery upm 3 battery upm 4 battery outputs from upms 1a (30) 2a (35) 3a (40) 4a (45) 1b (25) 2b (20) 3b (15) 4b (10) 15 of 15 note: wire lengths in the di...
Page 195
1 of 6 conduit and wire entry locations 111504 b 164201554---6 remove debris shield covering exhaust grill before operating system. Top entry conduit landing for ac input and output, dc input, dc control, and interface connections. (remove panel to drill or punch conduit holes.) description: date: d...
Page 196
2 of 6 conduit and wire entry locations 121504 c left side view description: date: drawing no: sheet: revision: right side view inter-cabinet wiring access knockouts. Remove knockouts, as required, to route wires between cabinets. (install nylon grommet after removal of knockouts.) inside panels int...
Page 197
1 of 4 ups power terminal locations 032406 c 164201554---7 208v input and 208v output note: metal shields covering wiring terminals must be removed or opened to gain access to terminals. Ground terminals ac input to ups rectifier and bypass (a, b, c, n) description: date: drawing no: sheet: revision...
Page 198
2 of 4 ups power terminal locations 111504 b 164201554---7 description: date: drawing no: sheet: revision: 208v input and 208v output rectifier input terminals (located on contactor k1) bypass input terminals output terminals (located on contactor k3) dc input from battery + (e4) --- (e5) ac input t...
Page 199
3 of 4 ups power terminal locations 032406 c 164201554---7 480v input and 480v output ground terminals wireway for top entry power wiring note: metal shields covering wiring terminals must be removed or opened to gain access to terminals. Description: date: drawing no: sheet: revision: ac input to u...
Page 200
4 of 4 ups power terminal locations 121504 c 164201554---7 480v input and 480v output terminal detail phase a (e9) phase b (e10) phase c (e11) description: date: drawing no: sheet: revision: ac output to critical load dc input from battery + (e4) --- (e5) phase a (e1) phase b (e2) phase c (e3) phase...
Page 201
1 of 13 interface wiring installation notes and terminal locations 032406 e description: date: drawing no: sheet: revision: 164201554---8 installation information a-33 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 1. Use class 1 wiring met...
Page 202
032406 d 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations tb1 tb2 x-slots standard x-slot communication bay wireway for bottom entry interface wiring note: metal shields covering wiring terminals must be removed or opened to gai...
Page 203
Note: 1. All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 vdc, 20 ma minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either normally-open or normally-closed cont...
Page 204
081505 c 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations note: 1. All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 vdc, 20 ma minimum) connected between the alarm inp...
Page 205
032406 d 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 5 of 13 installation information a-37 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 9. The ups dc uvr trip an...
Page 206
032406 d 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 6 of 13 installation information a-38 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 11. The remote epo featur...
Page 207
032406 d 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 7 of 13 installation information a-39 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 14. Wire the maintenance ...
Page 208
081505 c 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 8 of 13 installation information a-40 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com 15. 120 vac should be pro...
Page 209
081505 d 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations connections for parallel system control connections for rmp ii, rim ii, or scm ii building alarm 2 replacement j3 note: all interface wiring is to be provided by the cust...
Page 210
081505 d 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations note: this drawing is for parallel wiring purposes and is not a floor layout plan. Upms can be placed in any physical order. Parallel system can (pull chain) wiring upm 1...
Page 211
Installation information a-43 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com building alarm pull chain wiring terminations from upm 1 to upm 2 to upm 3 (if installed) to upm 4 (if installed) tb2–1 (bldg alarm 2) tb2–3 (on bypass no) tb2–3 (...
Page 212
081505 c 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations terminal tb–1 signal connections from the ups ground terminal remote monitor panel and relay interface module terminal locations terminal tb–3 120 vac power supervisory c...
Page 213
081505 c 164201554---8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations ups can card j3 120 vac from critical bus line neutral twisted pair ground terminal rmp ii, rim ii, or scm ii 13 of 13 installation information a-45 eaton powerware ® 939...
Page 214
1 of 4 ups cabinet dimensions 111504 b 164201554---9 front view right side view description: date: drawing no: sheet: revision: dimensions are in millimeters [inches] installation information a-46 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware....
Page 215
Ups cabinet dimensions 111504 b 164201554---9 top view bottom view dimensions are in millimeters [inches] 2 of 4 description: date: drawing no: sheet: revision: installation information a-47 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com.
Page 216
Ups cabinet dimensions 111504 b 164201554---9 bottom view with optional floor mounting brackets dimensions are in millimeters [inches] 3 of 4 description: date: drawing no: sheet: revision: installation information a-48 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164...
Page 217
Ups cabinet dimensions 081505 d 164201554---9 bottom view with optional seismic mounting brackets dimensions are in millimeters [inches] 4 of 4 description: date: drawing no: sheet: revision: seismic kit installation installation information a-49 eaton powerware ® 9390 ups (100–160 kva) installation...
Page 218
1 of 1 optional remote emergency power-off 111504 b 164201554---10 description: date: drawing no: sheet: revision: 114.3 (4.50) 115.8 (4.56) 11.9 (0.47) 95.3 (3.75) square 88.9 (3.50) 1/2 in. Knockout pattern typ. 5 sides to ups to other equipment dimensions are in millimeters [inches] note: 1. Cond...
Page 219
1 of 1 optional remote monitor panel 111504 b 164201554---11 description: date: drawing no: sheet: revision: knockouts provided on five surfaces flush mount use #10 pan head screws (mount with vent holes facing up) surface mount use #10 pan head screws (for hanging) (mount with vent holes facing up)...
Page 220
1 of 2 optional relay interface module 111504 b 164201554---12 description: date: drawing no: sheet: revision: knockouts provided on five surfaces flush mount use #10 pan head screws (mount with vent holes facing up) surface mount use #10 pan head screws (for hanging) (mount with vent holes facing u...
Page 221
Optional relay interface module 111504 b description: date: drawing no: sheet: revision: 164201554---12 2 of 2 15–pin d–sub connectors installation information a-53 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com.
Page 222
1 of 1 optional supervisory contact module 111504 b 164201554---13 description: date: drawing no: sheet: revision: knockouts provided on five surfaces flush mount use #10 pan head screws (mount with vent holes facing up) surface mount use #10 pan head screws (for hanging) (mount with vent holes faci...
Page 223
W-1 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com warranty limited factory warranty for three-phase powerware ® products warrantor: the warrantor for the limited warranties set forth herein is eaton electrical inc., a delaware corporation ...
Page 224
Warranty w-2 eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201554 rev e powerware.Com this page intentionally left blank..
Page 226
*164201554e* 164201554 e.