- DL manuals
- Eaton
- UPS
- Powerware 9390
- Installation And Operation Manual
Eaton Powerware 9390 Installation And Operation Manual - page 46
INSTALLING A REMOTE EMERGENCY POWER-OFF CONTROL
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S 164201604 Rev D www.powerware.com
5-2
NOTE REPO switch rating is 6A/120 Vac or 3A/240 Vac. The REPO switch must be a latching-type switch
with a dedicated circuit.
REPO
Switch
Twisted Wires (2)
4
5
CUSTTB
Figure 5‐2. REPO Wiring
5.
If you are installing multiple REPO stations, wire additional stations in parallel
with the first REPO station.
6.
If required, install ½” conduit and wiring from the second contact block in the
REPO station to trip circuitry of other equipment, such as upstream protective
devices, facility monitoring devices, or alarms. Using the contact block that was
not used for the UPS EPO wiring will help maintain isolation between the control
systems.
A normally open (NO) contact and a normally closed (NC) contact are provided,
and the two are electrically isolated. If single-pole, double-throw action is desired,
one side of the NO contact can be jumpered to one side of the NC contact to
form the common connection point. REPO switch wiring must be according to
UL Class I requirements.
7.
Secure the UPS by reversing all steps taken to prepare it for a REPO station
installation.
Summary of Powerware 9390
Page 1
Powerware 9390 ups 100–160 kva installation and operation manual ®.
Page 3
Powerware 9390 ups 100–160 kva installation and operation manual ®.
Page 4
Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...
Page 5
Special symbols the following are examples of symbols used on the ups or accessories to alert you to important information: risk of electric shock - observe the warning associated with the risk of electric shock symbol. Caution: refer to operator's manual - refer to your operator's manual for additi...
Page 6
This page intentionally left blank..
Page 7
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com i table of contents 1 introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 8
Table of contents eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com ii 4.8 installing interface connections 4-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 9
Table of contents eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com iii 8.3 system controls screen 8-39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 10
Table of contents eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com iv 13.3 recycling the used battery or ups 13-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 11
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com v list of figures figure 1‐1. Powerware 9390 ups (100–160 kva) cabinet 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fi...
Page 12
List of figures eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com vi figure 8‐33. Output unit x meter screen 8-26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 13
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-1 chapter 1 introduction eaton's powerware ® 9390 uninterruptible power supply (ups) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system...
Page 14
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-2 1.1 ups standard features the ups has many standard features that provide cost‐effective and consistently reliable power protection. 1.1.1 control panel the control panel, ...
Page 15
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-3 1.1.8 installation features cabinets can be permanently bolted to the floor or left standing on leveling feet. Power and control wiring can be routed through the top or bot...
Page 16
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-4 1.2.4 powerware hot sync parallel system a parallel ups system with two to four uninterruptible power modules (upms) can be installed to provide a parallel capacity and/or ...
Page 17
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-5 1.3 basic system configurations the following basic ups system configurations are possible: s single module ups and one to four battery cabinets s single module ups with up...
Page 18
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-6 1.4 conventions used in this manual this manual uses these type conventions: s bold type highlights important concepts in discussions, key terms in procedures, and menu opt...
Page 19
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-7 1.6 getting help if you need help with any of the following: s scheduling initial startup s regional locations and telephone numbers s a question about any of the informati...
Page 20
Introduction eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 1-8 this page intentionally left blank..
Page 21
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 2-1 chapter 2 safety warnings important safety instructions save these instructions s this manual contains important instructions that should be followed during installation and maintenance...
Page 22
Safety warnings eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 2-2 c a u t i o n s installation or servicing should be performed by qualified service personnel knowledgeable of ups and battery systems, and required precautions. Keep una...
Page 23
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 2-1 section i installation.
Page 24
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 2-2.
Page 25
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 3-1 chapter 3 ups installation plan and unpacking use the following basic sequence of steps to install the ups: 1. Create an installation plan for the ups system (chapter 3). 2. Prepare you...
Page 26
Ups installation plan and unpacking eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 3-2 3.2.2 preparing for wiring the ups system note if installing, as part of the ups system, a maintenance bypass without a rectifier input breaker, a mi...
Page 27
Ups installation plan and unpacking eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 3-3 w a r n i n g the ups cabinet is heavy (see table a on page a-3). If unpacking instructions are not closely followed, the cabinet may tip and cause s...
