Eberspächer B3LC User Manual - page 21
21
Installation
3
Permissible pipe lengths for petrol heater
Intake side
Pressure side
a = max. 2 m
b = max. 4 m
Permissible pipe lengths for diesel heater
Intake side
Pressure side
a = max. 5 m
• For suction pipe di= Ø 2 mm
b = max. 6 m
• For suction pipe di= Ø 5 mm
b = max. 10 m
Fuel feed point with tank connection – ascending pipe, integrated in the vehicle tank
or in the tank fitting
Tank connection for metal tank
– di = Ø 2 mm, da = Ø 6 mm
Tank connection for tank fitting
– di = Ø 2 mm, da = Ø 4 mm
Dosing pump
Fuel filter – only required for contaminated fuel.
Fuel hose, 5 x 3 (di = Ø 5 mm)
Fuel pipe, 6 x 2 (di = Ø 2 mm)
Fuel pipe, 4 x 1 (di = Ø 2 mm)
Fuel hose, 3.5 x 3 (di = Ø 3.5 mm),
ca. 50 mm long
Fuel hose, 5 x 3 (di = Ø 5 mm), ca. 50 mm long
Fuel pipe, 4 x 1.25 (di = Ø 1.5 mm)
Connection fitting, da = Ø 4 mm
Fuel supply
Items
are included in the “tank connection“
setup kit, see additional parts catalogue for Order No.
Item
is not included in the “installation set“, see
additional parts catalogue for Order No.
Caution!
Safety instructions for the fuel supply
• The fuel must not be conveyed by gravity or
overpressure in the fuel tank.
• Withdrawel of the fuel after the vehicle’s fuel pump
is not allowed.
• When the pressure in the fuel pipe is more than 0.2
bar to max. 4.0 bar, use a pressure reducer (order
no. 22 1000 20 08 00) or a separate tank
connection.
• When the pressure in the fuel pipe is more than 4.0
bar or there is a non-return valve in the return pipe
(in the tank), a separate tank connection must be
used.
• When using a T-piece in a plastic pipe, always use
support sleeves in the plastic. Connect the T-piece
and the plastic pipe with corresponding fuel hoses
and secure with hose clips.