Samlexpower PST-1000-12 Owner's manual - Dc Side Connections
30 | SAMLEX AMERICA INC.
- Mount horizontally on a horizontal surface - above a horizontal surface
(e.g.tabletoporashelf).
- Mount horizontally on a vertical surface – The unit can be mounted on a vertical
surface(likeawall)withthefanaxishorizontal(fanopeningfacingleftorright).
WARninG!
MountingtheunitverticallyonaverticalsurfaceisNoTallowed(fanopening
facingupordown).Asexplainedabove,thisistopreventfallingofobjectsinto
the unit through the fan opening when the fan opening faces up. If fan open-
ingfacesdown,hotdamagedcomponentmayfallout.
Dc Side connections
Preventing Dc input over Voltage
ItistobeensuredthattheDCinputvoltageofthisunitdoesnotexceed16.5VDCfor
the12-Vbatteryversionsand33.0VDCforthe24-Vbatteryversionstopreventperma-
nent damage to the unit. Please observe the following precautions:
- Ensurethatthemaximumchargingvoltageoftheexternalbatterycharger/alterna-
tor/solarchargecontrollerdoesnotexceed16.5VDCforthe12Vbatteryversionand
33.0VDCforthe24-Vbatteryversion
- Donotuseunregulatedsolarpanelstochargethebatteryconnectedtothisunit.
Underopencircuitconditionsandincoldambienttemperatures,theoutputofthe
solarpanelmaybe>44VDC.Alwaysuseachargecontrollerbetweenthesolarpanel
and the battery.
- WhenusingDiversionChargeControlModeinachargecontroller,thesolar/wind/
hydrosourceisdirectlyconnectedtothebatterybank.Inthiscase,thecontrollerwill
divertexcesscurrenttoanexternalload.Asthebatterycharges,thediversionduty
cyclewillincrease.Whenthebatteryisfullycharged,allthesourceenergywillflow
into the diversion load if there are no other loads. The charge controller will discon-
nectthediversionloadifthecurrentratingofthecontrollerisexceeded.Disconnec-
tionofthediversionloadmaydamagethebatteryaswellastheinverterorotherDC
loads connected to the battery due to high voltages generated during conditions of
highwinds(forwindgenerators),highwaterflowrates(forhydrogenerators).Itis,
therefore,tobeensuredthatthediversionloadissizedcorrectlytopreventtheabove
over voltage conditions.
- Donotconnectthisunittoabatterysystemwithavoltagehigherthantheratedbat-
teryinputvoltageoftheunit(e.g.donotconnectthe12Vversionoftheunitto24V
or48VBatterySystem)
Preventing Reverse Polarity on the input Side
!
cAUtion!
Damagecausedbyreversepolarityisnotcoveredbywarranty!Whenmaking
batteryconnectionsontheinputside,makesurethatthepolarityofbattery
connectionsiscorrect(ConnectthePositiveofthebatterytothePositivetermi-