Installation and network connection
3 Installation and network connection
3.1
RS485/422 Installing module in control unit MGC-PRO
Hints and recommendations
NOTE!
The RS485/422 module can only be operated with
the MAGNETIC control units MGC-PRO.
The RS485/422 module is installed and set in the factory. Observe
the following safety note in case of retrofitting by the customer.
RS485/422 Module retrofitting
NOTICE!
NOTICE!
Property damage from improper installation
and improper commissioning.
Therefore:
– Only qualified staff must install the RS485/422
module, connect and commission it.
– Take ESD precautions and comply with them.
1.
Open barrier casing according to operating instructions
"Barrier MHTM
TM
MicroDrive". Observe warning notes.
2.
Switch off power supply. Ensure that the system is powered
down. Secure against reactivation. The balancing springs in
the lever system are relaxed.
3.
Take care when opening control unit cover.
4.
Plug in plug-in module in a free slot.
NOTE!
Slot selection influences the plug-in module's
module address.
See page 17, chapter 4.2.2.
5.
Switch on power supply.
6.
Check LEDs at the plug-in module. The green LED at the
centre must be lit.
If applicable, read the following chapter
"Corrective action".
7.
The main menu shows the menu "RS485/422".
8.
Apply cover of the control unit.
9.
Close barrier casing according to operating instructions
"Barrier MHTM
TM
MicroDrive".