9 |
P a g e
MODEL
ES50LVP
ES90LVP
DX Cooling Capacity (tons)
1 to 2
1.5 to 3.5
Power (Volts/Phase/Hz)
120/1/60
120/1/60
Cabinet Size W x D x H (in)
14 x 21 x 29
21 x 21 x 29
Supply Air Opening W x D (in)
11.8 X 17.8
18.8 x 17.8
Side Return Air Opening (in)
18.3 X 14.3
18.3 X 14.3
Recommended Filter Size (in)
16 x 20
16 x 20
Shipping Weight (lb)
85
95
Shipping Dimensions W x D x H (in) 15 x 24 x 30.5 22 x 24 x 30.5
ES50LVP ECM blower performance (CFM/amps)
SWITCH
SETTING
0.1” WC
0.2” WC
0.3” WC
0.4” WC
0.5” WC
300 CFM
298
0.36
315
0.55
338
0.70
342
0.91
348
1.1
400 CFM
352
0.45
384
0.66
392
0.85
408
1.04
411
1.22
500 CFM
478
0.7
491
0.92
497
0.95
511
1.34
519
1.56
600 CFM
615
1.13
624
1.35
630
1.61
643
1.86
655
2.13
700 CFM
681
1.47
698
1.74
726
2.02
733
2.32
736
2.56
800 CFM
800
2.01
798
2.31
806
2.58
831
2.95
849
3.26
900 CFM
905
2.70
908
2.99
916
3.31
927
3.65
937
3.9