Table7.2belowgivessomeexamplesofC-Ratespecificationsandapplications:
tABLe 7.2: DiScHARGe cURRent RAteS - “c-RAteS”
Hours of discharge time “t”
till the “end Point Voltage”
c-Rate Discharge current in Amps
example of c-Rate
Discharge currents
for 100 Ah battery
Fraction
Decimal
Subscript
0.5Hrs.
2C
2C
2C
200A
1Hrs.
1C
1C
1C
100A
5Hrs.
C/5
0.2C
C5
20A
8Hrs.
(UPSapplication)
C/8
0.125C
C8
12.5A
10Hrs.
(Telecomapplication)
C/10
0.1C
C10
10A
20Hrs.
(Automotiveapplication)
C/20
0.05C
C20
5A
100Hrs.
C/100
0.01C
C100
1A
note: Whenabatteryisdischargedoverashortertime,itsspecified“C-Rate”dis-
chargecurrentwillbehigher.forexample,the“C-Rate”dischargecurrentat5Hour
dischargeperiodi.e.0.2C/C5/C/5Ampswillbe4timeshigherthanthe“C-Rate”
dischargecurrentat20Hourdischargeperiodi.e.0.05C/C20/C/20Amps
.
charging / Discharging curves
fig.7.1(page19)showsthecharginganddischargingcharacteristicsofatypical,6cell,
12V,LeadAcidbatteryatelectrolytetemperatureof80°f/26.7°C.Thecurvesshowthe
%StateofCharge(X-axis)versusterminalvoltage(Y-axis)duringcharginganddischarg-
ingatdifferentC-Rates.for24Vbattery,multiplyvoltageonY-axisby2for48Vbattery,
multiplyvoltageonY-axisby4(Please note that X-axis shows % State of Charge. State
of Discharge will be = 100% - % State of Charge). These curves will be referred to in
subsequentexplanations.
Reduction in Usable capacity at Higher Discharge Rates –
typical in inverter Application
Asstatedabove,theratedcapacityofthebatteryinAhisnormallyapplicableatadis-
chargerateof20Hours.Asthedischargerateisincreasedasincaseswheretheinverters
aredrivinghighercapacityloads,theusablecapacityreducesdueto“PeukertEffect”.
ThisrelationshipisnotlinearbutismoreorlessaccordingtotheTable7.3(page19).