Echoflex RTS-1T-nW Installation Manual - Light Level Test Table
6
releasedthetestmodebutton,placethesensorunderalampwithatleast100foot-
candles (1000 lux) for 1 hour before retrying.
LIGHT LEVEL TEST TABLE
The green LED will blink according to the energy produced by the solar cell
Blinks Lux
Foot Candles Time to Fully Charge
Discharge time
0,1
<15
<1.4
belowoperatinglevel
n/a
2
15-50
1.4-4.6
minoperatinglevel
n/a
3
50-100
4.6-9.3
24hourstofullcharge 100 hours
4
100-200
9.3 - 18.6
12 hours to full charge 150 hours
5
200-400
18.6 - 37.2
6 hours to full charge
200 hours
The time to fully charge is based on the storage capacitor charging from a
non-operationalcondition.Dischargetimeindicateshowlongafullycharged
sensor will operate in the dark. The test will repeat every 2 seconds and run for
adurationof100seconds.Youmayquitthetestatanytimebypressingthetest
buttonfor6seconds.
Range Confirmation Test: provides visual feedback of the sensors signal
strengthbyalinkedreceiverwithrangeconfirmationcapability(only“Fseries”
controllershaverangeconfirmationability).Oneandonlyonereceivercanbe
linkedtothesensorforproperoperationofthetest.(disablerepeatersinrange
forpropertestoperation).
1. ToenterRangeConfirmationTestmode,pressandholdtheoccupancy/
testbuttonfor6seconds.Thegreenledwillbegintoblink.
2. Aquickpressandreleaseofthebuttonatthispointwillallowyoutoselect
betweenlightleveltest(greenLED)andrangeconfirmationtest(amber).
When the amber LED is blinking, go to step 3. (If the 3 LEDs fail to blink
during this test, place under a lamp with at least 100 fc (1000 lux) for 1
hour before retrying.)
3. Pressandholdthetestbuttonagainfor6secondstoselectRange
ConfirmationTest.
All three LED’s can blink in this test mode when the sensor transmits or receives
a Range Confirmation Telegram. The sensor will display the signal strength
status for 5 seconds, see table below.
RANGE CONFIRMATION TEST TABLE
LED
Signal Strength
Green
> -70 dbm
Amber
> -80 dbm
Red
<-80dbm
The test will repeat every 10 seconds and run for a duration of 3 minutes.
Youmayquitthetestatanytimebypressingtheoccupancy/testbuttonfor6
seconds.