Goldine Controls Pro Logic PL-P-4 Installation Manual - Table of Contents
Table of Contents
Introduction
Before You Begin................................................................... 1
Installation Steps....................................................................
2
1. Preparing
General Water Chemistry.....................................................
3
Pool/Spa Water
Salt..........................................................................................
4
2. Mounting
Pro Logic Control Center...................................................... 6
Equipment
Temperature Sensors...........................................................
6
Optional AQL-CL Chlorination Kit........................................
6
Optional AQL-CHEM Sensing Kit.......................................
6
Optional AQL-CHEM2 CO
2
Dispense Kit..........................
6
Optional Remote Controls....................................................
7
Optional Base Station...........................................................
8
Optional Valve Actuators....................................................... 8
3. Plumbing
Pool/Spa Configuration........................................................
9
Turbo Cell...............................................................................
10
Flow Switch............................................................................
10
4. Electrical
Main Service..........................................................................
11
Wiring
Grounding and Bonding........................................................ 11
Circuit Breaker Installation and Wiring......................... ...... 11
General Purpose Outlet........................................................
12
Pro Logic Control Power......................................................
12
High Voltage Pool Equipment.............................................. 13
Low Voltage Wiring...............................................................
14
5. Configuration
Configuration Menu...............................................................
21
6. System Startup
Before Startup...................................................................... 30
and Checkout
Heater Checkout...................................................................
31
Service Mode........................................................................
31
7. Warranty
Pro Logic Limited Warranty.................................................
32
31
Heater Checkout
Follow these instructions to verify that the Pro Logic is properly controlling the heater.
1. Check that the Pro Logic is calling for the heater to turn on as indicated by the “Heater” LED being
illuminated. If the “Heater” LED is illuminated, go directly to step 2; if not, then check the following:
•
The heater is enabled (Configuration Menu/Heater Config.).
•
The heater temperature setting is at least 2ºF greater than the water temperature (Settings Menu /
Pool Heater & Spa Heater).
•
The filter pump is running.
•
If the pool has solar heat and the solar priority feature is enabled (Configuration Menu/Solar
Config) then solar must be off in order for the heater to fire. The easiest way to force solar off is to
go to the Settings Menu / Pool Solar & Spa Solar and temporarily lower the temperature settings
below the current water temperature.
2. Check that the heater is running. If not, then check:
•
Power is supplied to the heater.
•
The Pro Logic control output is properly connected to the heater control (see ”Heater Control”
wiring, page 14).
•
Some heaters also have internal switches or jumpers that have to be set correctly for remote
control operation—refer to the heater manual and also “Heater Control” (page 14).
•
Heater is turned on (“Kill Switch” is in the “ON” position).
•
If a heater bypass valve is installed, check that water is flowing through the heater.
•
The heater temperature setting is set as high as possible (usually 104ºF/40ºC). Also note that
some heat pumps actually have be set to the lowest possible temperature.
3. Once the heater is running, you can verify the “heater cooldown” feature (optional - see Configuration
Menu/Heater Config.) is operating properly:
•
Press the “Filter” button once (for 2 speed pumps, this may require 2 pushes of the “Filter”
button).
•
The heater should turn off (“Heater” LED off) and the “Filter” LED will flash to indicated heater
cooldown is active.
•
The display will periodically indicate that the filter pump is on for heater cooldown and show the
minutes remaining.
•
The pump will automatically turn off at the end of the 5 minute heater cooldown period.
For more detailed instructions on control and operation of the Pro Logic system, refer to the Operation
Manual.
Service Mode
Service mode disables all automatic control operation and is intended to be used when servicing the pool
system. To enter service mode, push the SERVICE button once on the main unit keypad. This will initially
turn all outputs off and then allow you to turn outputs on/off manually at the main display (only). In service
mode, the buttons on the optional remote display/keypad and the optional spa side remote will turn
outputs off, but will not turn any output on. Heater control outputs and solar control outputs are prevented
from turning on if the water temperature exceeds 104ºF (40ºC).
Pushing the SERVICE button again will enter a timed service mode. Service operation as described
above will continue for 3 hours, then automatically return to normal operation.
Push the SERVICE button once more to exit out of Service mode.