    Powerware 9390 ups sidecar installation and operation manual ® for use with 40–80 kva and 100–160 kva ups models.

  • Page 2

    Important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. Please read all instructions before operating the equipment and save this manual for future reference. Consignes de s...

  • Page 3: Table Of Contents

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com i table of contents 1 introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 co...

  • Page 4

    Table of contents eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com ii 4.5 ups sidecar operation – maintenance bypass configuration 4-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Page 5: List Of Figures

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com iii list of figures figure 1-1. Powerware 9390 ups (40–80 kva) with ups sidecar 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-2....

  • Page 6

    List of figures eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com iv this page intentionally left blank..

  • Page 7: Chapter 1

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-1 chapter 1 introduction the eaton ® powerware ® 9390 ups sidecar is designed for use with the powerware 9390 80 kva 208/208v and 480/480v and 160 kva 480/480v three-phase uninterruptible power...

  • Page 8

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-2 figure 1-1. Powerware 9390 ups (40–80 kva) with ups sidecar.

  • Page 9

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-3 figure 1-2. Powerware 9390 ups (100–160 kva) with ups sidecar.

  • Page 10

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-4 1.2 using this manual this manual describes how to install and operate the powerware 9390 ups sidecar. Read and understand the procedures described in this manual to ensure troub...

  • Page 11

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-5 1.3 conventions used in this manual this manual uses these type conventions: s bold type highlights important concepts in discussions, key terms in procedures, and menu options. ...

  • Page 12

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-6 1.4 safety warnings important safety instructions save these instructions this manual contains important instructions that should be followed during installation and maintenance ...

  • Page 13

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-7 1.6 getting help if help is needed with any of the following: s scheduling initial startup s regional locations and telephone numbers s a question about any of the information in...

  • Page 14

    Introduction eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-8 this page intentionally left blank..

  • Page 15: Section I

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-1 section i installation.

  • Page 16

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 1-2.

  • Page 17: Chapter 2

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-1 chapter 2 installing the ups sidecar 2.1 installation plan and unpacking refer to the applicable powerware 9390 installation and operation manual, listed in paragraph 1.5, for installation pl...

  • Page 18

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-2 3. If not already removed, remove the screws securing the internal safety shield panel and remove the panel to gain access to the terminals. Note if a bypass input ...

  • Page 19

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-3 front panel front panel attaching screw ups sidecar ups cabinet figure 2-1. 80 kva ups with ups sidecar.

  • Page 20

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-4 2.4 ups sidecar installation – parallel redundant configuration the method used to install the ups sidecar depends on the type of installation being undertaken. The...

  • Page 21

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-5 1. Verify that the upm 1 is properly installed and secured. Refer to the applicable powerware 9390 installation and operation manual, listed in paragraph 1.5, for i...

  • Page 22

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-6 17. Align the holes in the other end of the bracket with the holes in the bottom right-hand side of the ups sidecar attached to upm 1 (see figure 2-3). Secure the b...

  • Page 23

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-7 2.4.2 installing line-up-and-match parallel redundant power wiring note remove the ups sidecar top or bottom conduit landing plate to drill or punch conduit holes, ...

  • Page 24

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-8 2.4.3 standalone parallel redundant installation use this procedure to install separately located upms (see figure 2-4). Upm 1 has the sidecar installed. The ups si...

  • Page 25

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-9 2.4.4 installing standalone parallel redundant power wiring note remove the ups sidecar top or bottom conduit landing plate to drill or punch conduit holes, or remo...

  • Page 26

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-10 2.4.5 installing ups sidecar tb1 interface connections note when installing control wiring (such as pull chain and mob auxiliary contacts) to the ups sidecar inter...

  • Page 27

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-11 installation checklist - all conduits and cables are properly routed to the ups sidecar. - all power cables are properly sized and terminated. - ups sidecar auxili...

  • Page 28

    Installing the ups sidecar eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-12 notes _________________________________________________________________________ _________________________________________________________________________ _________...

  • Page 29: Section Ii

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-13 section ii operation.

  • Page 30

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 2-14.

  • Page 31: Chapter 3

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 3-1 chapter 3 understanding operation the ups sidecar can be configured for either maintenance bypass or parallel redundant operation. 3.1 maintenance bypass configuration 3.1.1 ups mode when the...

  • Page 32

    Understanding operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 3-2 3.1.2 maintenance bypass mode with ups sidecar an mbp is used to safely supply utility power to the critical load during periods of ups maintenance or repairs. The byp...