Page 28
Ups installation plan and unpacking eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 3-4 this page intentionally left blank..
Page 29
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-1 chapter 4 installing the ups system this section describes the ups system installation for single modules and multi-modules, including: unloading the cabinets, ups internal and external...
Page 30
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-2 4.2 unloading the ups cabinet from the pallet and mechanical installation note when a line-up-and-match ups system is ordered together with battery cabinets, t...
Page 31
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-3 shipping bracket bolts front view vented front doors front shipping bracket shipping bracket bolts removable skid skid bolts pallet figure 4‐1. Removing front ...
Page 32
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-4 rear shipping bracket rear view shipping bracket bolts shipping bracket bolts pallet figure 4‐2. Removing rear shipping bracket on the powerware 9390 ups.
Page 33
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-5 note in the following step the pallet tilts and acts as a ramp once the cabinet is rolled beyond the the center of the pallet. Be sure to restrain the cabinet ...
Page 34
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-6 4.5 integrated accessory cabinet installation to install and wire an integrated accessory cabinet (iac), refer to the powerware 9390 integrated accessory cabin...
Page 35
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-7 4.7.1 external wiring installation procedure a to install wiring to connections: 1. Slide the air filters up and remove them from the cabinet. 2. Remove the sc...
Page 36
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-8 15. Connect phase a, b, and c, and neutral (if required) power wiring from the idc or iac to the ups cabinet output and neutral terminals. See appendix a for w...
Page 37
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-9 10. Disconnect the single-feed jumpers from the phase a, b, and c terminals on the rectifier input terminals and bypass input terminals. Remove the jumpers fro...
Page 38
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-10 4.7.3 battery wiring c a u t i o n when sizing the battery system, do not exceed the internal battery charger capabilities. See chapter 14, “product specifica...
Page 39
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-11 6. If installing interface wiring from the bottom of the cabinet, proceed to step 7; otherwise, proceed to step 8. 7. Remove the screws securing the right sid...
Page 40
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-12 9. Connect the wiring to tb2 terminals. 10. Proceed to step 17. 11. If installing interface wiring from the bottom of the cabinet, proceed to step 12; otherwi...
Page 41
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-13 7. Close the control panel door and secure with the retained hardware. 8. Reinstall the doors removed previously and secure with the retained hardware. 9. Clo...
Page 42
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-14 installation checklist - all packing materials and restraints have been removed from each cabinet. - each cabinet in the ups system is placed in its installed...
Page 43
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-15 parallel system installation checklist - each cabinet in the parallel system is placed in its installed location. - all conduits and cables are properly route...
Page 44
Installing the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 4-16 notes _________________________________________________________________________ _________________________________________________________________________ ____...
Page 45
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 5-1 chapter 5 installing a remote emergency power-off control a latching-type remote emergency power-off (repo) switch can be used in an emergency to shut down the ups and remove power to t...
Page 46
Installing a remote emergency power-off control eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 5-2 note repo switch rating is 6a/120 vac or 3a/240 vac. The repo switch must be a latching-type switch with a dedicated circuit. Repo switch...
Page 47
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-1 chapter 6 installing optional accessories this chapter contains installation instructions for the following options: s powerware hot sync can bridge card and parallel system control wir...
Page 48
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-2 4. Install wiring from the powerware hot sync can bridge card in accordance with the instructions listed below: s parallel system wiring (see paragraph 6...
Page 49
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-3 12. Install parallel system backup control (pull chain) wiring between the bypass relay and building alarm 2. See drawing 164201604-8 starting on page a-...
Page 50
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-4 9. To check the operation of the rmp, ensure that the ups is supplying the load via inverter or bypass. If the indicators on the rmp show the appropriate...
Page 51
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-5 9. Contact your eaton service representative for verification and testing of the rim and its connections prior to making connections with j1 through j4 (...
Page 52
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-6 6.5 installing a scm to install scm wiring: 1. Verify the ups system is turned off and all power sources are removed. See chapter 9, “ups operating instr...
Page 53
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-7 9. Install wiring between the scm terminal block tb2 and the monitoring equipment. See figure 6‐2 for terminal assignments and drawing 164201604-8 on pag...
Page 54
Installing optional accessories eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-8 this page intentionally left blank..
Page 55
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-9 section ii operation.
Page 56
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 6-10
Page 57
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-1 chapter 7 understanding ups operation the powerware 9390 ups is a continuous-duty, solid‐state, transformerless (at 208, 400, and 480 vac), three-phase, true online system that provides...
