3. Mounting and installation
18
3.5
Supply of convection air
The Heat Pure is surrounded by a
convection casing, that warms up
the room in a constantly pleasant
and efficient manner.
For this system to operate to its
maximum effect, a convection set
is required.
This optional convection set
consists of:
Heat Pure 65R and 65L
•
2 flexible aluminium hoses Ø150 mm 1.25 m: 1 hose of 2.5 m
which must be divided in half, in order to get a total of 2 hoses.
•
4 hose brackets.
•
4 grills: outer dimensions 20 x 20 cm, recess dimension 16.5 x 16.5
cm, with connection collar Ø150 mm.
For the Heat Pure 65 corner models, the mantle iron and roll of felt
should be ordered separately, it’s not included in the convection set.
This convection set is ordered separately to the Heat Pure. Instead of a
grill, openings (for example recessed plinths) can be used. Do not reduce
the convection openings.
Place all of the grills / openings, both upper and lower, to facilitate the
natural circulation. The gratings / openings should be situated in the
same pressure area (the same room) as the Heat Pure.
Heat Pure 66 3-sided and Heat Pure 80 tunnel
•
2 flexible aluminium hoses Ø150 mm 1.25 m: 1 hose of 2.5 m which
must be divided in half, in order to get a total of 2 hoses.
•
8 hose brackets.
•
4 grills: outer dimensions 20 x 20 cm, recess dimension 16.5 x 16.5
cm, with connection collar Ø150 mm.