  • Page 33: Chapter 4

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-1 chapter 4 ups sidecar features, controls, and operation 4.1 ups sidecar standard features the ups sidecar has many standard features that provide cost-effective and consistently reliable powe...

  • Page 34

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-2 4.2.2 rectifier input breaker (rib) maintenance bypass configurations have an optional rib for dual-feed systems. The rib provides a single point...

  • Page 35

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-3 4.4 ups sidecar controls figure 4-1 through figure 4-8 identify and show the location of the controls on the powerware 9390 ups sidecar. Note rea...

  • Page 36

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-4 maintenance bypass switch (mbp) maintenance isolation switch (mis) interlock plate figure 4-1. Ups sidecar controls (bypass) – 40/20, 40/30, 40/4...

  • Page 37

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-5 optional bypass input breaker (bib) optional rectifier input breaker (rib) maintenance bypass switch (mbp) maintenance isolation switch (mis) int...

  • Page 38

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-6 maintenance bypass switch (mbp) maintenance isolation switch (mis) interlock plate figure 4-3. Ups sidecar controls (bypass) – 40/20, 40/30, 40/4...

  • Page 39

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-7 optional bypass input breaker (bib) optional rectifier input breaker (rib) maintenance bypass switch (mbp) maintenance isolation switch (mis) int...

  • Page 40

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-8 maintenance bypass switch (mbp) maintenance isolation switch (mis) figure 4-5. Ups sidecar controls (bypass) – 80/40, 80/50, 80/60, 80/80 kva, 20...

  • Page 41

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-9 optional bypass input breaker (bib) maintenance bypass switch (mbp) maintenance isolation switch (mis) optional rectifier input breaker (rib) fig...

  • Page 42

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-10 optional system load breaker (slb) module output breaker 2 (mob 2) module output breaker 1 (mob 1) figure 4-7. Ups sidecar controls (parallel re...

  • Page 43

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-11 optional system load breaker (slb) module output breaker 1 (mob 1) module output breaker 2 (mob 2) figure 4-8. Ups sidecar controls (parallel re...

  • Page 44

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-12 optional system load breaker (slb) module output breaker 1 (mob 1) module output breaker 2 (mob 2) figure 4-9. Ups sidecar controls (parallel re...

  • Page 45

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-13 4.5 ups sidecar operation – maintenance bypass configuration 4.5.1 using the ups when a ups sidecar is installed note before starting the ups wi...

  • Page 46

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-14 w a r n i n g power is present inside the ups cabinets. 6. Remove the screw securing the bottom of the ups sidecar front panel. Lift up the pane...

  • Page 47

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-15 4.6 ups sidecar operation – parallel redundant configuration 1. Remove the screw securing the bottom of the ups sidecar front panel. Lift up the...

  • Page 48

    Ups sidecar features, controls, and operation eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 4-16 this page intentionally left blank..

  • Page 49: Chapter 5

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 5-1 chapter 5 warranty limited factory warranty three-phase powerware ups products warrantor: the warrantor for the limited warranties set forth herein is eaton electrical inc., a delaware corpor...

  • Page 50

    Warranty eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com 5-2 this page intentionally left blank..

  • Page 51: Appendix A

    Eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-1 appendix a figur installation information the information in this appendix will help during the planning and installation of the ups sidecar. This appendix contains the following drawings: s ...

  • Page 52

    1 of 3 031505 a description: date: drawing no: sheet: revision: battery cabinet 80 kva ups cabinet 164201546---1 typical maintenance bypass or standalone parallel redundant configuration sidecar typical powerware 9390 ups system with ups sidecar installation information eaton powerware ® 9390 ups si...

  • Page 53

    031505 a description: date: drawing no: sheet: revision: 164201546---1 battery cabinet 160 kva ups cabinet typical powerware 9390 ups system with ups sidecar 2 of 3 typical maintenance bypass or standalone parallel redundant configuration sidecar installation information eaton powerware ® 9390 ups s...

  • Page 54

    031505 a description: date: drawing no: sheet: revision: 164201546---1 typical powerware 9390 ups system with ups sidecar battery cabinet 80 kva ups cabinet 1 80 kva ups cabinet 2 battery cabinet typical line-up-and-match parallel redundant configuration 3 of 3 sidecar installation information eaton...

