Raypak D-2 Power Vent Operating And Installation Instructions

Manual is about: For 206A, 207A, 266A; 267A; 336A; 406A 407A Swimming Pool & SPA Heaters

Summary of D-2 Power Vent

  • Page 1

    Operating and installation instructions models 185, 265, 335, 405 swimming pool and spa heaters 181/182, 260/261, 330/331, 400/401 water heaters and boilers d-2 power vent (for electronic ignition models only) catalog no. 6000.57d effective: 10-26-06 replaces: 03-15-03 for your safety do not store o...

  • Page 2

    Power vent assembly installation, start-up and operation 1. Receiving equipment on receipt of your equipment it is suggested that you visually check for external damage to the carton. If the carton is damaged, it is suggested that a note be made on the bill of lading when signing for equipment. Remo...

  • Page 3

    3 3. Installation requirements the equipment must be installed in accordance with local codes, or in the absence of local codes with the latest edition of the national fuel gas code, ansi z223.1, the national electrical code, ansi/nfpa 70. The equipment shall be installed in accordance with those in...

  • Page 4

    4 wiring a powervent assembly to an appliance with iid ignition. Warning: disconnect all electrical power to the unit before servicing to avoid potential shock injury or damage to the unit. To change voltages, follow wiring diagram for correct voltage connections. Improper wiring connections can bur...

  • Page 5

    Venting the vent pipe must be the same size or larger than what is indicated. The d-2 power vent are capable of 360-degree discharge rotation and operate with a positive vent static pressure and with a vent gas temperature less than 400°f. The total length of horizontal run shall not exceed an equiv...

  • Page 6

    6 the raypak power vent operates with a positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent and as such it is listed as a category iii appliance. Exception: when a power vent is connected to a vertical vent of sufficient height to gen...

  • Page 7

    7 185-405 pool heater (atmospheric).

  • Page 8

    8 185-405 pool heater (low nox).

  • Page 9

    9 182-260 wh1 (atmospheric).

  • Page 10

    181-261 wh1 (low nox) 10

  • Page 11

    Sequence of operation on call for heat, the d-2 power vent fan (and appliance pump) start. When the flow switch circuits close, the ignition system consisting of an electronic spark module, pilot gas system and flame sensor, are energized. When draft proving switch closes and all safety circuits are...

  • Page 12

    Start up procedures the water system, the gas system and the electrical system for the heater should be completed and checked as per the heater installation manual and associated documents. 1. Turn on power to the heater with the manual main gas valve and pilot gas valve off. The electric power supp...

  • Page 13

    Illustrated parts list 13 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15.

  • Page 14

    Raypak, inc., 2151 eastman avenue, oxnard, ca 93030 (805) 278-5300 fax (800) 872-9725 raypak canada ltd, 2805 slough street, mississauga, ontario, canada l4t 1g2 (905) 677-7999 fax (905) 677-8036 raypak australia pty. Ltd, 7 geddes st., mulgrave, victoria, australia 3170 (6139) 560 4944 fax (6139) 5...