© 2008 panasonic ha air-conditioning (m) sdn. Bhd. (11969-t). All rights reserved. Unauthorized copying and distribution is a violation of law. Order no. Mac0802020a8 air conditioner cs-f14db4e5 cu-yl28hbe5 cs-f18db4e5 cu-yl34hbe5 cs-f24db4e5 cu-yl24hbe5 cs-f24db4e5 cu-yl43hbe5 cs-f28db4e5 cu-yl28hb...
Page 2
2 3.1. Outdoor unit ------------------------------------------------6 4 specifications ------------------------------------------------------7 4.1. Product specification --------------------------------------7 5 dimensions ------------------------------------------------------- 14 5.1. Cu-yl24hbe5 c...
Page 3: 1 Safety Precautions
3 1 safety precautions • read the following “safety precautions” carefully before perform any servicing. • electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. • the caution items stated...
Page 4
4 20. After completion of the installation servicing confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fire. 21. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fire. ...
Page 5: 2 Service Information
5 2 service information 2.1. Operation range 2.1.1. Power supply the applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be h...
Page 6: 3 Features
6 3 features 3.1. Outdoor unit 3.1.1. Flexible installation in smaller spaces • spacing-saving outdoor unit with the improvement of the outdoor unit fan makes it possible to install the outdoor unit into a smaller space where the conventional model cannot be installed. • long pipe design with maximu...
Page 7: 4 Specifications
7 4 specifications 4.1. Product specification 4.1.1. Cs-f14db4e5 cu-yl28hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on ...
Page 8
8 4.1.2. Cs-f18db4e5 cu-yl34hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on indoor temperature of 20 °c d.B. (68°f d.B.)...
Page 9
9 4.1.3. Cs-f24db4e5 cu-yl24hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on indoor temperature of 20 °c d.B. (68°f d.B.)...
Page 10
10 4.1.4. Cs-f24db4e5 cu-yl43hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on indoor temperature of 20 °c d.B. (68°f d.B....
Page 11
11 4.1.5. Cs-f28db4e5 cu-yl28hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on indoor temperature of 20 °c d.B. (68°f d.B....
Page 12
12 4.1.6. Cs-f34db4e5 cu-yl34hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on indoor temperature of 20 °c d.B. (68°f d.B....
Page 13
13 4.1.7. Cs-f43db4e5 cu-yl43hbe5 1. Cooling capacities are based on indoor temperature of 27 °c d.B. (80.6°f d.B.), 19.0°c w.B. (66.2°f w.B.) and outdoor air temperature of 35 °c d.B. (95°f d.B.), 24°c w.B. (75.2°f w.B.) 2. Heating capacities are based on indoor temperature of 20 °c d.B. (68°f d.B....
Page 14: 5 Dimensions
14 5 dimensions 5.1. Cu-yl24hbe5 cu-yl28hbe5.
Page 15
15 5.2. Cu-yl34hbe5.
Page 16
16 5.3. Cu-yl43hbe5.
Page 17: 6 Block Diagram
17 6 block diagram 6.1. Cu-yl24hbe5 cu-yl28hbe5.
Page 18
18 6.2. Cu-yl34hbe5.
Page 19
19 6.3. Cu-yl43hbe5.
Page 20: 7 Wiring Diagram
20 7 wiring diagram 7.1. Cu-yl24hbe5 cu-yl28hbe5.
Page 21
21 7.2. Cu-yl34hbe5.
Page 22
22 7.3. Cu-yl43hbe5.
Page 23
23 8 electronic circuit diagram 8.1. Cu-yl24hbe5 cu-yl28hbe5.
Page 24
24 8.2. Cu-yl34hbe5.
Page 25
25 8.3. Cu-yl43hbe5.
Page 26: 9 Printed Circuit Board
26 9 printed circuit board 9.1. Cu-yl24hbe5 cu-yl28hbe5 9.1.1. Printed circuit board (main).
Page 27
27 9.1.2. Printed circuit board (noise filter) 9.1.3. Printed circuit board (display).
Page 28
28 9.2. Cu-yl34hbe5 cu-yl43hbe5 9.2.1. Printed circuit board (main).
Page 29
29 9.2.2. Printed circuit board (capacitor).
Page 30
30 9.2.3. Printed circuit board (display/noise filter).