  • Page 55

    Description: date: drawing no: sheet: revision: 164201546---2 1 of 1 physical features and requirements 031505 a installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-5 1. The ups sidecar equipment operating environment mu...

  • Page 56

    Ups sidecar oneline drawings 062806 c description: date: drawing no: sheet: revision: maintenance bypass configuration 80/40, 80/50, 80/60 and 80/80 kva, 208/208v and 480/480v with ups serial number seventh digit at “a” or “b” k1 k5 k3 ups sidecar maintenance bypass switch (mbp) ac input to bypass a...

  • Page 57

    Ups sidecar oneline drawings 062806 b description: date: drawing no: sheet: revision: maintenance bypass configuration 120/100 and 120/120 kva, 480/480v 160/100, 160/120, and 160/160 kva, 480/480v with ups serial number seventh digit at “a” k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance...

  • Page 58

    Ups sidecar oneline drawings 062806 b description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance bypass switch (mbp) ac input to bypass a maintenance isolation switch (mis) ac input to ups e1, e2, e3 single-feed jumper (remove for dual-feed) e6, e7, e...

  • Page 59

    Ups sidecar oneline drawings 062806 b description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance bypass switch (mbp) ac input to bypass a maintenance isolation switch (mis) ac input to ups e1, e2, e3 e6, e7, e8, e12 c ac output to critical load e4. E5...

  • Page 60

    Ups sidecar oneline drawings 062806 b maintenance bypass with bib configuration 40/20, 40/30, 40/40, 80/40, 80/50, 80/60, and 80/80 kva, 208/208v and 480/480v with ups serial number seventh digit at “a” or “b” description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups si...

  • Page 61

    Ups sidecar oneline drawings 062806 b maintenance bypass with bib configuration 120/100 and 120/120 kva, 480/480v 160/100, 160/120, and 160/160 kva, 480/480v with ups serial number seventh digit at “a” description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar ma...

  • Page 62

    Ups online oneline drawings 062806 b maintenance bypass with bib configuration 120/100 and 120/120 kva, 480/480v with ups serial number seventh digit at “b” or higher description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance bypass switch (mbp) ac in...

  • Page 63

    Ups sidecar oneline drawings 062806 b maintenance bypass with bib configuration 160/100, 160/120, and 160/160 kva, 480/480v with ups serial number seventh digit at “b” or higher description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance bypass switch ...

  • Page 64

    Ups sidecar oneline drawings 092107 c maintenance bypass with bib and rib 40/20, 40/30, 40/40, 208/208v, 120/100, 120/120 kva, 480/480v and 160/100, 160/120, 160/160 kva, 480/480v description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance bypass switc...

  • Page 65

    Ups sidecar oneline drawings 092107 c maintenance bypass with bib and rib 80/40, 80/50, 80/60, 80/80 kva, 480/480v, description: date: drawing no: sheet: revision: k1 k5 k3 powerware 9390 ups cabinet ups sidecar maintenance bypass switch (mbp) ac input to bypass b maintenance isolation switch (mis) ...

  • Page 66

    Description: date: drawing no: sheet: revision: 031505 a output to critical load e4. E5 fuse k5 static switch fuse k3 fuse battery converter rectifier inverter k1 upm 2 e1 e2 e3 e6 e7 e8 e12 a b see note 2 ups sidecar e4. E5 fuse k5 static switch fuse k3 fuse battery converter rectifier inverter k1 ...

  • Page 67

    1 of 10 power wiring installation notes 092107 description: date: drawing no: sheet: revision: d 164201546---4 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-17 table b . Input/output ratings & external wiring requi...

  • Page 68

    Power wiring installation notes 061507 description: date: drawing no: sheet: revision: d 164201546---4 2 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-18 table c . Input/output ratings & external wiring requi...

  • Page 69

    Power wiring installation notes 092107 description: date: drawing no: sheet: revision: d 164201546---4 3 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-19 table d. Input/output ratings & external wiring requir...

  • Page 70

    Power wiring installation notes 061507 description: date: drawing no: sheet: revision: c 164201546---4 4 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-20 read and understand the following notes while planning...

  • Page 71

    Power wiring installation notes 092107 description: date: drawing no: sheet: revision: d 164201546---4 5 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-21 table f. Ups sidecar maintenance bypass power cable te...

  • Page 72

    Power wiring installation notes 092107 description: date: drawing no: sheet: revision: d 164201546---4 6 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-22 table i. Ups sidecar maintenance bypass power cable te...

