Ecofires eko 2040 Installation And User Instructions Manual - page 4
INSTALLATION REQUIREMENTS
This appliance MUST NOT be installed into a room containing a bath or shower, or where steam maybe
present. The fire has been designed to fit into a purpose made builders’ opening meeting certain dimen-
sional requirements
.
The flue must have an effective height of at least three meters, as measured from the hearth to the top of
the flue. Any flue damper plates or restrictors should be removed and no other restriction fitted to the flue.
Where removal is not practical, the restriction must be fixed in the fully open position.
A natural draught flue system is required, and if previously used for solid fuel or oil burning, the flue and
chimney must be swept prior to appliance installation. The flue must be checked before installation by using
a smoke pellet or similar to ensure proper draw and that leakage is not evident at any joints. Repair and re-
test as necessary before the appliance is installed.
2.0
3.0
A. Opening height:
360mm Min / 470mm Max.
B. Opening width:
455mm Min / 545mm Max.
C. Opening depth: 355 mm Min.
‘A’
‘B’
‘C’
2
APPLIANCE DATA
Gas Group
G20 Natural Gas CAT I2H
Inlet Pressure
20 mbar (+/- 2.0mbar)
Max Energy Input (gross)
5.5 kW
Min Energy Input (gross)
3.5 kW
Pilot Energy Input (gross)
166 W
Setting Pressure (cold)
12.2 mbar (+/- 1.5mbar)
Main Injector Burner
Stereo size 77
Gas Inlet Connection
8mm Inlet Restrictor Elbow
Gas Control Valve
Dungs BM 733/Negabahn 6801
Ignition
Integral Piezo spark
Spark Gap
3.5 to 4.5mm
Weight
20 Kg
Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data
Badge, and is for decorative purposes.
©