Page 58
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-2 the emergency bypass consists of a continuous-duty static switch and backfeed protection contactor k5. The backfeed protection contactor is located in series...
Page 59
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-3 7.1.2 normal mode – rt figure 7‐2 shows the path of electrical power through the ups system when the ups is operating in normalmode. Static switch k5 rectifi...
Page 60
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-4 the neutral from the system input is connected to the neutral regulator in the dc capacitors. The output neutral of the system is connected with the required...
Page 61
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-5 in bypass mode, the output of the system is provided with three-phase ac power directly from the system input. While in this mode, the output of the system i...
Page 62
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-6 7.1.4 battery mode – rt the ups automatically transfers to battery mode if a utility power outage occurs, or if the utility power does not conform to specifi...
Page 63
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-7 if at any time during the battery discharge the input power becomes available again, contactors k1 and k5 close and the rectifier begins to supply dc current...
Page 64
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-8 7.2.1 multiple module parallel system modes similar to the single module system, the powerware 9390 ups parallel system supports a critical load in three dif...
Page 65
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-9 7.2.2 normal mode – parallel in normal mode, utility ac power is supplied to the upms. Each upm then conditions the incoming ac power and provides clean, reg...
Page 66
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-10 7.2.3 bypass mode – parallel in bypass mode, the output of the system is provided with three-phase ac power directly from the bypass input. While in this mo...
Page 67
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-11 the parallel system can be transferred from normal mode to bypass mode manually. However, the parallel system automatically switches to bypass mode whenever...
Page 68
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-12 7.2.4 battery mode – parallel the upms transfer to battery mode automatically if a utility power outage occurs, or if the utility power does not conform to ...
Page 69
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-13 if at any time during the battery discharge the input power becomes available again, the rectifier begins to supply dc current to the inverter. At this poin...
Page 70
Understanding ups operation eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 7-14 an abm charge cycle is initiated whenever one of these four conditions occurs since the last charge cycle: s the batteries have rested over the maximum rest...
Page 71
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-1 chapter 8 using the control panel this chapter describes the ups control panel, including controls and indicators, and how to monitor ups operation. The control panel is located on the ...
Page 72
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-2 8.1 using the lcd and pushbuttons the lcd on the control panel provides an operator interface with the ups system. Figure 8‐2 identifies the display areas discus...
Page 73
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-3 8.2 using the main menu the ups main menu bar allows you to display data in the information area to help you monitor and control ups operation. The following men...
Page 74
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-4 8.2.2 event screens press the events pushbutton on the main menu bar or history menu bar to display a listing of all system events that are currently active. The...
Page 75
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-5 press the history pushbutton on the active events menu bar to display the history log. The history log lists up to the 512 system events in chronological order, ...
Page 76
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-6 8.2.3 unit meter screens the unit meter screens show the ups meter readings for the unit (or units, if a parallel system is installed). The default voltage displ...
Page 77
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-7 the input screen shows input voltage (phase‐to‐neutral), input current (each phase), and frequency of the incoming utility source, as well as the kva, kw, and po...
Page 78
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-8 the battery screen displays the battery voltage (vdc), the battery current (idc), the minutes of battery time remaining, and battery temperature. Battery tempera...
Page 79
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-9 8.2.4 battery discharge log press the meters pushbutton on the main menu bar to display the unit meter screens. Scroll through the meter screens using the or pus...
Page 80
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-10 press the log pushbutton on the battery discharge log summary menu bar to display the battery discharge log screen. The battery discharge log screen displays th...
Page 81
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-11 8.2.5 kw demand log press the meters pushbutton on the main menu bar to display the unit meter screens. Scroll through the meter screens using the or pushbutton...
Page 82
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-12 press the log pushbutton on the kw demand log summary menu bar to display the kw demand log screen. The kw demand log screen displays the individual log entries...
Page 83
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-13 press the setup pushbutton on the kw demand log summary menu bar to display the current kw demand log setup screen 1. The current kw demand log setup screen 1 d...
Page 84
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-14 press the change pushbutton on the current kw demand log setup menu bar to display the current kw demand log setup screen 2. The current kw demand log setup scr...
Page 85
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-15 select time interval monitored from the current kw demand log setup screen 2 menu to display the time interval monitored setup screen. The time interval monitor...