Page 31: 10 Installation Instruction
31 10 installation instruction 10.1. Outdoor unit installation • precautions shown here are differentiated between and . Those that have much chances for leading to significant result such as fatality or serious injury if wrong installation would have been carried out are listed compiling them espec...
Page 32
32 10.1.1. Accessories supplied with outdoor unit • the following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before installing the outdoor unit. 10.1.2. Before installation work • this product is using new refrigeration (r410a). The basic way...
Page 33
33 2. Installation work a. Brazing work brazing work needs replacing air inside pipe with nitrogen gas in order to prevent oxidization scale from occurring. This is called nitrogen replacement, and one of very important work in brazing refrigerant piping. (oxidation preventive is not possible to use...
Page 34
34 dry vacuuming • if vacuum pump possible vacuuming until less than -100.7kpa. 10.1.3. Selecting the outdoor unit installation locations • select location which satisfies the following condition, and then confirm with the customer that such a place is satisfactory before installing the outdoor unit...
Page 35
35 12. Be sure to leave enough space around the outdoor unit to maintain proper performance and to allow access for routine maintenance. • allow enough space from any obstacles as shown in fig.1.2 below in order to prevent short-circuits from occurring. (if installing more than one outdoor unit, mak...
Page 36
36 • if a drain pipe needs to be installed, insert the accessory drain elbow into the mounting hole at the bottom of the outdoor unit, and connect a hose with an inside diameter of 15mm to this drain elbow. (the hose is not supplied.) in cold regions (where the outdoor air temperature can drop to 0°...
Page 37
37 2. Allowable piping length 3. Additional limitations for twin-type • maximum allowable one-way piping length is the larger numerical value between (lo + la) and (lo + lb). • for twin type, only the main piping can be reused among the existing piping. Brandnew standard pipe should be installed for...
Page 38
38 2. Cutting and flaring the piping. A. Please cut using pipe cutter and then remove the burrs. B. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. C. Please make flare after inserting the fla...
Page 39
39 • pump down operation • operate the pump down according to the following procedures. 10.1.9. Electrical wiring • connect the power supply wiring and indoor/outdoor unit connection wiring according to the electrical circuit diagram instructions. • clamp the wires securely to the terminal connectio...
Page 40
40 earth lead wire shall be longer than other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage. Outdoor unit/single-phase model • power supply specifications model name leakage current breaker (a) circuit breaker (minimum capacity...
Page 41
41 10.1.10. Cool only • setting of cooling only model [setting method] when the equipment is not power on, cut off jp1 (cool only) as shown in figure 1. After cut off the wire, switch on the equipment power. By setting to cooling only model, heating operation is disabled. (wired remote controller ca...
Page 42
42 10.1.12. As to making the inspection after completion of work fully understood • at the time when the work has been completed, measure and record the characteristics of test run without fail and keep the measuring date, etc. • carry out the measurement regarding room temperature outside air tempe...
Page 43
43 10.2. Outdoor unit installation • precautions shown here are differentiated between and . Those that have much chances for leading to significant result such as fatality or serious injury if wrong installation would have been carried out are listed compiling them especially into the column of . H...
Page 44
44 10.2.1. Accessories supplied with outdoor unit • the following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before installing the outdoor unit. 10.2.2. Before installation work • this product is using new refrigeration (r410a). The basic way...
Page 45
45 2. Installation work a. Brazing work brazing work needs replacing air inside pipe with nitrogen gas in order to prevent oxidization scale from occurring. This is called nitrogen replacement, and one of very important work in brazing refrigerant piping. (oxidation preventive is not possible to use...
Page 46
46 dry vacuuming • if vacuum pump possible vacuuming until less than -100.7kpa. 10.2.3. Regarding handling handling the unit by hold the handle at compressor side and hold the basepan bottom at fan side. 10.2.4. Selecting the outdoor unit installation locations • select location which satisfies the ...
Page 47
47 10. When installing the product in a place where it will be affected by typhoon or strong wind such as wind blowing between buildings, including the rooftop of a building and a place where there is no building in surroundings, fix the product with an overturn prevention wire, etc. (overturn preve...
Page 48
48 10.2.5. Transporting and installing the outdoor unit • transporting 1. The outdoor unit should be transported in its original packaging as close to the installation location as possible. 2. If suspending the outdoor unit, use a rope or belt, and use cloth or wood as padding in order to avoid dama...
