Magnetic Autocontrol MGC-PRO Technical Manual

Other manuals for MGC-PRO: Technical Manual
Manual is about: MicroDrive Ethernet Module

Summary of MGC-PRO

  • Page 1

    Technical manual rs485/422 mgc-pro microdrive this technical manual is a supplement to the operating instructions "barrier mhtm tm microdrive" (5815,5001) and describes the rs485/422 module. Before using the rs485/422 module, read this handbook and the operating instructions "barrier mhtm tm microdr...

  • Page 2

    Rs485/422 mgc-pro microdrive 2 5815,0003en / version 00 magnetic autocontrol gmbh grienmatt 20 79650 schopfheim germany phone: +49 (0) 7622 695 5 fax.: +49 (0)7622 695 602 email: info@ac-magnetic.Com internet: www.Ac-magnetic.Com.

  • Page 3: Contents

    Rs485/422 mgc-pro microdrive contents 5815,0003en / version 00 3 contents 1 general....................................................................................5 1.1 information regarding the technical manual ..................5 1.2 function ......................................................

  • Page 4

    Rs485/422 mgc-pro microdrive contents 4 5815,0003en / version 00

  • Page 5: 1 General

    Rs485/422 mgc-pro microdrive general 1 general 1.1 information regarding the technical manual this manual offers important information on handling of the rs485/422 module. The rs485/422 module can only be operated installed in the magnetic mhtm tm microdrive barriers. Prerequisite for secure work is...

  • Page 6

    Rs485/422 mgc-pro microdrive general 1.3 reference documents note! This technical manual is based on the documents listed in the following table. All listed reference documents are available free of charge via the indicated procurement source. Number title author procurement source 5815,5001 operati...

  • Page 7: Notice!

    Rs485/422 mgc-pro microdrive general 1.4 pictogram explanation warning notes warning notes are characterised by pictograms in this manual. It is absolutely essential to observe the notes and to proceed with caution in order to prevent property damage. Notice! Notice! … points to a potentially harmfu...

  • Page 8: 2 Technical

    Rs485/422 mgc-pro microdrive technical data 8 5815,0003en / version 00 2 technical data designation unit value current consumption ma 50 max. Line length: m 1000 cable type – 2x2 (twisted), shielded plug type – spring clip max. 2.5mm² supported services – modbus table 2: technical data.

  • Page 9: Notice!

    Rs485/422 mgc-pro microdrive installation and network connection 3 installation and network connection 3.1 rs485/422 installing module in control unit mgc-pro hints and recommendations note! The rs485/422 module can only be operated with the magnetic control units mgc-pro. The rs485/422 module is in...

  • Page 10

    Rs485/422 mgc-pro microdrive installation and network connection 3.1.1 corrective action possible cause malfunction corrective action green led at the centre is not permanently lit. The rs485/422 module is only supported by the control units mgc- pro. Check label or type sign of the control unit. Th...

  • Page 11

    Rs485/422 mgc-pro microdrive installation and network connection 5815,0003en / version 00 11 3.4 address settings the subscriber address is set comfortably using the operating display of the mgc-pro control unit. When setting the address, observe that the addresses of the different subscribers in th...

  • Page 12

    Rs485/422 mgc-pro microdrive installation and network connection 12 5815,0003en / version 00 operating view  main menu  rs485/422  settings parameters description address the settings and display of the address of the bus participant. Factory setting 1 termination activation/deactivation of the b...

  • Page 13: 4 Modbus

    Rs485/422 mgc-pro microdrive modbus interface 4 modbus interface 4.1 standard modbus communication takes place via the modbus protocol. After the connection between the client (master) and server (slave) is established, the master sends modbus requests to the server. The result is returned as a modb...

  • Page 14

    Rs485/422 mgc-pro microdrive modbus interface 14 5815,0003en / version 00 4.1.2 address table the following modbus address table permits access to the most important functions and conditions of the barrier. For this, the "function codes" 0x3 to 0x6 are used.  see page 6, chapter 1.3 "reference docu...

  • Page 15

    Rs485/422 mgc-pro microdrive modbus interface 5815,0003en / version 00 15 4.1.3 examples reading status – request meaning value (hex) adu address 01 function code (read holding register) 03 00 starting address 01 00 pdu quantity of register 02 95 adu crc-16 cb reading status – response meaning value...

  • Page 16

    Rs485/422 mgc-pro microdrive modbus interface 16 5815,0003en / version 00 opening barrier – request meaning value adu address 01 function code (write single register) 06 00 register address 00 00 pdu register value 01 48 adu crc-16 0a opening barrier – response meaning value adu address 01 function ...

  • Page 17

    Rs485/422 mgc-pro microdrive modbus interface 4.2 expanded access via modbus "function code 43/13" 4.2.1 canopen tcp/ip interface in addition to the control via standard modbus, access to further parameters is possible via "function code 43/13".  see page 6, chapter 1.3 "reference documents", docum...

  • Page 18

    Rs485/422 mgc-pro microdrive modbus interface 18 5815,0003en / version 00 the rs485/422 module supports only the sdo commands defined in document cia ds 309, section 4.1. Simple transfer default network number default data type of the protocol  refer to cia ds 309-2, 3.2.3.4.2 protocol control. 4.2...

  • Page 19

    Rs485/422 mgc-pro microdrive modbus interface 5815,0003en / version 00 19 setting programme mode – request meaning value adu address 01 function code (encapsulated interface) 2b mei type 0d protocol control 01 protocol option fields reserved field 00 node id 01 hi 21 index lo 04 sub-index 01 hi 00 s...

  • Page 20

    Rs485/422 mgc-pro microdrive modbus interface 20 5815,0003en / version 00 reading device name module 1 – request meaning value adu address 01 function code (encapsulated interface) 2b mei type 0d protocol control 02 reserved field 00 protocol option fields encoded data 50 node id 01 hi 10 index lo 0...

  • Page 21

    Rs485/422 mgc-pro microdrive modbus interface 5815,0003en / version 00 21 reading device name module 1 – response description value adu address 01 function code (encapsulated interface) 2b mei type 0d protocol control 02 reserved field 00 protocol option fields encoded data 50 node id 01 hi 10 index...

  • Page 22: 5 Commissioning

    Rs485/422 mgc-pro microdrive commissioning 22 5815,0003en / version 00 5 commissioning 5.1 procedure we recommend the following procedure for initial commissioning: 1. Specify bus topology. 2. Perform wiring. 3. Unplug spring clip. 4. Switch on control unit. 5. Perform settings via menu. Set bus typ...

  • Page 23

    Rs485/422 mgc-pro microdrive commissioning 5.3 software tools the following software tools can be helpful to support development: name manufacturer docklight scripting http://www.Docklight.De/ modbusdoctor http://kikos31.Developpez.Com/modbusdoctor/ modbus tk http://code.Google.Com/p/modbus-tk/ modb...

  • Page 24: 6 Appendix

    Rs485/422 mgc-pro microdrive appendix 24 5815,0003en / version 00 6 appendix the description of the status words and object tables are available in document 5815,0000 "microdrive mgc/mgc-pro additional information for system integrators". 7 list of abbreviations abbreviatio n meaning description mgc...

  • Page 25: Index

    Rs485/422 mgc-pro microdrive index 5815,0003en / version 00 25 index a address setting.............................................................11 address settings ................................................11 address table......................................................14 adu ...........