Page 86
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-16 select maximum level (kw) from the current kw demand log setup screen 2 menu to display the maximum level (kw) setup screen. The maximum level (kw) setup screen...
Page 87
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-17 8.2.6 maximum current log press the meters pushbutton on the main menu bar to display the unit meter screens. Scroll through the meter screens using the or push...
Page 88
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-18 press the log pushbutton on the maximum current log summary menu bar to display the maximum current log screen. The maximum current log screen displays the indi...
Page 89
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-19 press the setup pushbutton on the maximum current log summary menu bar to display the maximum current log setup screen 1. The maximum current log setup screen 1...
Page 90
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-20 press the change pushbutton on the maximum current log setup menu bar to display the maximum current log setup screen 2. The maximum current log setup screen ca...
Page 91
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-21 select time interval monitored from the maximum current log setup screen 2 menu to display the time interval monitored setup screen. The time interval monitored...
Page 92
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-22 select maximum % of full load from the maximum current log setup screen (screen 2) menu to display the maximum % of full load setup screen. The maximum % of ful...
Page 93
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-23 select calculation method from the maximum current log setup screen 2 menu to display the calculation method setup screen. The calculation method setup screen a...
Page 94
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-24 8.2.7 system meters screens the system meters screens show the total system and individual ups unit meter readings from any unit, when a parallel system is inst...
Page 95
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-25 the output total system screen shows output voltage (phase‐to‐neutral), output current (each phase), and frequency being supplied by the ups, as well as the kva...
Page 96
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-26 figure 8‐33 through figure 8‐37 show the system meters screens. To scroll through the meter screens, press the or pushbuttons on the menu bar. The current ups r...
Page 97
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-27 the input screen shows input voltage (phase‐to‐neutral), output current (each phase), and frequency of the incoming utility source, as well as the kva, kw, and ...
Page 98
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-28 the battery screen displays the battery voltage (vdc), the battery current (idc), the minutes of battery time remaining, and battery temperature. Battery temper...
Page 99
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-29 8.2.8 system setup level 0 screens press the setup pushbutton on the main menu bar to display the system setup level 0 screen. This screen can be used to: s ent...
Page 100
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-30 select contrast from the system setup level 0 menu to display the contrast adjust screen. Figure 8‐39 shows the contrast adjust screen. Use the or pushbuttons t...
Page 101
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-31 select unit type from the system setup level 0 menu to display the unit type screen. The unit type screen provides the model, cto, and serial numbers of the ups...
Page 102
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-32 the system setup level 1 screen can be used to set the ups date and time, set the serial ports, change the level 1 password, and log out of level 1. In addition...
Page 103
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-33 select change password from the system setup level 1 menu to display the change password screen. The change password screen allows the system setup level 1 pass...
Page 104
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-34 select date and time from the system setup level 1 menu to display the time format setup screen. The time format setup screen allows the selection of either mon...
Page 105
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-35 the set date and time mm/dd/yyyy screen allows the internal date and time of the ups to be set in the month/day/year format. The date and time information is us...
Page 106
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-36 the set date and time dd/mm/yyyy screen allows the internal date and time of the ups to be set in the day/month/year format. The date and time information is us...
Page 107
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-37 select com port setup from the system setup level 1 menu to display the com port setup screen. This screen allows selection of the serial com port to set up. Fi...
Page 108
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-38 the com setup screen is used to change and save the settings for the serial communication ports. The com port number selected from the com port setup screen dis...
Page 109
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-39 8.3 system controls screen press the controls pushbutton on the main menu bar to display the system controls screen. Load off, normal operation, transfer to byp...
Page 110
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-40 8.4 load off screen the load off screen appears when the load off pushbutton is selected from the main menu bar or system controls menu bar. This screen allows ...
Page 111
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-41 8.5 reading the status indicators the four symbols on the right side of the control panel are status indicators. They are colored light emitting diode (led) lam...
Page 112
Using the control panel eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 8-42 this page intentionally left blank..
Page 113
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-1 chapter 9 ups operating instructions the following procedures provide instructions for operating the ups or parallel system. For a description of the ups control panel functions, see ch...
Page 114
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-2 8. Close the battery breaker any time after inverter syncing or close battery appears on the display. Once the inverter reaches full voltage, and the battery ...
Page 115
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-3 8. Observe the following messages appear sequentially on the power module (pm) status line: dc starting inverter starting inverter syncing ready the rectifier...
