Range Senator RFB006 6kW Installation And User Instructions Manual - page 25
Manual is about: electric flow boiler
of
32
Model
Current@240v Drawn
Suggested MCB Rating
6kW
25.00 Amp
30
9kW
37.50 Amp
45
11kW
45.83 Amp
50
12kW
50.00 Amp
63
TECHNICAL SPECIFICATION
Output Temperature Control Range: 65°C to 80°C.
Operating voltage 200V -245V 50Hz.
Pump supply fuse (internal) T 2A 240v -20x5mm.
‘DEMAND’ control input signal requires 200v -245v 50Hz.
‘DEMAND’ control input signal draws less than 0.25A. 10mA typical.
Optical isolation Between the control signals and the boiler supply.
High limit switches trip @ 90°C ± 4°C.
No of Elements
3kw
2kw
6kW
2
220v
230v
240v
22.92A
23.96A
25.00A
5.04kW
5.51kW
6.00kW
9kW
3
220v
230v
240v
34.38A
35.94A
37.50A
7.56kW
8.27kW
9.00kW
11kW
3
1
220v
230v
240v
42.01A
43.92A
45.83A
9.24kW
10.10kW
11.00kW
12kW
4
220v
230v
240v
45.83A
47.92A
50.00A
10.08kW
11.02kW
12.00kW
25