Novatek Volt Control RN-122 Operating Manual - page 4
~ 4 ~
NOVATEK-ELECTRO
RN-122
– Relative humidity (at temperature of +25 °С): 30 … 80 %.
If the temperature of the device after transportation or storage differs from the ambient temperature at
which it is supposed to be operated, then before connecting to the mains keep the device under the operating
conditions within two hours (because of condensation may be on the device elements)
.
ATTENTION! The device is not intended for operation in the following conditions:
– Significant vibration and shocks;
– High humidity;
– Aggressive environment with content in the air of acids, alkalis, etc., as well as severe contaminations
(grease, oil, dust, etc.).
2. TECHNICAL SPECIFICATIONS
The basic technical specifications of RN-122 are given in Table 2.
General data is given in Table 3
Table 2
– Basic Technical Specifications
Description
Value
AC single-phase operating supply voltage, V
220/230
Mains frequency, Hz
47
– 65
Harmonic composition (unsinusoidality) of supply voltage
EN 50160
Control range:
– U
min
response, V
– U
m
ах
response, V
– AR interval, s
160
– 210
230
– 290
5
– 900
Fixed time of U
mах
response, s
1
Fixed off-delay due to U
min
, s
7
Fixed time of response when voltage reducing less than 120 V, s
0.12
Fixed time of response in case of voltage spike of more than 450 V when pulse duration
reaching more than 1 ms, max., s
0.02
Accuracy of determination of the voltage operation threshold, max., V
3
Hysteresis of overvoltage release, V
5
Minimum voltage when maintaining serviceability (effective value), V
120
Maximum switched current with active load, A
16
Maximum voltage when maintaining serviceability (effective value), V
350
Commutation life of output contacts:
–
under load of 16 A, time, min.
–
under load of 5 A, time, min.
100 thousand
1 million
Power consumption when load is not connected, W
Up to 1.3
Power of switched load, kW, max.
3.6
Weight, kg, maximum
0.16
Overall dimensions (Fig. 1), H*B*L, mm
122
х61х76
The device remains operational capability in any position in space
Table 3
– General Data
Description
Value
Device service
Switchgear and controlgear
Rated operating condition
Continuous
Protection class rating
IP30
Electric shock protection class
I
Climatic design version
NC 3.1
Permissible contamination level
II
Overvoltage category
II
Rated voltage of insulation, V
450
Rated impulse withstand voltage, kV
2.5
3. THE INTENDED USE
3.1. Preparation for operation
3.1.1. Preparation for connection:
Unpack the device (we recommend to keep the original packing for the entire warranty period of the device
operation);