Page 116
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-4 9.1.6 transfer from normal to bypass mode and shut down ups to transfer the critical load to bypass mode and shut down the ups: 1. Transfer the critical load ...
Page 117
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-5 9.1.9 using the ups load off pushbutton a ups load off is initiated by the load off pushbutton from the main menu bar or the system controls menu bar. This pu...
Page 118
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-6 9.1.10 using the remote emergency power-off switch a ups emergency power-off is initiated by the repo pushbutton switch. In an emergency, you can use this swi...
Page 119
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-7 9.2 multiple module parallel operation 9.2.1 starting the parallel system in normal mode to start the parallel system: 1. Close all uninterruptible power modu...
Page 120
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-8 9.2.2 starting the parallel system in bypass mode if the inverter output of the upms is not available and the critical load needs to be energized: c a u t i o...
Page 121
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-9 9.2.4 transfer parallel system from bypass to normal mode to transfer the critical load to normal mode: 1. Press the controls pushbutton on the main menu bar ...
Page 122
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-10 3. Close the upm input feeder circuit breaker. 4. If the upm is dual feed, close the upm bypass input feeder circuit breaker. 5. Press the controls pushbutto...
Page 123
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-11 7. To shut down the last upm, press the repo pushbutton switch. See “using the parallel system remote emergency power-off switch” in paragraph 9.2.9. The inp...
Page 124
Ups operating instructions eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 9-12 9.2.9 using the parallel system remote emergency power-off switch a parallel system emergency power-off is initiated by the repo pushbutton switch. In an eme...
Page 125
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 10-1 chapter 10 using features and options the many standard features of your ups system provide consistent, economical, and dependable power protection. In addition, you can add available ...
Page 126
Using features and options eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 10-2 10.3 optional remote monitor panel as an option, a remote monitor panel (rmp) can be installed to monitor the operation of the ups system from virtually any ...
Page 127
Using features and options eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 10-3 the rmp contains a local horn and the backlit status indicators listed in table 10‐1. Table 10‐1. Rmp status indicators system normal the ups is energized (e...
Page 128
Using features and options eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 10-4 10.4 relay interface module an optional relay interface modulel (rim) uses relay contact closures to indicate the operating status and alarm condition of the...
Page 129
Using features and options eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 10-5 10.5 supervisory contact module an optional supervisory contact module (scm) establishes an interface between the ups system and the customer's monitor. This...
Page 130
Using features and options eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 10-6 this page intentionally left blank..
Page 131
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-1 chapter 11 responding to system events 11.1 general when the ups system is running in normal mode, it continually monitors itself and the incoming utility power. In battery or bypass m...
Page 132
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-2 table 11‐1. Alarms message horn phone relay log* indication battery totally discharged 1 no 1 ha shutdown imminent battery totally discharged ok off no 1 ha...
Page 133
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-3 table 11‐1. Alarms (continued) indication log* relay phone horn message configuration error 1 no 1 ha service required configuration error ok off no 1 ha co...
Page 134
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-4 table 11‐1. Alarms (continued) indication log* relay phone horn message l3 overload (high level) 1 no 1 ha user action required l3 overload (high level) ok ...
Page 135
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-5 table 11‐2. Notices message horn phone relay log* indication automatic shutdown pending 1 no no a information only automatic shutdown pending ok off no no a...
Page 136
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-6 table 11‐2. Notices (continued) indication log* relay phone horn message input ac over voltage 1 no no ha information only input ac over voltage ok off no n...
Page 137
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-7 table 11‐2. Notices (continued) indication log* relay phone horn message output ac under voltage 1 no no ha information only output ac under voltage ok off ...
Page 138
Responding to system events eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 11-8 table 11‐3. Status (continued) indication log* relay phone horn message modem connection established no no no h user status outgoing modem call started no n...
Page 139
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 12-1 chapter 12 communication this chapter describes the communication features of the powerware 9390 100–160 kva ups and provides information about connecting hardware and using terminal m...
Page 140
Communication eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 12-2 relay interface card modbus card multi-server card modem card single-port card connectups-x web/snmp card power xpert ® gateway card figure 12‐1. Optional x-slot cards 12...
Page 141
Communication eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 12-3 remote notification differs from the basic terminal mode with the addition the following functions: s call answer – the call answer function allows the user to call into ...
Page 142
Communication eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 12-4 this page intentionally left blank..
