Garador Garamatic 10 Installation, Operating And Maintenance Instructions - page 37
E N G L I S H
40
07.2006 TR10A020-A RE
7.2.1
7-segment display when changing from the
customer menu to the special menus
Note
When changing to the special menus, depending on the
current setting in menu 2, a number between "0" and "6"
flashes in the 7-segment display.
7.2.2
7-segment display after selecting a special menu
Note
After selecting a special menu, a number between 0…9
can flash in the 7-segment display, depending on the menu.
This number indicates the (first) active parameter
7.3
MENU 3 – automatic timed closing (see fig.
22
)
Note
Automatic timed closing can only be activated when at
least one safety device is active (menu 4).
Display
Automatic timed closing
not activated
after 10 seconds
after 20 seconds
after 30 seconds
after 45 seconds
after 60 seconds
after 90 seconds
after 120 seconds
after 150 seconds
after 180 seconds
Note
If the operator receives an impulse during automatic timed
closing (menu 3, parameter greater than 0), then the door
stops and opens again.
Press the PRG button to return to normal operation
(menu 0).
7.4
MENU 4 – safety devices (see fig.
23
)
Display
Function
Photocell
not present
present (with dynamic self-monitoring unit)
Closing edge safety device / leading photocell without
self-monitoring unit
not present
present
Closing edge safety device / leading photocell with
self-monitoring unit
present
Wicket door contact with self-monitoring unit
not present
present
ATTENTION
Safety devices without a self-monitoring unit
must be tested every 6 months.
Press the PRG button to return to normal operation
(menu 0).
7.5
MENU 5 – setting the advance warning phase,
options relay (accessories) and maintenance indi-
cation (see fig.
24
)
7.5.1
Maintenance indication
If the maintenance indication is activated (parameter A),
the operator lighting flashes at the end of a door cycle
when the prescribed maintenance interval - maintenance
of the door system - has been exceeded. The mainte-
nance indication can be reset by performing a learning
cycle.
7.5.2 Overview of maintenance intervals
Operator for single / double garages
Operation for 1 year or 2,000 door cycles
Operator for underground and collective garages
Operation for 1 year or 10,000 door cycles
➤