EcoSmart ES50LVP Installation, Operation And Maintenance Manual - Performance
6 |
P a g e
PERFORMANCE
RATINGS
ES50LVP
Performance Data - Hot Water Capacities (BTUH) @ 70°F Entering Air Temperature
Entering Water Temperature
CFM
GPM
110°F
120°F
130°F
140°F
150°F
160°F
170°F
180°F
Water PD
feet WC
@140°F
300
3
10,700
13,400
16,100
18,810
21,520
24,240
26,960
29,680
2.32
4
10,970
13,730
16,500
19,270
22,050
24,820
27,600
30,380
3.87
5
11,140
13,940
16,740
19,550
22,360
25,180
27,990
30,810
5.77
400
3
13,260
16,610
19,980
23,350
26,730
30,110
33,500
36,890
2.32
4
13,730
17,190
20,670
24,150
27,640
31,130
34,620
38,120
3.87
5
14,020
17,550
21,090
24,640
28,190
31,740
35,300
38,860
5.77
500
3
15,470
19,390
23,330
27,280
31,240
35,210
39,180
43,160
2.32
4
16,160
20,250
24,360
28,470
32,590
36,710
40,840
44,970
3.87
5
16,600
20,790
24,990
29,200
33,420
37,640
41,870
46,100
5.77
600
3
17,390
21,820
26,260
30,720
35,180
39,660
44,150
48,640
2.32
4
18,330
22,980
27,640
32,320
37,000
41,700
46,400
51,100
3.87
5
18,920
23,710
28,510
33,320
38,150
42,970
47,810
52,650
5.77
700
3
19,090
23,950
28,840
33,740
38,660
43,590
48,530
53,470
2.32
4
20,270
25,420
30,590
35,770
40,970
46,180
51,390
56,610
3.87
5
21,030
26,360
31,710
37,070
42,440
47,820
53,210
58,610
5.77
800
3
20,580
25,840
31,120
36,420
41,730
47,070
52,410
57,760
2.32
4
22,020
27,620
33,250
38,890
44,550
50,220
55,900
61,590
3.87
5
22,950
28,770
34,620
40,480
46,360
52,250
58,150
64,050
5.77
900
3
21,910
27,510
33,150
38,800
44,480
50,170
55,870
61,590
2.32
4
23,600
29,610
35,650
41,720
47,800
53,890
60,000
66,110
3.87
5
24,710
30,990
37,290
43,620
49,960
56,310
62,680
69,050
5.77