Page 143
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 13-1 chapter 13 maintaining the ups system the components inside the ups cabinet are secured to a sturdy metal frame that is supported by the ups magnetics. This design allows authorized se...
Page 144
Maintaining the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 13-2 13.2 performing preventive maintenance the ups system requires very little preventive maintenance. However, inspect the ups system periodically to verify tha...
Page 145
Maintaining the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 13-3 13.2.4 battery maintenance note do not disconnect the batteries while the ups is in battery mode. Contact your eaton service representative for battery maint...
Page 146
Maintaining the ups system eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 13-4 this page intentionally left blank..
Page 147
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 14-1 chapter 14 product specifications the following sections detail the input, output, environmental, and battery specifications for the ups. 14.1 model numbers the ups systems are housed ...
Page 148
Product specifications eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 14-2 14.2.2 ups system output ups output capacity 100% rated current output voltage regulation 1% (10% to 100% load) output voltage adjustment (nominal +/–3%) 208 vac...
Page 149
Product specifications eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 14-3 14.3 multiple module parallel specifications 14.3.1 upm input same as single module. 14.3.2 upm output same as single module. 14.3.3 environmental same as single...
Page 150
Product specifications eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 14-4 this page intentionally left blank..
Page 151
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 15-1 chapter 15 warranty limited factory warranty three‐phase powerware ® ups products warrantor: the warrantor for the limited warranties set forth herein is eaton electrical inc., a delaw...
Page 152
Warranty eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com 15-2.
Page 153
Eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-1 appendix a 1- installation information the information in this appendix is helpful during the planning and installation of the ups system. This appendix contains the following drawings:...
Page 154
Battery cabinet ups cabinet 164201604-1 1 of 1 typical powerware 9390 ups system 091505 a description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-2.
Page 155
164201604-2 1 of 2 physical features and requirements 011509 c description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-3 1. The ups equipment operating environment must m...
Page 156
2 of 2 physical features and requirements 011509 c 164201604-2 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-4 7. The basic environmental requirements for opera...
Page 157
1 of 1 ups system oneline configurations 011509 c 164201604-3 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-5 table d. Ups system oneline configurations oneline...
Page 158
Battery breaker 1 of 6 ups system oneline drawing 011509 d 164201604-4 description: date: drawing no: sheet: revision: ups cabinet inverter rectifier static switch remote epo building alarms ac output to critical load ac input to ups rectifier 3 wire a-b-c ac input to bypass 3 or 4 wire a-b-c rotati...
Page 159
E1, e2, e3 battery breaker ups system oneline drawing 011509 f 164201604-4 description: date: drawing no: sheet: revision: ups cabinet inverter rectifier static switch remote epo building alarms ac output to critical load ac input to ups rectifier 3 wire a-b-c ac input to bypass 3 or 4 wire a-b-c ro...
Page 160
3 of 6 ups system oneline drawing 091505 a 164201604-4 description: date: drawing no: sheet: revision: maintenance bypass panel (provided by others) output from ups mib to ups input mib: maintenance isolation breaker mbp: maintenance bypass breaker mbp backfeed k5 k3 static switch ac input battery b...
Page 161
Ups system oneline drawing 091505 a description: date: drawing no: sheet: revision: output to critical load battery cabinet battery breaker e4. E5 e9 e10 e11 e12 fuse k5 static switch fuse k3 fuse battery converter rectifier inverter k1 upm 1 e1 e2 e3 e6e 7e8 e12 a b see note 2 module tie cabinet (o...
Page 162
Ups system oneline drawing 091505 a typical parallel system (2+1 and 3+0 configurations) 5 of 6 164201604-4 note: 1. Upm and system bypass input feeds must come from the same source. 2. Remove jumper for dual‐feed. 3. See note 27 on page a-21 for neutral bonding instructions. Description: date: draw...
Page 163
Ups system oneline drawing 091505 a typical parallel system (3+1 and 4+0 configurations) 6 of 6 164201604-4 note: 1. Upm and system bypass input feeds must come from the same source. 2. Remove jumper for dual‐feed. 3. See note 27 on page a-21 for neutral bonding instructions. Description: date: draw...
Page 164
1 of 15 power wiring installation notes 011509 d 164201604-5 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-12 table e. Input/output ratings & external wiring re...
Page 165
Power wiring installation notes 011509 d 164201604-5 2 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-13 table f. Input/output ratings & external wiring re...
Page 166
Power wiring installation notes 011509 d 164201604-5 3 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-14 table g. Input/output ratings & external wiring re...