  • Page 73

    Power wiring installation notes 092107 description: date: drawing no: sheet: revision: e 164201546---4 7 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-23 table k. Ups sidecar 1+1 parallel redundant power cabl...

  • Page 74

    Power wiring installation notes 092107 description: date: drawing no: sheet: revision: e 164201546---4 8 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-24 table m. Ups sidecar 1+1 parallel redundant power cabl...

  • Page 75

    Power wiring installation notes 062206 description: date: drawing no: sheet: revision: c 164201546---4 9 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-25 15. Table o lists the maximum rating for rectifier inp...

  • Page 76

    Power wiring installation notes 063006 b 164201546---4 description: date: drawing no: sheet: revision: 10 of 10 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-26 16. The mis and slb breakers on the 80 kva, 120 kva, ...

  • Page 77

    1 of 3 conduit and wire entry locations 031505 a 164201546---5 description: date: drawing no: sheet: revision: top view bottom view ups sidecar bottom entry conduit landing for ac input and output. (remove panel to drill or punch conduit holes.) ups sidecar top entry conduit landing for ac input and...

  • Page 78

    Conduit and wire entry locations 031505 a description: date: drawing no: sheet: revision: top view bottom view ups sidecar bottom entry conduit landing for ac input and output. (remove panel to drill or punch conduit holes.) ups sidecar top entry conduit landing for ac input and output. (remove pane...

  • Page 79

    Conduit and wire entry locations 031505 a description: date: drawing no: sheet: revision: 164201546---5 inter-cabinet wiring access knockouts. Remove knockouts, as required, to route wires between cabinets. (install nylon grommet after removal of knockouts.) inside panel 3 of 3 hanger bracket locati...

  • Page 80

    1 of 34 power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to gain access to terminals. Maintenance bypass switch (mbp) (see sheet 21 of 34 for details) 40/20, 40/30, 40/40 kva, 480/480v mainten...

  • Page 81

    Power terminal locations 092107 d description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to gain access to terminals. 164201546---6 2 of 34 maintenance bypass switch (mbp) (see sheet 21 of 34 for details) 40/20, 40/30, 40/40 kva, 480/480v mainten...

  • Page 82

    Power terminal locations 092107 d description: date: drawing no: sheet: revision: note 1. Metal shields covering wiring terminals must be removed to access terminals. 2. 80/40 must be wired as 80/50. 164201546---6 40/20, 40/30, 40/40 kva, 208/208v and 80/40, 80/50, 80/60, 80/80 kva, 480/480v mainten...

  • Page 83

    Power terminal locations 092107 d description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 120/100, 120/120 kva, 480/480v maintenance bypass configuration maintenance bypass switch (mbp) (see sheet 24 of 34 for de...

  • Page 84

    Power terminal locations 092107 d description: date: drawing no: sheet: revision: note 1. Metal shields covering wiring terminals must be removed to access terminals. 2. 80/40 must be wired as 80/50. 164201546---6 40/20. 40/30, 40/40 kva, 208/208v and 80/40, 80/50, 80/60, 80/80 kva, 480/480v mainten...

  • Page 85

    Power terminal locations 062806 c description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 120/100, 120/120 kva, 480/480v maintenance bypass configuration with optional bib maintenance bypass switch (mbp) maintena...

  • Page 86

    Power terminal locations 092107 d description: date: drawing no: sheet: revision: 164201546---6 maintenance bypass switch (mbp) maintenance isolation switch (mis) (see sheet 26 of 34 for details) ac output to critical load (a, b, c) maintenance bypass configuration with bib and rib options 7 of 34 4...

  • Page 87

    Power terminal locations 062806 c description: date: drawing no: sheet: revision: 164201546---6 maintenance bypass switch (mbp) maintenance isolation switch (mis) (see sheet 25 of 34 for details) ac output to critical load (a, b, c) maintenance bypass configuration with bib and rib options 8 of 34 1...

  • Page 88

    Power terminal locations 062806 c description: date: drawing no: sheet: revision: 164201546---6 maintenance bypass switch (mbp) (see sheet 27 of 34 for details) maintenance isolation switch (mis) (see sheet 27 of 34 for details) ac output to critical load (a, b, c) ac input to bypass (a, b, c) maint...

