Summary of Powerware 9390

  • Page 1

    Static uninterruptible power supply page 1 of 1 eaton 9390 guide specification october 9, 2009 static uninterruptible power supply guide specification model eaton 9390 20-160 kva part 1 - general 1.01 summary a. This specification describes a three-phase continuous duty, on-line, double conversion, ...

  • Page 2

    Static uninterruptible power supply page 2 of 2 eaton 9390 guide specification october 9, 2009 ups will utilize a minimal/optimal combination of its internal subsystems to ensure acceptable power is always delivered to the critical load, at a system efficiency of 99% or greater, over the range of 10...

  • Page 3

    Static uninterruptible power supply page 3 of 3 eaton 9390 guide specification october 9, 2009 i) performance and technical specifications j) wiring requirements and recommendations k) physical features and requirements l) cabinet dimensions 1.05 qualifications a. The ups manufacturer shall have a m...

  • Page 4

    Static uninterruptible power supply page 4 of 4 eaton 9390 guide specification october 9, 2009 1.07 safety a. The ups shall be certified by underwriters laboratories in accordance with ul 1778. B. The ups shall be certified by the canadian standards association in accordance with csa c22.2 no.107.1-...

  • Page 5

    Static uninterruptible power supply page 5 of 5 eaton 9390 guide specification october 9, 2009 b) critical bus voltage out of limits. C) internal over temperature period expired. D) total battery discharge. E) ups failure. 2. Uninterrupted automatic re-transfer shall take place whenever the inverter...

  • Page 6

    Static uninterruptible power supply page 6 of 6 eaton 9390 guide specification october 9, 2009 ups system will alarm that the battery needs attention/replacement. The battery test shall be able to detect the following: open battery string shorted battery string battery capacity (runtime) less than 8...

  • Page 7

    Static uninterruptible power supply page 7 of 7 eaton 9390 guide specification october 9, 2009 network management systems. This capability shall allow the unit to be monitored remotely over an ethernet network using a standard web browser. 1. Ups power monitoring software: this system shall continuo...

  • Page 8

    Static uninterruptible power supply page 8 of 8 eaton 9390 guide specification october 9, 2009 shall be designed for remote installation using customer-supplied wiring and conduit, and shall be capable of free-standing or wall-mounted installation. 2.05 uninterruptible power supply ratings and opera...

  • Page 9

    Static uninterruptible power supply page 9 of 9 eaton 9390 guide specification october 9, 2009 1. Synchronizing bypass voltage range shall be +/- 10% of average nominal input voltage. 2. Synchronizing bypass frequency range is centered on the nominal frequency. 3. Bypass and rectifier inputs can be ...

  • Page 10

    Static uninterruptible power supply page 10 of 10 eaton 9390 guide specification october 9, 2009 1. Nominal output voltage 208 vac, 3-phase, 3 wire or 4-wire (or 480v, 3-phase, 3- wire or 4-wire) plus ground at the output of the integrated distribution and bypass cabinet. Output wiring configuration...

  • Page 11

    Static uninterruptible power supply page 11 of 11 eaton 9390 guide specification october 9, 2009 f. Ups output with energy saver system option 1. The energy saver system acts to optimize the internal components of the ups power train to maximize system efficiency when the bypass source is within the...

  • Page 12

    Static uninterruptible power supply page 12 of 12 eaton 9390 guide specification october 9, 2009 designed for computer room applications. Front doors shall have locks to prevent unauthorized entry. B. Ventilation: the ups shall be designed for forced-air cooling. Air inlets shall be on the front of ...

  • Page 13

    Static uninterruptible power supply page 13 of 13 eaton 9390 guide specification october 9, 2009 the load. A text message shall indicate if the battery charge is low or if the battery is installed but disconnected. 4. Alarm: this shall indicate that the ups detects an alarm condition, outlined in de...

  • Page 14

    Static uninterruptible power supply page 14 of 14 eaton 9390 guide specification october 9, 2009 a. Communications bay: the ups shall be equipped with field configurable communications bays that will accommodate four (4) communication devices b. Remote monitoring: 1. Optional web/snmp communication ...

  • Page 15

    Static uninterruptible power supply page 15 of 15 eaton 9390 guide specification october 9, 2009 d. To comply with agency safety requirements, the ups module shall not rely upon any disconnect devices outside of the ups module to isolate the battery cabinet from the ups module. Part 3 - execution 3....

  • Page 16

    Static uninterruptible power supply page 16 of 16 eaton 9390 guide specification october 9, 2009 f) check for the voltage difference between the inverter output and the bypass source. G) optional on site full-load, step-load, and battery discharge tests using supplier furnished load bank, shall also...