Page 49
49 • in the circumstances listed below, do not reuse the refrigerant piping as it is but wash it thoroughly before reusing it. - pump down operation cannot be performed for the existing air conditioner. - the compressor has a failure history. - oil is discolored. - the existing air conditioner is ga...
Page 50
50 • maximum allowable one-way piping length is the larger numerical value between (lo + la) and (lo + lb). • for twin type, only the main piping can be reused among the existing piping. Brandnew standard pipe should be installed for branch pipe/branch piping. 10.2.8. Connecting the pipes • use a cl...
Page 51
51 • refer to the following table for the tightening torques. Be sure to use two spanners to tighten. (if the nuts are overtightened, it may cause the flares to break or leak.) 3. After piping connection has been completed, make sure that the joint areas of the indoor and outdoor units are free from...
Page 52
52 10.2.10. Electrical wiring • connect the power supply wiring and indoor/outdoor unit connection wiring according to the electrical circuit diagram instructions. • clamp the wires securely to the terminal connections using cord clamps so that no undue force is placed on the wires. • once all wirin...
Page 53
53 outdoor unit/single-phase model this equipment complies with en/iec 61000-3-12 provided that the short-circuit power ssc is greater than or equal to yl34 : 3967.5kw, yl43 : 4657.5kw at the interface point between the user’s supply and the public system. It is the responsibility of the installer o...
Page 54
54 10.2.11. Cool only • setting of cooling only model [setting method] when the equipment is not power on, cut off jp1 (cool only) as shown in figure 1. After cut off the wire, switch on the equipment power. By setting to cooling only model, heating operation is disabled. (wired remote controller ca...
Page 55
55 10.2.13. As to making the inspection after completion of work fully understood • at the time when the work has been completed, measure and record the characteristics of test run without fail and keep the measuring date, etc. • carry out the measurement regarding room temperature outside air tempe...
Page 56: 11 Technical Data
56 11 technical data 11.1. Sound data.
Page 57
57.
Page 58
58 11.2. Capacity and power consumption 11.2.1. Cooling performance calculation of actual cooling capacity and power consumption: example: cs-f24db4e5 / cu-yl24hbe5 • calculation of the actual cooling capacity and power consumption for the following cooling conditions; indoor temperature of 27/19 °c...
Page 59
59 11.2.1.1. Cs-f14db4e5 × 2 cu-yl28hbe5.
Page 60
60 cooling capacity curve.
Page 61
61 cooling power consumption curve.
Page 62
62 11.2.1.2. Cs-f18db4e5 × 2 cu-yl34hbe5.
Page 63
63 cooling capacity curve.
Page 64
64 cooling power consumption curve.
Page 65
65 11.2.1.3. Cs-f24db4e5 cu-yl24hbe5.
Page 66
66 cooling capacity curve.
Page 67
67 cooling power consumption curve.
Page 68
68 11.2.1.4. Cs-f24db4e5 × 2 cu-yl43hbe5.
Page 69
69 cooling capacity curve.
Page 70
70 cooling power consumption curve.
Page 71
71 11.2.1.5. Cs-f28db4e5 cu-yl28hbe5.
Page 72
72 cooling capacity curve.
Page 73
73 cooling power consumption curve.
Page 74
74 11.2.1.6. Cs-f34db4e5 cu-yl34hbe5.
Page 75
75 cooling capacity curve.
Page 76
76 cooling power consumption curve.
Page 77
77 11.2.1.7. Cs-f43db4e5 cu-yl43hbe5.
Page 78
78 cooling capacity curve.
Page 79
79 cooling power consumption curve.
Page 80
80 11.2.2. Heating performance 1. Heating capacity when the unit is frosted over or while being defrosted will vary depending on outdoor temperature and the frosting. 2. Heating capacity must be compensated because it does not take into account the capacity drop incurred when the unit is frosted ove...
Page 81
81 11.2.2.1. Cs-f14db4e5 × 2 cu-yl28hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 82
82 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 83
83 heating cop curve.
Page 84
84 11.2.2.2. Cs-f18db4e5 × 2 cu-yl34hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 85
85 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 86
86 heating cop curve.
Page 87
87 11.2.2.3. Cs-f24db4e5 cu-yl24hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 88
88 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 89
89 heating cop curve.
Page 90
90 11.2.2.4. Cs-f24db4e5 × 2 cu-yl43hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 91
91 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 92
92 heating cop curve.
Page 93
93 11.2.2.5. Cs-f28db4e5 cu-yl28hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 94
94 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 95
95 heating cop curve.
