Samsung AC***MNADKH Installation Manual - page 21
21
English
Ins
tallation
Setting the indoor unit addresses
1
Make sure that the power is supplied to the indoor unit. If the indoor unit is not plugged in, it must include a power
supply.
2
The panel(display ) should be connected to an indoor unit to receive option.
3
Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
4
Assign an indoor unit address by wireless remote controller.
– The initial indoor unit ADDRESS is set as "MAIN : 0, RMC : 0".
– Set Main and RMC Address only the setting is required.
– There is no need to assign the indoor unit Main Address if the outdoor unit is addressing automatically.
The indoor unit Main address will follow the outdoor unit's automatically.
– Assign 12 digit when setting the indoor unit address.
– No need to assign SEG4, 5, 8, 10 which are non applicable. Even though those segments are set, they will be
ignored.
– If you set the applicable segments with numbers other than the indiciated, the initial setting will be maintained.
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Setting Main address
RESERVED
RESERVED
The unit digit of
an indoor unit
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
A
0
No Main
address
0~3(ACN*)
Details
1
Main address
setting mode
0~4
(AJN*)
A
single
digit
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
RESERVED
Setting RMC address
RESERVED
Group
channel(*16)
Group address
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
1
0
No RMC
address
RMC1
0~2
RMC2
0~F
1
RMC address
setting mode
*SEG6: AJN** models should check maximum installation indoor unit number of outdoor unit.
(Indoor1: 0, Indoor2: 1, ~)
CAUTION
•
When “A”~”F” is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
•
If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option
value of SEG6.
•
If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of
SEG11~12.
Example) If you want to set as "MAIN: 3, CHANNEL: 1, RMC: B",