Page 167
Power wiring installation notes 011509 d 164201604-5 note: customer ground can be run in any conduit listed in table j. 4 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Po...
Page 168
Power wiring installation notes 011509 c 164201604-5 note: customer ground can be run in any conduit listed in table j. 5 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Po...
Page 169
Power wiring installation notes 091505 a 164201604-5 6 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-17 11. Per nec article 300‐20(a), all three‐phase con...
Page 170
Power wiring installation notes c 164201604-5 011509 7 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-18 table j. Power cable conduit requirements (cont'd)...
Page 171
Installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-19 14. External overcurrent protection is not provided by this product, but is required by codes. Refer to table e through table g for wiring requirements. If an ...
Page 172
Power wiring installation notes 011509 c 164201604-5 9 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-20 19. There is no dc disconnect device within the up...
Page 173
Power wiring installation notes 032406 b 164201604-5 10 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-21 25. Parallel system upm and system bypass input f...
Page 174
Power wiring installation notes 011509 c 164201604-5 11 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-22 28. See drawing 164201604-7 for upm terminal loca...
Page 175
Power wiring installation notes 011509 d 164201604-5 12 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-23 table o. Input/output ratings for powerware 9390-...
Page 176
Power wiring installation notes 011509 d 164201604-5 13 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-24 table p. Input/output ratings for powerware 9390-...
Page 177
Power wiring installation notes 011509 d 164201604-5 14 of 15 description: date: drawing no: sheet: revision: installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-25 table q. Input/output ratings for powerware 9390-...
Page 178
Power wiring installation notes 091505 a 164201604-5 description: date: drawing no: sheet: revision: upm 2 battery bypass inputs to upms upm 1 battery upm 3 battery upm 4 battery outputs from upms 1a (30) 2a (35) 3a (40) 4a (45) 1b (25) 2b (20) 3b (15) 4b (10) 15 of 15 note: wire lengths in the diag...
Page 179
1 of 2 conduit and wire entry locations 091505 a 164201604-6 remove debris shield covering exhaust grill before operating system. Top entry conduit landing for ac input and output, dc input, dc control, and interface connections. (remove panel to drill or punch conduit holes.) description: date: dra...
Page 180
2 of 2 conduit and wire entry locations 091505 a left side view description: date: drawing no: sheet: revision: right side view inter‐cabinet wiring access knockouts. Remove knockouts, as required, to route wires between cabinets. (install nylon grommet after removal of knockouts.) inside panels int...
Page 181
1 of 4 ups power terminal locations 011509 d 164201604-7 note: metal shields covering wiring terminals must be removed or opened to gain access to terminals. Ground terminals ac input to ups rectifier and bypass (a, b, c, n) description: date: drawing no: sheet: revision: dc input from battery to up...
Page 182
2 of 4 ups power terminal locations 011509 c 164201604-7 terminal detail phase a (e9) phase b (e10) phase c (e11) description: date: drawing no: sheet: revision: ac output to critical load dc input from battery + (e4) - (e5) phase a (e1) phase b (e2) phase c (e3) phase a (e6) phase b (e7) phase c (e...
Page 183
3 of 4 ups power terminal locations 011509 d 164201604-7 ground terminals wireway for top entry power wiring note: metal shields covering wiring terminals must be removed or opened to gain access to terminals. Description: date: drawing no: sheet: revision: ac input to ups rectifier and bypass (a, b...
Page 184
4 of 4 ups power terminal locations 011509 c 164201604-7 description: date: drawing no: sheet: revision: rectifier input terminals bypass input terminals dc input from battery + (e4) - (e5) ac input to ups bypass (dual input) ac input to ups rectifier and bypass (single input) ac input to ups rectif...
Page 185
1 of 15 interface wiring installation notes and terminal locations 032406 b description: date: drawing no: sheet: revision: 164201604-8 installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-33 1. Use class 1 wiring m...
Page 186
082108 c 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations tb1 tb2 x-slots x-slot communication bay wireway for bottom entry interface wiring note: metal shields covering wiring terminals must be removed or opened to gain access to...
Page 187
Note: 1. All building alarm inputs require an isolated normally‐open or normally‐closed contact or switch (rated at 24 vdc, 20 ma minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either normally‐open or normally‐closed cont...
