NAPCO F-TPBR Installation Instructions Manual - page 2
2
F-TPBR Touchpad Configuration Jumper JP1
F-TPBR Touchpad Wiring Diagram
Touchpad Addresses
The F-TPBR Touchpad jumper is installed at the factory--
Do Not Remove. The system requires an F-TP Touchpad
configured for address number 1 (no shunt on address
jumper).
F-TPBR System Zones
The F-TPBR provides 2 additional system zones.
F-TPBR Zone 1 may be used as a wireless zone and will
report and display as system Zone 7. Zone 2 is the integral
PIR of the F-TPBR which will report and display as system
Zone 8.
F-TPBR Touchpad Zone 1 Configuration.
To enable wireless on Zone 7, program "Dealer Options
2" location with a 3, i.e., [97-3].
F-TPBR Touchpad Zone 2 Configuration.
By default (JP1.2 not installed), the F-TPBR Touchpad’s
integral PIR is configured as Zone 8. A violation of the
F-TPBR Touchpad PIR will cause a Zone 8 alarm if
armed AWAY.
If JP1.2 jumper is installed, the integral PIR will not acti-
vate an alarm. In this configuration, the F-TPBR Touch-
pad PIR will function only as an activity sensor (preventing
false alarms when erroneously armed AWAY) and will not
provide any protective burglary functions.
F-TPBR Touchpad Terminal Descriptions
Terminals 1-3: F-TPBR Touchpad Data Bus Terminals
The F-TPBR Touchpad communicates to the F-8 Panel
via the F-8 Panel’s 3-wire keypad bus. Wire the F-TPBR
Touchpad to the F-8 Panel as shown on wiring diagram.
Terminal 1 is + 12 V DC, Term 2 is GND and Term 3 is
Data.
Terminal 4: Alarm Output
The F-TPBR Touchpad has an integral sounder, but
unlike the F-TP Touchpad, the sounder does not meet
(even at full volume) the NFPA audible requirement of
85dB @ 10 feet for residential fire or residential bur-
glary. NOTE: In UL Residential Fire and NFPA instal-
lations, the F-TPBR Touchpad must not have the bell
terminal connected, as connection would prevent the
supervision of the F-TP Touchpad bell.
Alarm Sounder Volume Adjustment
The F-TPBR Touchpad alarm circuit includes a potenti-
ometer which regulates the volume of the sounder. The
sounder volume is set at the factory to the minimum level
(fully counter-clockwise) and can be increased to satisfy
the requirements of the installation. Turn the potentiome-
ter clockwise to increase the volume or remove the wire
from terminal 4 of the F-TPBR Touchpad to silence.
JP1
F-TPBR Touchpad
Address
F-TPBR Touchpad
Zone 2 Configuration
DO NOT REMOVE,
SHUNT CONNECTOR
MUST BE ON
Integral PIR will trip
Zone 8.
OFF
Integral PIR will NOT trip
alarm.
ON
JP1 Configuration
Jumper
T 16
T 17
T 18
T 14
T
o F-8
Pa
nel Te
rm
inals
JP
ADDR
PIR
≠
AUX2
(+)PWR
(-)GND
DATA
(+)
REM
BUS
1
2
3
4
Turn clockwise to
increase volume
Emergency Button Decals
Position as follows:
Flame = Fire Emergency (apply to middle button).
A = Auxiliary Emergency (optional) (apply to right button).
Shield = Police Emergency (apply to left button).
A
A