  • Page 89

    Power terminal locations 062806 c description: date: drawing no: sheet: revision: 164201546---6 maintenance bypass switch (mbp) (see sheet 28 of 34 for details) maintenance isolation switch (mis) bypass input breaker (bib) (optional) (see sheet 27 of 34 for details) ac output to critical load (a, b,...

  • Page 90

    Power terminal locations 092107 e description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 module output breaker 2 (mob 2) (see sheet 29 of 34 for details) 40/20, 40/30, 40/40 kva 480/480v parallel redundant confi...

  • Page 91

    Power terminal locations 092107 e description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 module output breaker 2 (mob 2) (see sheet 29 of 34 for details) 40/20, 40/30, 40/40 kva 480/480v parallel redundant confi...

  • Page 92

    Power terminal locations 092107 e description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 13 of 34 40/20, 40/30, 40/40 kva, 208/208v parallel redundant configuration (see sheet 31 of 34 for details) module output...

  • Page 93

    Power terminal locations 092107 e description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 14 of 34 80/40, 80/50, 80/60, 80/80 kva, 480/480v parallel redundant configuration (see sheet 31 of 34 for details) module...

  • Page 94

    Power terminal locations 063006 d description: date: drawing no: sheet: revision: note metal shields covering wiring terminals must be removed to access terminals. 164201546---6 15 of 34 120/100, 120/120 kva, 480/480v parallel redundant configuration (see sheet 32 of 34 for details) module output br...

  • Page 95

    Power terminal locations 092107 e description: date: drawing no: sheet: revision: 164201546---6 (see sheet 31 of 34 for details) 40/20, 40/30, 40/40 kva, 208/208v parallel redundant configuration w/slb module output breaker 1 (mob 1) ac input from upm 2 (a, b, c) neutral ground module output breaker...

  • Page 96

    Power terminal locations 061507 e description: date: drawing no: sheet: revision: 164201546---6 (see sheet 31 of 34 for details) 80/40, 80/50, 80/60, 80/80 kva, 480/480v parallel redundant configuration w/slb module output breaker 1 (mob 1) ac input from upm 2 (a, b, c) neutral ground module output ...

  • Page 97

    Power terminal locations 063006 e description: date: drawing no: sheet: revision: 164201546---6 (see sheet 32 of 34 for details) 120/100, 120/120 kva, 480/480v parallel redundant configuration module output breaker 1 (mob 1) ac input from upm 2 (a, b, c) neutral ground module output breaker 2 (mob 2...

  • Page 98

    Power terminal locations 063006 d description: date: drawing no: sheet: revision: 164201546---6 (see sheet 33 of 34 for details) 80/40, 80/50, 80/60, 80/80 kva, 208/208v and 160/100, 160/120, 160/160 kva, 480/480v parallel redundant configuration module output breaker 1 (mob 1) (see sheet 33 of 34 f...

  • Page 99

    Power terminal locations 063006 d description: date: drawing no: sheet: revision: 164201546---6 (see sheet 33 of 34 for details) parallel redundant configuration with slb module output breaker 1 (mob 1) (see sheet 34 of 34 for details) ac output to critical load (a, b, c) ac input from upm 2 (a, b, ...

  • Page 100

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 480/480v ups sidecar maintenance bypass configuration input and load output terminal detail ac input to bypass phase c phase b phase a ac output to critical load phase c phase b p...

  • Page 101

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 480/480v ups sidecar maintenance bypass configuration rectifier input terminal detail ac input to ups rectifier phase c phase b phase a rib 22 of 34 installation information eaton...

  • Page 102

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 208/208v and 80/40, 80/50, 80/60, 80/80 kva, 480/480v maintenance bypass configuration input and load output terminal detail ac input to bypass without bib phase c phase b phase a...

  • Page 103

    Power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 120/100, 120/120 kva, 480/480v maintenance bypass configuration input and load output terminal detail ac input to bypass phase c phase b phase a mbp ac output to critical load phase a 24 of 34 tb phase b ...

  • Page 104

    Power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 120/100, 120/120 kva, 480/480v maintenance bypass configuration input and load output terminal detail ac input to ups rectifier phase c phase b phase a rib ac output to critical load phase a 25 of 34 tb p...

  • Page 105

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 208/208v and 80/40, 80/50, 80/60, 80/80 kva, 480/480v ups sidecar maintenance bypass configuration rectifier and bypass input terminal detail 26 of 34 ac output to critical load p...

