Operating pressure in the heating
system
The heating system (measured on the
boiler) must be filled at least to the hyd-
raulic pressure of 1 bar (corresponds to
a 10 m hydrostatic water column). We re-
commend that you maintain the pressure
within the range 1 – 2 bar. The expansion
vessel capacity is sufficient for up to 70 l
of heating water in the heating system (at
temperature 85 °C).
HeW expansion vessel
Before filling the heating system up, check
pressure in the expansion vessel. The ini-
tial pressure inside the expansion vessel
should be 0.2 – 0.3 bar lower than the as-
sumed pressure in the heating system.
If the heating system is already filled, shut
the HeW valves located underneath the
boiler and, using the drainage valve, relie-
ve the boiler from pressure. Then you can
check the expansion vessel pressure and
if necessary increase the pressure.
Important:
Make sure that the expansion
vessel capacity is sufficient for the volume
of water in the heating system (see instal-
lation design documentation).
Domestic HoW expansion vessel
The expansion vessel is used to balance
the water pressure in the tank. The pres-
sure in the expansion vessel for hot water
should be 0.2 – 0.3 bar higher than the
real HoW pressure in the mains. When
checking the pressure proceed just as for
the HeW expansion vessel.