Equithermal mode - curve slope
Press the
button -
letter E with the characters
(0) through to (9) attached
will appear on the display.
By pressing the
but-
tons, select the required
equithermal curve. The cur-
ve´s slope grows with the growing number
(E0
By pressing the
.button, the selecti-
on is saved in the memory.
Note:
Equithermal control requires an ex-
ternal sensor to be connected to the boi-
ler, which must not be set to the SUMMER
mode.
Attention:
Boiler does heating with maxi-
mal power on one hour after installation of
the outdoor sensor. All settings are igno-
red in this time except room thermostat (if
is connected).
Equithermal mode – paralel curve
shift
If previous parameter E
was confirmed by pres-
sing the
button
- letter P with the chara-
cters (0) through to (9)
attached will apear on
display. By pressing the
buttons, select the required shift
(see fig. 3, table 1). For beginning setting
choose the parameter P5, which respond
to outdoor temperature 15 °C (see table
1, fig. 3).
Note:
If boiler reaches the reference tem-
perature, then heats system by minimal
temperature (38 °C) till outdoor tempe-
rature increase at 3 °C, then is heating
switched-off (see table 1 - switch-off tem-
perature).
fig. 3
Equithermal curves
„P“ parameter
0
1
2
3
4
5
6
7
8
9
Reference temp. °C
6
7
9
11
13
15
17
19
21
23
Switch-off temp. °C
9
10
12
14
16
18
20
22
24
26
Table 1