VIII) Troubleshooting
Problem/Symptom
Possible Cause
Solution
No power to any of the six outputs
1) No or low (
2) Bad power input ground connection
3) Defective unit.
1) Remove protective plastic cover &
place a dc voltmeter or DMM across
PDS-100 positive & negative power
input studs to verify input voltage. If
no voltage check for blown or tripped
input fuse/circuit breaker.
2) If no power to PDS-100 input and
fuse/breaker is OK, check for loose
ground cable.
3) Contact Kussmaul for RMA.
Load Group set for timed disconnect
turns off too soon
1) DIP switches not set correctly
2) Battery voltage is dropping below
10.0 VDC causing activation of Master
Low Voltage Shutdown circuit
3) Unit may have been reset to Factory
Default settings, thus unit is not
operating according to the dip switch
positions observed.
1) Reset this Load Group for Mode 2:
IGN with Timeout & verify time period
selected, see Section V.
2) Check for low voltage at the
battery terminals. If voltage is low:
recharge. If problems persists check
for faulty alternator or replace battery.
3) Re-program the unit - see page 6.
Load Group set for timed disconnect
does not disconnect
1) DIP switches not set correctly
2) Defective unit
3) Unit may have been reset to Factory
Default settings, thus unit is not
operating according to the dip switch
positions observed.
1) Verify DIP switches for this Load
Group are set for Mode 2: IGN
with Timeout & verify time period
selected, see Section V.
2) Contact Kussmaul for an RMA.
3) Re-program the unit - see page 6.
Ignition controlled circuits not on when
ignition is ON.
1) Ignition terminal on PDS-100 not
receiving +12 vdc when ignition is on.
2) Incorrect Mode programming
selected for this Load Group.
3) Unit may have been reset to Factory
Default settings, thus unit is not
operating according to the dip switch
positions observed.
1) Check ignition wiring, check for
blown ignition source fuse.
2) See Mode selection section on
page 6.
3) Re-program the unit - see page 6.
Load Group set for low voltage
disconnect, disconnects when battery
is not below selected disconnect
threshold
1) DIP switches not set properly
2) PDS-100 input wires under-sized or
too long resulting in excessive voltage
drop
3) Unit may have been reset to Factory
Default settings, thus unit is not
operating according to the dip switch
positions observed.
1) See Table 6 for LVD disconnect
voltage choices
2) See Table 1 ‘Recommended input
power feed wire size’ and increase
wire size or reduce wire length.
3) Re-program the unit - see page 6.