Pacific Energy FP30AR Installation And Operating Instructions Manual

Manual is about: ZERO CLEARANCE WOOD FIREPLACE B series

Summary of FP30AR

  • Page 1

    190913-28 pacific fp30 5055.5152 installation and operating instructions safety notice if this stove is not properly installed, a house fi re may result. For your safety, follow the installation instructions. Contact local building or fire officials about restrictions and installation inspection req...

  • Page 2: Contents

    2 pacific fp30 190913-28 note: we strongly r e c o m m e n d t h at smoke detectors be installed. If smoke detectors have been previ- ously installed, you may notice that they are operating more frequently. This may be due to curing of stove paint or fumes caused by accidentally leaving the fi re do...

  • Page 3

    Pacific fp30 190913-28 3 safety and maintenance 1. Burn only, dry and well seasoned cord wood. The denser or heavier the wood when dry, the greater its heat value. This is why hardwoods are generally preferred. Green or wet wood should not be used, it will reduce heat output, as well as, contribute ...

  • Page 4

    4 pacific fp30 190913-28 maintenance checks check the following parts for damage such as cracks, excessive corrosion, burned out sections and excessive warping: (see website for descriptions and more detail) weekly: - firebrick - visual, for cracking. - door gasket - sagging, placement, damage. Mont...

  • Page 5

    Pacific fp30 190913-28 5 creosote formation and need for removal when wood is burned slowly, it produces tar and other or- ganic vapours, which combine with expelled moisture to form creosote. The creosote vapours condense in the relatively cool chimney fl ue of a slow burning fi re. As a result, cr...

  • Page 6

    6 pacific fp30 190913-28 operation caution: hot while in operation. Keep children, clothing and furniture away. Contact will cause skin burns. Warning: over firing the appliance will short- en the life of the product. Failure to rectify an over firing condition can be hazardous and may void the manu...

  • Page 7

    Pacific fp30 190913-28 7 baffle removal the baffle should only be removed when chimney is being cleaned. Do not operate with baffle assembly or insulation removed. Removal remove retaining pin at the rear inside top of the fi rebox, just under the baffle. Lift baffle up and pull forward to disconnec...

  • Page 8

    8 pacific fp30 190913-28 fig. #5 nuts blower replacement 1. The blower is located in the bottom rear compartment of the woodstove and can be accessed by removing the access panel on the bottom of the fi rebox. Remove the bricks to expose the access panel, then remove the 8 bolts or screws holding th...

  • Page 9

    Pacific fp30 190913-28 9 item size part number a 9” x 4 1/2” x 1 1/4” (230 mm x 115 mm x 32 mm) 5096.99 b 9” x 3 1/2” x 1 1/4” (102 mm x 115 mm x 32 mm) 3245.501 c 7 1/4” x 4 1/2” x 1 1/4” (184 mm x 115 mm x 32 mm) 245.001 firebrick installation this package contains 19 full-size fi rebricks, as wel...

  • Page 10

    10 pacific fp30 190913-28 fireplace installation crate removal 1) carefully remove wood top and supports. 2) remove the screws securing the fi replace to the pallet(4). 3) remove from pallet bottom. Warning: under no circumstances is this heater to be installed in a makeshift or "temporary" manner. ...

  • Page 11

    Pacific fp30 190913-28 11 fp30 45" 44" 30 3/4" 11 1/4" 21 7/8" 28 1/8" 29 1/2" 25" dimensions clearances this heater must be installed with a listed compatible chimney system listed on page 15. Clearances to combustible surfaces and materials are shown on pages 11 & 13. Clearances may be reduced wit...

  • Page 12

    12 pacific fp30 190913-28 1/2 38 3/4 " 109 1/2 " 27 3/8 " 50 5/8 " 50 5/8 " 61 3/4 " 50 5/8 " 6 3/8" 77 3/8 " 77 3/8 " minimum framing dimensions fig. #8 note: the framing dimensions around the fireplace include the inner drywall board..

  • Page 13

    Pacific fp30 190913-28 13 item part # description qty. 1 5049.9912 screw, teks pkg #8 x 1/2” 40 2 7746 stud, top/bottom 50 1/2”l 2 3 9093.22 stud, cntr support sides, 15”l 5 4 7747 framing kit leg 3 1/2"l 3 framing kit assembly 2 3 each kit contains: assembly • lay out top/bottom studs (2) and cente...