Page 96
96 11.2.2.6. Cs-f34db4e5 cu-yl34hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 97
97 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 98
98 heating cop curve.
Page 99
99 11.2.2.7. Cs-f43db4e5 cu-yl43hbe5 heating capacity curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 2 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.84 0.88 0.96 1 1 1 1.
Page 100
100 heating power consumption curve outdoor intake air ambient temperature (d.B./ °c) -15 °c -10 °c -5 °c 0 °c 5 °c 7 °c 10 °c 15 °c >15 °c heating capacity compensation coefficient 0.93 0.93 0.92 0.86 0.97 1 1 1 1.
Page 101
101 heating cop curve.
Page 102
102 11.3. Safety device 11.3.1. Outdoor unit 1mpa = 10.2kgf/cm 2 outdoor unit heat pump model 50hz cu-yl24hbe5 cu-yl28hbe5 cu-yl34hbe5 cu-yl43hbe5 for refrigerant cycle high pressure off mpa 4.15 4.15 4.15 4.15 switch on mpa 3.3 3.3 3.3 3.3 for compressor over current protection for cooling mode ct1...
Page 103
103 11.4. Operating characteristics model main power source compressor motor indoor unit fan motor (note) outdoor unit fan motor electrical data (50hz) voltage frequency s.C. R.C. (a) ipt (kw) r.C. Ipt r.C. Ipt current (a) power consumption (kw) (v) (hz) (a) cool / heat cool / heat (a) (kw) (a) (kw)...
Page 104
104 11.5. Fan performance 11.5.1. Cs-f24db4e5 cu-yl24hbe5 (note) indoor fm is dc brushless motor current and power consumption including the indoor p.C.B. Outdoor fm is ac motor. 11.5.2. Cs-f28db4e5 cu-yl28hbe5 (note) indoor fm is dc brushless motor current and power consumption including the indoor...
Page 105
105 11.5.3. Cs-f34db4e5 cu-yl34hbe5 (note) indoor fm is dc brushless motor current and power consumption including the indoor p.C.B. Outdoor fm is ac motor. 11.5.4. Cs-f43db4e5 cu-yl43hbe5 (note) indoor fm is dc brushless motor current and power consumption including the indoor p.C.B. Outdoor fm is ...
Page 106
106 11.6. Discharge and suction pressure 11.6.1. Cs-f24db4e5 cu-yl24hbe5 operation mode : cooling hp indoor temp (wb) outdoor temp (db) 16 18 20 22 -5 1.81 1.89 1.98 2.08 0 1.86 1.94 2.03 2.13 10 1.99 2.07 2.16 2.26 20 2.19 2.27 2.36 2.46 30 2.59 2.67 2.76 2.86 35 2.79 2.87 2.96 3.06 40 2.99 3.07 3....
Page 107
107 11.6.2. Cs-f24db4e5 cu-yl24hbe5 operation mode : heating hp indoor temp (db) outdoor temp (wb) 15 20 25 -15 1.90 1.97 2.17 -10 2.00 2.07 2.27 -6 2.13 2.21 2.41 1 2.21 2.29 2.49 6 2.33 2.40 2.60 10 2.48 2.55 2.75 15 2.68 2.75 2.95 18 2.92 2.99 3.19 lp indoor temp (db) outdoor temp (wb) 15 20 25 -...
Page 108
108 11.6.3. Cs-f28db4e5 cu-yl28hbe5 operation mode : cooling hp indoor temp (wb) outdoor temp (db) 16 18 20 22 -5 1.94 2.02 2.11 2.26 0 1.99 2.07 2.16 2.31 10 2.12 2.2 2.29 2.44 20 2.32 2.4 2.49 2.64 30 2.72 2.8 2.89 3.04 35 2.92 3 3.09 3.24 40 3.12 3.2 3.29 3.44 43 3.32 3.4 3.49 3.64 lp indoor temp...
Page 109
109 11.6.4. Cs-f28db4e5 cu-yl28hbe5 operation mode : heating hp indoor temp (db) outdoor temp (wb) 15 20 25 -15 1.99 2.06 2.26 -10 2.09 2.16 2.36 -6 2.22 2.30 2.50 1 2.30 2.38 2.58 6 2.42 2.49 2.69 10 2.57 2.64 2.84 15 2.77 2.84 3.04 18 3.01 3.08 3.28 lp indoor temp (db) outdoor temp (wb) 15 20 25 -...