  • Page 106

    Power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 80/40, 80/50, 80/60, 80/80 kva, 208/208v and 160/100, 160/120, 160/160 kva, 480/480v ups sidecar maintenance bypass configuration rectifier and bypass input terminal detail ac input to bypass phase c phas...

  • Page 107

    Ac input to bypass phase c phase b phase a bib power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 80/40, 80/50, 80/60, 80/80 kva, 208/208v and 160/100, 160/120, 160/160 kva, 480/480v ups sidecar maintenance bypass configuration rectifier and bypass input ...

  • Page 108

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 480/480v ups sidecar parallel redundant configuration mob input and load output terminal detail phase c phase b phase a ac output terminal block ac output to critical load ac inpu...

  • Page 109

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 208/208v and 40/20, 40/30, 40/40 kva, 480/480v and 80/40, 80/50, 80/60, 80/80 kva, 480/480v and 120/100, 120/120 kva, 480/480v ups sidecar parallel redundant configuration slb out...

  • Page 110

    Power terminal locations 092107 d 164201546---6 description: date: drawing no: sheet: revision: 40/20, 40/30, 40/40 kva, 208/208v and 80/40, 80/50, 80/60, 80/80 kva, 480/480v ups sidecar parallel redundant configuration mob input and load output terminal detail 31 of 34 ac output to critical load ph...

  • Page 111

    Ac input from upm 2 phase c phase b phase a mob 2 power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 120/100, 120/120 kva, 480/480v ups sidecar parallel redundant configuration mob input and load output terminal detail 32 of 34 ac output to critical load ...

  • Page 112

    Power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 80/40, 80/50, 80/60, 80/80 kva, 208/208v and 160/100, 160/120, 160/160 kva, 480/480v ups sidecar parallel redundant configuration terminal detail mob 1 33 of 34 mob 2 phase a ac input from upm 2 phase c p...

  • Page 113

    Power terminal locations 062806 c 164201546---6 description: date: drawing no: sheet: revision: 80/40, 80/50, 80/60, 80/80 kva, 208/208v and 160/100, 160/120, 160/160 kva, 480/480v ups sidecar parallel redundant configuration slb output terminal detail phase c phase b phase a slb ac output to critic...

  • Page 114

    1 of 4 interface and control wiring installation notes and terminal locations 063006 d description: date: drawing no: sheet: revision: 164201546---7 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-64 1. Use class 1 w...

  • Page 115

    063006 d description: date: drawing no: sheet: revision: ups sidecar terminal tb1 for parallel redundant configurations 1 10 tb1 not used not used interface and control wiring installation notes and terminal locations note 1. Alarm displays as building alarm 2 on the ups control panel display screen...

  • Page 116

    Installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-66 backup control (pull chain) wiring terminations from to upm 1 tb2–1 (bldg alm 2) ups sidecar tb1–5 (mob 1 aux 2 no) upm 2 tb2–1 (bldg alm 2) ups sidecar tb1–9 (mob 2...

  • Page 117

    Installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-67 module output breaker monitoring wiring terminations from to upm 1 can bridge card j3–1 (bldg alm) ups sidecar tb1–3 (mob 1 aux 1 nc) upm 1 can bridge card j3–2 (bld...

  • Page 118

    1 of 4 ups sidecar dimensions 092107 b 164201546---8 description: date: drawing no: sheet: revision: front view right side view dimensions are in millimeters [inches] 40 kva and 80 kva ups with sidecar installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 16...

  • Page 119

    Ups sidecar dimensions 092107 b 164201546---8 description: date: drawing no: sheet: revision: top view dimensions are in millimeters [inches] bottom view 40 kva and 80 kva ups with sidecar 2 of 4 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 16420158...

  • Page 120

    Ups sidecar dimensions 031505 a description: date: drawing no: sheet: revision: front view right side view dimensions are in millimeters [inches] 120 kva and 160 kva ups with sidecar 164201546---8 3 of 4 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s ...

  • Page 121

    Ups sidecar dimensions 031505 a 164201546---8 description: date: drawing no: sheet: revision: top view dimensions are in millimeters [inches] bottom view 120 kva and 160 kva ups with sidecar 4 of 4 installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201...

  • Page 122

    Installation information eaton powerware ® 9390 ups sidecar installation and operation manual s 164201586 rev e www.Powerware.Com a-72 this page intentionally left blank..

  • Page 124

    *164201586e* 164201586 e.