Page 188
091505 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations note: 1. All building alarm inputs require an isolated normally‐open or normally‐closed contact or switch (rated at 24 vdc, 20 ma minimum) connected between the alarm input...
Page 189
011509 c 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 5 of 15 installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-37 9. The ups dc uvr trip ...
Page 190
032406 b 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 6 of 15 installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-38 11. The remote epo feat...
Page 191
032406 b 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 7 of 15 installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-39 14. Wire the maintenanc...
Page 192
091505 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations 8 of 15 installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-40 15. 120 vac should be p...
Page 193
091505 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations powerware hot sync can bridge card connections for parallel system control connections for rmp, rim, or scm building alarm 2 replacement j3 note: all interface wiring is to...
Page 194
091505 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations note: this drawing is for parallel wiring purposes and is not a floor layout plan. Upms can be placed in any physical order. Parallel system can and backup control (pull ch...
Page 195
Installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-43 building alarm pull chain wiring terminations from upm 1 to upm 2 to upm 3 (if installed) to upm 4 (if installed) tb2–1 (ba 2) tb2–1 (ba 2) tb2–1 (ba 2) tb2–1 ...
Page 196
Installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-44 082108 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations parallel system backup control ...
Page 197
Installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-45 parallel interface wire charts using customer–supplied mob dual aux contacts building alarm pull chain wiring terminations all modules from upm 1 to upm 2 to u...
Page 198
091505 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations terminal tb–1 signal connections from the ups ground terminal rim and rmp terminal locations terminal tb–3 120 vac power scm terminal locations ground terminal terminal tb–...
Page 199
091505 a 164201604-8 description: date: drawing no: sheet: revision: interface wiring installation notes and terminal locations ups can card j3 120 vac from critical bus line neutral twisted pair ground terminal rmp, rim, or scm 15 of 15 installation information eaton powerware ® 9390 ups (100–160 k...
Page 200
1 of 4 ups cabinet dimensions 091505 a 164201604-9 front view right side view description: date: drawing no: sheet: revision: dimensions are in millimeters [inches] installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com...
Page 201
Ups cabinet dimensions 091505 a 164201604-9 top view bottom view dimensions are in millimeters [inches] 2 of 4 description: date: drawing no: sheet: revision: left side left side right side right side front front installation information eaton powerware ® 9390 ups (100–160 kva) installation and oper...
Page 202
Ups cabinet dimensions 091505 a 164201604-9 bottom view with optional floor mounting brackets dimensions are in millimeters [inches] 3 of 4 description: date: drawing no: sheet: revision: left side right side front installation information eaton powerware ® 9390 ups (100–160 kva) installation and op...
Page 203
Ups cabinet dimensions 091505 a 164201604-9 bottom view with optional seismic mounting brackets dimensions are in millimeters [inches] 4 of 4 description: date: drawing no: sheet: revision: seismic kit installation left side right side front installation information eaton powerware ® 9390 ups (100–1...
Page 204
1 of 1 optional powerware remote emergency power‐off 082108 b 164201604-10 description: date: drawing no: sheet: revision: dimensions are in millimeters [inches] note: 1. Conduit and wiring between the remote emergency power‐off (repo) and the ups to be supplied by the customer. 2. Maximum distance ...
Page 205
1 of 1 optional remote monitor panel (rmp) 091505 a 164201604-11 description: date: drawing no: sheet: revision: knockouts provided on five surfaces flush mount use #10 pan head screws (mount with vent holes facing up) surface mount use #10 pan head screws (for hanging) (mount with vent holes facing...
Page 206
1 of 2 optional relay interface module (rim) 091505 a 164201604-12 description: date: drawing no: sheet: revision: knockouts provided on five surfaces flush mount use #10 pan head screws (mount with vent holes facing up) surface mount use #10 pan head screws (for hanging) (mount with vent holes faci...
Page 207
Optional relay interface module (rim) 091505 a description: date: drawing no: sheet: revision: 164201604-12 2 of 2 15–pin d–sub connectors installation information eaton powerware ® 9390 ups (100–160 kva) installation and operation manual s 164201604 rev d www.Powerware.Com a-55.
Page 208
1 of 1 optional supervisory contact module (scm) 091505 a 164201604-13 description: date: drawing no: sheet: revision: knockouts provided on five surfaces flush mount use # 10 pan head screws (mount with vent holes facing up) surface mount use # 10 pan head screws (for hanging) (mount with vent hole...
Page 210
*164201604d* 164201604 d.