seCtIOn 10 |
Protections
The inverter has been provided with protections detailed below:
overload / Short circuit Shut Down
Theinvertercanprovideahigherthannormalinstantaneouspower(<1second)limited
tothesurgepowerratingoftheinverter.Also,theinvertercanprovidecontinuous
power limited to the continuous power rating of the inverter. If there is an overload
beyondthesespecifiedlimits,theACoutputoftheunitwillbeshutdownpermanently.
StatusLED(2)willturnoRANGEandbuzzeralarmwillsound.Theunitwillbelatchedin
thisshutdownconditionandwillrequiremanualreset.Toreset,switchoff the power
oN/offswitch,waitfor3minutesandthenswitchoN again. before switching oN
again,removethecauseoftheshutdown.
Warning Alarm - Low Dc input Voltage
ThevoltageattheDCinputterminalswillbelowerthanthevoltageatthebatteryter-
minals due to voltage drop in the battery wires and connectors. The drop in the voltage
attheDCinputterminalsoftheinvertercouldbeduetolowerbatteryvoltageordue
toabnormallyhighdropinthebatterywiresifthewiresarenotthickenough(Please
read “Section 8, Installation; DC SIDE CONNECTIONS; Connection From the Batteries To
the DC Input Side of The Unit – Wire and External Fuse Sizes”).IfthevoltageattheDC
inputterminalsfallsbelow10.5Vfor12Vversionsor21.0Vfor24Vversions,abuzzer
alarm will be sounded. The StatusLED(2)willcontinuetobeGREENandtheACoutput
voltage would continue to be available. This warning buzzer alarm indicates that the
battery is running low and that the inverter will be shut down after sometime if the
voltage at the inverter terminals further drops to 10 V for 12 V versions or 20V for 24V
versions.
Low Dc input Voltage Shut Down
IfthevoltageattheDCinputterminalsfallsbelow10Vfor12Vversionsor20Vfor24V
versions,theACoutputisshutdown.BuzzeralarmissoundedandtheStatusLED(2)
willturnoRANGE.
TheunitwillresetautomaticallywhentheDCinputvoltagerises>11.5Vfor12Vver-
sionsand>23Vfor24Vversions
High Dc input Voltage Shutdown
IfthevoltageattheDCinputterminalsexceeds16.5Vfor12Vversionsor33Vfor
24Vversions,theinverterwillbeshutdowntemporarily.TheStatusLED(2)willturn
oRANGEandtherewillbebuzzeralarm.Theunitwillberesetautomaticallywhenthe
voltagedropsdownto<16.5Vfor12Vversionsandto<33Vfor24Vversions.
over-temperature Shut Down
In case of failure of the cooling fan or in the case of inadequate heat removal due to
higherambienttemperatures/insufficientairexchange,thetemperatureinsidethe