Page 110
110 11.6.5. Cs-f34db4e5 cu-yl34hbe5 operation mode : cooling hp indoor temp (wb) outdoor temp (db) 16 18 20 22 -5 2.08 2.16 2.25 2.35 0 2.13 2.21 2.30 2.40 10 2.26 2.34 2.43 2.53 20 2.46 2.54 2.63 2.73 30 2.86 2.94 3.03 3.13 35 3.06 3.14 3.23 3.33 40 3.26 3.34 3.43 3.53 43 3.46 3.54 3.63 3.73 lp ind...
Page 111
111 11.6.6. Cs-f34db4e5 cu-yl34hbe5 operation mode : heating hp indoor temp (db) outdoor temp (wb) 15 20 25 -15 2.08 2.16 2.36 -10 2.18 2.26 2.46 -6 2.32 2.40 2.60 1 2.40 2.48 2.68 6 2.51 2.59 2.79 10 2.66 2.74 2.94 15 2.86 2.94 3.14 18 3.10 3.18 3.38 lp indoor temp (db) outdoor temp (wb) 15 20 25 -...
Page 112
112 11.6.7. Cs-f43db4e5 cu-yl43hbe5 operation mode : cooling hp indoor temp (wb) outdoor temp (db) 16 18 20 22 -5 1.70 1.78 1.87 1.97 0 1.75 1.83 1.92 2.02 10 1.88 1.96 2.05 2.15 20 2.08 2.16 2.25 2.35 30 2.48 2.56 2.65 2.75 35 2.68 2.76 2.85 2.95 40 2.88 2.96 3.05 3.15 43 3.08 3.16 3.25 3.35 lp ind...
Page 113
113 11.6.8. Cs-f43db4e5 cu-yl43hbe5 operation mode : heating hp indoor temp (db) outdoor temp (wb) 15 20 25 -15 2.27 2.34 2.54 -10 2.37 2.44 2.64 -6 2.50 2.58 2.78 1 2.58 2.66 2.86 6 2.69 2.77 2.97 10 2.84 2.92 3.12 15 3.04 3.12 3.32 18 3.28 3.36 3.56 lp indoor temp (db) outdoor temp (wb) 15 20 25 -...
Page 114
114 12 exploded view and replacement parts list 12.1. Outdoor unit.
Page 115
115 no. Part description qty cu-yl24hbe5 cu-yl28hbe5 1 base pan ass’y 1 cwd52k1190 ← 2 compressor 1 5kd184xaa21 ← 3 bushing-compressor mount 3 cwh50055 ← 4 nut-compressor mount 3 cwh561049 ← 5 packing 3 cwb81043 ← 6 crankcase heater 1 cwa341047 ← 7 condenser complete 1 cwb32c2409 cwb32c2369 8 tube a...
Page 116
116.
Page 117
117.
Page 118
118.
Page 119
119 no. Part description qty cu-yl34hbe5 1 base pan ass’y 1 cwd52k1194 2 compressor 1 5kd240xcc21 3 anti-vibration bushing 3 cwh50055 4 nut for comp. Mount. 3 cwh561049 5 packing 3 cwb811017 6 crankcase heater 1 cwa341012 7 condenser complete 1 cwb32c2549 9 discharge muffler 1 cwb121013 10 high pres...
Page 120
120 all parts are supplied from phaam, malaysia (vendor code: 061) 62 installation instruction 1 cwf613432.
Page 121
121.
Page 122
122.
Page 123
123.
Page 124
124 no. Part description qty cu-yl43hbe5 1 base pan ass’y 1 cwd52k1193 2 compressor 1 5jd420xaa22 3 anti-vibration bushing 3 cwh50055 4 nut for comp. Mount. 3 cwh561049 5 packing 3 cwb811017 6 crankcase heater 1 cwa341046 7 condenser complete 1 cwb32c2382 8 sound-proof material 1 cwg302266 9 dischar...
Page 125
125 all parts are supplied from phaam, malaysia (vendor code: 061) [phaam] printed in malaysia ssyw0803 - 00 54 handle 2 cwe161008 56 magnetic switch 1 cwa001023 57 tube ass’y (strainer, cap. Tube and exp. Valve) 1 cwt025560 59 spring for sensor 4 cwh711010 61 expantion valve 1 cwb051020j 62 install...