Samsung AC071MN4PKH Installation Manual - page 19
19
Ins
tallation Pr
oc
edur
e
English
5 Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Three or more layers of insulation are required.
Method 1
Method 2
Insulation tape
40 mm
35 mm
Insulation tape
6 Apply heat to the contraction tube to contract it.
Contraction tube
7 After tube contraction work is completed, wrap it with
the insulation tape to finish.
Insulation tape
CAUTION
ŷ Make sure that the connection parts are not exposed
to outside.
ŷ Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials that
have the same level of withstand voltage with the
power cable. (Comply with the local regulations on
extensions.)
WARNING
ŷ In case of extending the electric wire, please DO NOT
use a round-shaped Pressing socket.
– Incomplete wire connections can cause electric
shock or a fire.
Step 14 Setting the indoor unit
addresses and the installation options
You cannot set both of the indoor unit addresses and
the installation options in a batch: set both of them
respectively.
Common steps for setting the addresses and
options
AR-KH00E remote control (for 360 cassette only)
Temperature
button
Timer button
Wheel
Mode button
Setting the
option values
Entering the
mode for setting
the options
NOTE
ŷ The remote control display may vary depending on
the model.
1 Enter the mode for setting the options:
a Remove the batteries from the remote control.
b While holding down the
(Temp) and
(Timer) buttons simultaneously, insert the
batteries into the remote control.
c Make sure that you are entered to the mode for
setting the options: