Ecofires eko 2040 Installation And User Instructions Manual - page 8
OPERATING THE FIRE
The pilot is visible at the rear of the fuel bed. The control knob
is located on the right hand side of the appliance. Push in and
turn the control knob to the SPARK position, and hold there for
a few seconds.
Continue turning anti-clockwise through the spark click to the
PILOT light position, ensuring the pilot has lit. If not, return the
knob clockwise, and repeat.
When the pilot lights after the spark, keep the knob depressed
for approximately ten seconds. Now release the knob and the pilot should stay alight. If not, repeat ignition.
If the pilot is extinguished
during use
, wait three minutes before repeating the ignition procedure.
To achieve the HIGH setting, push the control knob in slightly and continue turning anti-clockwise to the
high position. The main burner should light after a few seconds. To decrease the setting to LOW, turn the
control knob clockwise to the low setting.
To turn to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to the
pilot position and release.
To turn the fire OFF, keep the knob pressed in, return to the off position and release.
A safety interlock prevents re-ignition of the pilot flame until the thermocouple has cooled sufficiently to
allow the magnetic valve unit to reset itself.
SPARK FAILURE
The gap between the spark electrode and the pilot should be 3.5 - 4.5mm to produce a good spark. There
should be no need to adjust this. If under any circumstances the electric spark fails, the pilot may be lit man-
ually by proceeding with the ignition sequence as previously described, and after turning the control knob
through the spark position, the knob should be held in and the pilot lit with a taper.
SETTING PRESSURE
Remove the screw from the pressure test point.
The pressure test point is situated on the front of the gas
control as shown and may be accessed by removing the
knob and the control plate.
The setting pressure should be in accordance with the
figures stated on page 2 of these instructions. The fire is
factory set to achieve these pressures, and any significant
variation could indicate a supply problem.
If the pressure is too high, the gas supply meter may be
set incorrectly. This should be checked with the fire run-
ning and if necessary reset by the gas supplier.
If the pressure is too low, then check the meter governor
pressure with the appliance running. If this is incorrect it will need to be reset by the gas supplier. If the set-
ting pressure is too low, but the meter pressure is acceptable, then a problem in the supply pipework is to
be suspected. This will be dirt and debris, kinked or inadequate size pipes, restriction in a fitting or solder
flashing across a joint. (NOTE: you will not get an accurate reading of the inlet pressure with a pressure
gauge on the end of the supply pipe - this is the static pressure in the system. You must use a T piece and
measure the supply pressure with the fire on High - the dynamic pressure). Refit and tighten the screw into
the pressure test point when the test is complete.
6
10.0
10.1
10.2
©
2009 Focal Point Fires plc.