  • Page 14

    14 pacific fp30 190913-28 minimum clearances to combustibles ರ fig. #10

  • Page 15

    Pacific fp30 190913-28 15 fig. #11 chimney roof fl ashing storm collar * 4" diameter combustion outside air inlet. One on either side of unit. The combustion air inlets can be rotated to draw air from the rear of the unit if desired. Spark arrestor rain cap radiation shield chimney support 39" (991m...

  • Page 16

    16 pacific fp30 190913-28 chimney installation listed chimney and chimney connector this appliance must be installed with a 6" chimney system approved under the following standards: can-ulc s629(in canada) and ul 103ht(in u.S.). You must follow the chimney manufacturer's installation instructions fo...

  • Page 17

    Pacific fp30 190913-28 17 offsets 15' 30° or 45° elbows the chimney for the fp30 can be installed with a maximum of four 45° elbows(in canada) and four 30° elbows(in u.S.A.) as shown in fig. #12. Installation: 1. Install the fi rst elbow; turn it in the required direction. It is required to secure c...

  • Page 18

    18 pacific fp30 190913-28 combustion air intake or combustion air can be supplied to the stove in one of two ways. Consult your local building code or can/csa- b365, installation code for solid-fuel-burning appliances and equipment before proceeding. 1. Outside air supply - outside air may be drawn ...

  • Page 19

    Pacific fp30 190913-28 19 18" [457mm] 8" [203mm] 8" [203mm] 19 1/8" [486mm] 38 1/2" [978mm] 18" [457mm] 8" [203mm] 8" [203mm] 58" [1.47m] canada only floor protector the stove may be installed on a combustible fl oor provided non-combustible ember protection, such as tile, metal, brick, etc., is use...

  • Page 20

    20 pacific fp30 190913-28 70” min 60 1/2”min gravity vent air inlet to center of outlet remote heat duct installation in u.S.A., a minimum of one remote gravity heat duct kit must be installed with the fp30. Part# fp30.Gvkit contents: 1 - outlet adapter 1 - heat duct adapter 1 - 14" x 10" outlet gri...

  • Page 21

    Pacific fp30 190913-28 21 70” min 12” min floor ceiling 11 1/4” 9 3/4” fig. #20 fig. #21 3. Locate and cut a 11 1/4” x 9 3/4” opening in the wall or facing material being sure to maintain structural integrity. 4. The centerline of the outlet must be a minimum 70” off the fl oor, 16" from any adjacen...

  • Page 22

    22 pacific fp30 190913-28 cement board installation the front facing area of the fp30 must be covered with non- combustible cement board as shown in fig.#23 and #24 prior to applying any fi nishing material. The cement board can be attached to the framing and to the front of the unit outside of the ...

  • Page 23

    Pacific fp30 190913-28 23 mantel clearance a-canada 42”(no gravity vent) a-canada 34"(gravity vent) a-u.S.A. 34" mantel depth b 2" to 12" mantel clearance chart 16 1/2” non-combustible cement board -non-combustible decorative facing non-combustible zone. Do not install any combustible material, elec...

  • Page 24

    24 pacific fp30 190913-28 troubleshooting problem cause cure glass is dirty 1. Wood is wet - use dry wood 2. Turning down air control - do not turn down until or damper too soon a) there is a good bed of coals b) the wood is charred 3. Draft too low - improper chimney height and / or diameter - chim...

  • Page 25

    Pacific fp30 190913-28 25 operating tips 1. Always use dry, seasoned fi rewood, up to 20" long. Load wood endwise, a mixture of large and small pieces, on top of a good ash base (1" minimum). 2. Operate on a medium to high setting, for up to 1 hour from cold start. After the initial warm up pe- riod...

  • Page 26

    26 pacific fp30 190913-28 replacement parts item description part no. 1............ Inlet air shield ............................................... 7719.5 2............ Cast ash lip .................................... Alip.50374753 3............ Blower ................................................

  • Page 27: Caution

    Pacific fp30 190913-28 27 label le systÈme de cheminÉe doit Être homologuÉ comme suit : au canada - cheminÉe homologuÉe ulc-s-629, icc le systÈme de cheminÉe doit Être homologuÉ comme suit : au canada - cheminÉe homologuÉe ulc-s-629, icc (industrial chimney company). Aux États-unis - cheminÉe homolo...

  • Page 28

    Pacific energy fireplace products ltd. 2975 allenby rd., duncan, b.C. V9l 6v8 phone: 250-748-1184 web site: http://www.Pacifi cenergy.Net printed in canada.