KEB COMBIVERT F5 Series Installation manual - Cp-Parameter
GB - 32
CP-Parameter
CP.33 Relay output 1 / function
CP.34 Relay output 2 / function
CP.33/34 determine the function of the two relay outputs (X2A.24-26, X2A.27-29).
Value Function
0
No function (generally off)
1
Generally on
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (without auto-reset)
6
Warning or error message after abnormal stopping
7
Overload alert signal
8
Overtemperature alert signal power modules
9
Ex. overtemperature pre-warning motor
11 Overtemperature pre-warning OHI
20 Actual value = set value (CP.3 = Fcon, rcon, not at noP, LS, error, SSF)
21 Accelerate (CP.3 = FAcc, rAcc, LAS)
22 Decelerate (CP.3 = FdEc, rdEc, LdS)
23 Real direction of rotation = set direction of rotation
24 Utilization > switching level
1)
25 Active current > switching level
1)
27 Real value (CP.1) > switching level
1)
28 Setpoint (CP.2) > switching level
1)
31 Absolute setpoint on AN1 > switching level
1)
32 Absolute setpoint on AN2 > switching level
1)
34 Setpoint at AN1 > switching level
1)
35 Setpoint at AN2 > switching level
1)
40 Hardware current limit activated
41 Modulation on-signal
47 Ramp output value>switching level
1)
48 Apparent current (CP.4) > switching level
1)
49 Forward running (not at nOP, LS, abnormal stopping or error)
50 Reverse running (not at nOP, LS, abnormal stopping or error)
51 Warning E.OL2
52 Current regulator limit reached
53 Speed regulator limit reached
63 Absolute value ANOUT1 > switching level
1)
64 Absolute value ANOUT2 > switching level
1)
65 ANOUT1 > switching level
1)
66 ANOUT2 > switching level
1)
70 Driver voltage activ (safety relay)
73 Absolut active power > switching level
1)
74 Active power > switching level
1)
No listed values are only for application mode.
1)
Switching level of CP.33 = 100; switching level of CP.34 = 4