Quadra-Fire 31I-ACC Installation manual - page 25
April 9, 2014
7044-225B
25
31-I ACC
Figure 25.1
Spark Arestor Cap
Roof Flashing
Storm Collar
Joist Shield/Firestop
Double Wall
Connector Pipe
8. Burn wood only. Other types of fuels may generate
poisonousgases(e.g.,carbonmonoxide).
9. Ifunitburnspoorlywhileanexhaustblowerisoninhome,
(i.e.,rangehood),increasecombustionair.
10. InstallationshallbeinaccordancewiththeManufacturers
Home&SafetyStandard(HUD)CFR3280,Part24.
NOTICE:
• Offsetsfromthevertical,notexceeding45°,areallowed
perSection905(a)oftheUniformMechanicalCode(UMC).
• Offsetsgreaterthan45°areconsideredhorizontalandare
alsoallowed,providingthehorizontalrundoesnotexceed
75%oftheverticalheightofthevent.
• Construction,clearanceandterminationmustbeincom-
pliancewiththeUMCTable9C.Thisinstallationmustalso
comply with NFPA 211.
NOTICE:Topsectionsofchimneymustberemovabletoallow
maximumclearanceof13.5feet(411cm)fromgroundlevel
for transportation purposes.
1. Anoutsideairinletmustbeprovidedforcombustionand
mustremainclearofleaves,debris,iceand/orsnow.It
mustbeunrestrictedwhileunitisinusetopreventroom
airstarvationwhichcancausesmokespillageandan
inabilitytomaintainafire.Smokespillagecanalsoset
off smoke alarms.
2. Unitmustbesecuredtothemobilehomestructureat
twoattachmentpoints.Removeboltsfromeachside
ofinsertanduseplumberstapetosecuretostructure
(awashermayberequired).Re-installbolts.
3. Unitmustbegroundedwith#8solidcoppergrounding
wireorequivalentandterminatedateachendwithN.E.C.
approvedgroundingdevice.
4. The factory-built fireplace must meet (UM)84-HUD
requirements for outside combustion air supply to
the fireplace fire chamber and the chimney must be
listedtoUL103HToralistedUL-1777fulllengthsix
inch(152mm)diameterlinermustbeused.Itmustbe
equippedwithasparkarrestorcapandtheoutsideair
mustbeinstalledontheinsert.
5. Refer to
pages 7-8 of this manual for clearance to
combustibles and floor protections requirements.
All
clearancesmustbefollowedprecisely.
6. Use silicone to create an effective vapor barrier at
the location were the chimney or other component
penetratestotheexteriorofthestructure.
7. Followthechimneyandchimneyconnectormanufacturer’s
instructionswheninstallingthefluesystemforuseina
mobilehome.
CAUTION
THESTRUCTURALINTEGRITYOFTHEMOBILEHOME
FLOOR,WALLANDCEILING/ROOFMUSTBEMAINTAINED
DoNOTcutthrough:
• Floorjoist,wall,studsorceilingtrusses.
•
Any supporting material that would affect the structural
integrity.
• NEVERINSTALLINASLEEPINGROOM.
Consumesoxygenintheroom.
WARNING
Asphyxiation Risk.
WARNING
Donotdrawoutsidecombustionairfrom:
• Wall,floororceilingcavity
• Enclosedspacesuchasanatticorgarage
• Closeproximitytoexhaustventsorchimneys.
Fumes or odor may result
Fire Risk.
Asphyxiation Risk.
6
Mobile Home Installation